EMR-5000
IM02602012E
Digital Inputs
Max. Input Voltage:
300 Vdc / 259 Vac
Input Current:
DC <4 mA
AC <16 mA
Reaction Time:
<20 ms
Fallback Time:
Shorted inputs
Open inputs
<30 ms
<90 ms
(Safe State of the Digital Inputs)
Switching Thresholds:
Un = 24 Vdc, 48 Vdc, 60 Vdc,
110 Vac / dc, 230 Vac / dc
Un = 24 Vdc
Switching Threshold 1 ON:
Switching Threshold 1 OFF:
Min. 19.2 Vdc
Max. 9.6 Vdc
Un = 48 V / 60Vdc
Switching Threshold 2 ON:
Switching Threshold 2 OFF:
Min. 42.6 Vdc
Max. 21.3 Vdc
Un = 110 / 120 Vac / dc
Switching Threshold 3 ON:
Switching Threshold 3 OFF:
Min. 88.0 Vdc / 88.0 Vac
Max. 44.0 Vdc / 44.0 Vac
Un = 230 / 240 Vac / dc
Switching Threshold 4 ON:
Switching Threshold 4 OFF:
Min. 184 Vdc / 184 Vac
Max. 92 Vdc / 92 Vac
Terminals:
Screw-type terminal
www.eaton.com
931
COM
DI8
DI2
DI1
COM
DI8
DI2
DI1
L+
L-
L+
L-
Open inputs
Shorted inputs
Содержание EMR-5000
Страница 62: ...EMR 5000 IM02602012E Ethernet RJ45 Terminal Marking www eaton com 62 1 8 TxD TxD RxD N C N C RxD N C N C...
Страница 271: ...EMR 5000 IM02602012E Fault Recorder Module Signals Signal Description Res record Signal Delete Record www eaton com 271...
Страница 524: ...EMR 5000 IM02602012E Motor Protection Curves Motor Protection Curve Example 1 www eaton com 524...
Страница 525: ...EMR 5000 IM02602012E Motor Protection Curve Example 2 without RTDs www eaton com 525...
Страница 526: ...EMR 5000 IM02602012E Motor Protection Curve Example 3 with RTDs www eaton com 526...
Страница 930: ...EMR 5000 IM02602012E Real Time Clock Running Reserve of the Real Time Clock 1 year min www eaton com 930...