Instructional Leafl et 

IL03901003E

Effective May 2011

DS7 series soft start controllers, Frame 1 (4–12A) 
  
  

EATON CORPORATION

 www.eaton.com

Operations 

24 Vac/Vdc, 110/230 Vac control voltage is applied to terminal U

• 

s

Line voltage is applied to the starter by closing the mains 

• 

contactor 

The soft start controller issues a RUN command by applying 

• 

24 Vac/Vdc, 110/230 Vac to teA1. Contacts 13 and –A2 
will close when the end of the ramp time is reached (TOR)

Bypass relays close at the end of ramp time + ~0.18 seconds. It is 

ote: 

N

important to correctly set the ramp time, so the bypass relays will close 
within 5 seconds after the motor has achieved rated RPM.

To remove the RUN command, remove control voltage from 

• 

teA1 

If ramp STOP time is set to a value greater than 0 seconds, a 

• 

RAMP STOP will be performed

Adjusting the soft start controller parameters

There are three adjustments to the DS7 soft start controller:

t-Start = ramp time

• 

u-Start = initial voltage (torque)

• 

t-Stop = stop ramp time

• 

DS7 parameters

Table 10. 

Application

t-Start

t-Stop

u-Start

Breakaway 
Torque

Remarks

Crusher, empty at start

20s

56%

75%

Possible high inertia

Conveyor, horizontal, loaded

25s

30s

76%

150%

Conveyor, horizontal, unloaded

25s

30s

48%

50%

Chiller

5s

37%

25%

Piston compressor, unloaded

10s

64%

100%

Circular saw

20s

48%

50%

Possible high inertia

Ball mill

20s

48%

50%

Eccentric load

Mixer, liquids

10s

37%

40%

Mixer, dry materials

15s

56%

75%

Pump, piston

25s

30s

82%

175%

Possible high starting torque

Pump, centrifugal

10s

30s

37%

25%

Escalator

10s

48%

50%

Rotary compressor, unloaded

20s

42%

35%

Agitator

15s

42%

35%

Feed screw

20s

82%

175%

Possible high starting torque

Press, flywheel

25s

76%

150%

Possible high starting torque

Drier, rotating

20s

64%

100%

Blower, axial fan, flaps open

30s

37%

25%

Blower, centrifugal fan, valve open

30s

35%

20%

Содержание DS7 Series

Страница 1: ...specifications set forth by UL 508 IEC 60947 4 2 CE C Tick and CSA This leaflet covers basic installation and setup No publication can take into account every possible situation If you require further...

Страница 2: ...ARD Mounting hardware and torque specifications Table 1 Screw Size Flat and Lock Washer Quantity Torque Requirements Unit Weight Lbs kg M4 4 10 lb in 1 2 Nm 0 8 0 35 Environmental requirements Table 2...

Страница 3: ...TOB010BC1 XTOE020BCS XTPR010BC1 XTPAXTPCB DS7 340SX012NO N DS7 342SX012NO N Product selection kW ratings according to IEC 60947 4 2 Please refer to Application Note AP03901006E for additional informat...

Страница 4: ...13 A2 TOR Start and stop ramp functions Figure 5 Terminal designations Table 8 Terminal Description Us Control ground or circuit common Us Power of AC load A2 Common with Us A1 Run command 13 Top of...

Страница 5: ...will be performed Adjusting the soft start controller parameters There are three adjustments to the DS7 soft start controller t Start ramp time u Start initial voltage torque t Stop stop ramp time DS7...

Страница 6: ...ce failure if power is applied to these terminals and no LED s are illuminated Initialization GREEN 4x s pulse 1 8s RED 4x s pulse 1 8s alternating Control power is applied to terminals Us and A2 If t...

Страница 7: ...move the controller to an optimum location to reduce operating temperatures Over under temperature heat sink GREEN Continuous RED Continuous Temperature of the SCR heat sink is not within operating sp...

Страница 8: ...ers Instructional Leaflet IL03901003E Effective May 2011 DS7 series soft start controllers Frame 1 4 12A Service For additional information on this product please call the Eaton Technical Resource Cen...

Отзывы: