Instructional Leafl et
IL03901003E
Effective May 2011
DS7 series soft start controllers, Frame 1 (4–12A)
EATON CORPORATION
www.eaton.com
Storage
It is recommended that the unit be stored in its original shipping
box/crate until it is to be installed.
The unit should be stored in a location where:
The ambient temperature is between –13° to 140°F (–25° to 55°C)
•
The relative humidity is between 0% and 95%, noncondensing
•
The environment is dry, clean, and noncorrosive
•
The unit will not be subjected to high shock or vibration conditions
•
Mounting instructions
The DS7 solid-state soft start controller is easy to mount. It does
not require any special tools. To aid you with panel layout, refer to
the dimension drawings shown in
Figure 1
. Drill and tap holes per
mounting hole/slot locations as shown. To mount the unit, use all the
hardware specified in
Table 1
of this leaflet. Tighten to the specified
torque.
5.12
(130.0)
3.74
(95.0)
M4
1.38
(35.0)
1.78
(45.0)
4.80
(122.0)
4.92
(125.0)
Approximate Dimensions in Inches (mm)
4 to 12 ampere models
Figure 1.
DANGER—HIGH VOLTAGE
HAZARDOUS VOLTAGE CAN CAUSE ELECTRIC SHOCK AND BURNS. TO
AVOID SHOCK HAZARD, DISCONNECT ALL POWER TO THE CONTROLLER,
MOTOR, OR OTHER CONTROL DEVICES BEFORE ANY WORK IS PERFORMED
ON THIS EQUIPMENT. FAILURE TO DO SO WILL RESULT IN PERSONAL
INJURY, DEATH, OR SUBSTANTIAL PROPERTY DAMAGE.
DO NOT APPLY A DISCONNECT DEVICE ON THE OUTPUT OF THE DS7
SOFT START CONTROLLER UNLESS A MEANS TO TURN OFF THE DEVICE
WHEN DISCONNECT SWITCH IS OPEN IS UTILIZED. OPENING THE
DISCONNECT WHILE THE SOFT START CONTROLLER IS OPERATING MAY
CAUSE A MALFUNCTION. CLOSING THE DISCONNECT SWITCH WHILE THE
SOFT START CONTROLLER IS OPERATING WILL RESULT IN POTENTIAL
EQUIPMENT DAMAGE AND PERSONNEL HAZARD.
Mounting hardware and torque specifications
Table 1.
Screw Size +
Flat and Lock
Washer
Quantity
Torque
Requirements
Unit Weight
Lbs (kg)
M4
4
10 lb-in (1.2 Nm)
0.8 (0.35)
Environmental requirements
Table 2.
Description
Requirement
Operating temperature
32° to 104°F (0° to 40°C) up to 140°F (60°C) with
derating of 1% of rated current per Kelvin
Storage temperature
13° to 140°F (–25° to 60°C )
Elevation
Up to 1000m; up to 2000m with derating of 1% rated
current for each 100m
Humidity
Functional to 95% noncondensing
Operating orientation
Less than 30 degrees from horizontal
Minimum clearance—
Upper and lower
2.165 in (55 mm) to a wall, 0.984 in (25 mm) to an
upper and lower NZM1 (size 1), 1.378 in (35 mm)
to an NZM2 (size 2), consult documentation of the
breaker used (ionization emissions)
Minimum clearance—sides
0.0 in (0 mm)
Minimum clearance—face
0.198 in (5 mm)
Shock resistance
8g for 11 ms in any direction
Vibration resistance
2M2 EN 60721-3-2: 10g (3.5 mm amplitude,
9 to 200 Hz)
Environment
Suitable for installation in a pollution Degree 2
environment
Emissions
The device is suitable for use in industrial
environments in accordance with EN 55011/22
Class A
Power wiring
Using the wiring diagram in
Figure 2
and
Table 3
as guides, connect
the line and motor wiring in accordance with appropriate local and
national codes.
To provide optimum motor protection, the line and motor power wiring
ote:
N
should be tightly bundled and run perpendicular to the orientation of the DS7.
Soft start controller to motor cable length is not to exceed 325 ft (100m).
1
3
5
L1
L2
L3
2
4
6
T1
T2
T3
M
3~
DS7
Power wiring diagram
Figure 2.
Power wire sizing and torque requirements
Table 3.
Wire Size
Torque
Wire Strip Length
18–10 AWG
10.62 lb-in
10 mm
2 x 21–20 AWG
10.62 lb-in
10 mm
DANGER
HAZARDOUS VOLTAGE. WILL CAUSE DEATH OR SERIOUS INJURY.
HAZARDOUS VOLTAGE IS PRESENT IN THE OFF/STOP STATUS OF THE SOFT
START CONTROLLER WHEN THE LINE VOLTAGE IS ENERGIZED.