Instructional Leafl et 

IL03901003E

Effective May 2011

DS7 series soft start controllers, Frame 1 (4–12A) 

  
  

EATON CORPORATION

 www.eaton.com

Storage

It is recommended that the unit be stored in its original shipping 
box/crate until it is to be installed. 

The unit should be stored in a location where: 

The ambient temperature is between –13° to 140°F (–25° to 55°C) 

• 

The relative humidity is between 0% and 95%, noncondensing 

• 

The environment is dry, clean, and noncorrosive 

• 

The unit will not be subjected to high shock or vibration conditions 

• 

Mounting instructions

The DS7 solid-state soft start controller is easy to mount. It does 
not require any special tools. To aid you with panel layout, refer to 
the dimension drawings shown in 

Figure 1

. Drill and tap holes per 

mounting hole/slot locations as shown. To mount the unit, use all the 
hardware specified in 

Table 1

 of this leaflet. Tighten to the specified 

torque. 

5.12

(130.0)

3.74

(95.0)

M4

1.38

(35.0)

1.78

(45.0)

4.80

(122.0)

4.92

(125.0)

Approximate Dimensions in Inches (mm)

4 to 12 ampere models

Figure 1. 

 DANGER—HIGH VOLTAGE 

HAZARDOUS VOLTAGE CAN CAUSE ELECTRIC SHOCK AND BURNS. TO 
AVOID SHOCK HAZARD, DISCONNECT ALL POWER TO THE CONTROLLER, 
MOTOR, OR OTHER CONTROL DEVICES BEFORE ANY WORK IS PERFORMED 
ON THIS EQUIPMENT. FAILURE TO DO SO WILL RESULT IN PERSONAL 
INJURY, DEATH, OR SUBSTANTIAL PROPERTY DAMAGE.

DO NOT APPLY A DISCONNECT DEVICE ON THE OUTPUT OF THE DS7 
SOFT START CONTROLLER UNLESS A MEANS TO TURN OFF THE DEVICE 
WHEN DISCONNECT SWITCH IS OPEN IS UTILIZED. OPENING THE 
DISCONNECT WHILE THE SOFT START CONTROLLER IS OPERATING MAY 
CAUSE A MALFUNCTION. CLOSING THE DISCONNECT SWITCH WHILE THE 
SOFT START CONTROLLER IS OPERATING WILL RESULT IN POTENTIAL 
EQUIPMENT DAMAGE AND PERSONNEL HAZARD. 

Mounting hardware and torque specifications

Table 1. 

Screw Size + 
Flat and Lock 
Washer

Quantity

Torque 
Requirements

Unit Weight
Lbs (kg)

M4

4

10 lb-in (1.2 Nm)

0.8 (0.35)

Environmental requirements

Table 2. 

Description

Requirement

Operating temperature

32° to 104°F (0° to 40°C) up to 140°F (60°C) with 
derating of 1% of rated current per Kelvin

Storage temperature

13° to 140°F (–25° to 60°C )

Elevation

Up to 1000m; up to 2000m with derating of 1% rated 
current for each 100m

Humidity

Functional to 95% noncondensing

Operating orientation

Less than 30 degrees from horizontal

Minimum clearance—
Upper and lower

2.165 in (55 mm) to a wall, 0.984 in (25 mm) to an 
upper and lower NZM1 (size 1), 1.378 in (35 mm) 
to an NZM2 (size 2), consult documentation of the 
breaker used (ionization emissions)

Minimum clearance—sides

0.0 in (0 mm)

Minimum clearance—face

0.198 in (5 mm)

Shock resistance

8g for 11 ms in any direction

Vibration resistance

2M2 EN 60721-3-2: 10g (3.5 mm amplitude, 
9 to 200 Hz)

Environment

Suitable for installation in a pollution Degree 2 
environment

Emissions

The device is suitable for use in industrial 
environments in accordance with EN 55011/22 
Class A

Power wiring

Using the wiring diagram in 

Figure 2

 and 

Table 3

 as guides, connect 

the line and motor wiring in accordance with appropriate local and 
national codes.

To provide optimum motor protection, the line and motor power wiring 

ote: 

N

should be tightly bundled and run perpendicular to the orientation of the DS7. 
Soft start controller to motor cable length is not to exceed 325 ft (100m).

1

3

5

L1

L2

L3

2

4

6

T1

T2

T3

M

3~

DS7

Power wiring diagram

Figure 2. 

Power wire sizing and torque requirements

Table 3. 

Wire Size

Torque

Wire Strip Length

18–10 AWG

10.62 lb-in

10 mm

2 x 21–20 AWG

10.62 lb-in

10 mm

 DANGER

HAZARDOUS VOLTAGE. WILL CAUSE DEATH OR SERIOUS INJURY.

HAZARDOUS VOLTAGE IS PRESENT IN THE OFF/STOP STATUS OF THE SOFT 
START CONTROLLER WHEN THE LINE VOLTAGE IS ENERGIZED.

Содержание DS7 Series

Страница 1: ...specifications set forth by UL 508 IEC 60947 4 2 CE C Tick and CSA This leaflet covers basic installation and setup No publication can take into account every possible situation If you require further...

Страница 2: ...ARD Mounting hardware and torque specifications Table 1 Screw Size Flat and Lock Washer Quantity Torque Requirements Unit Weight Lbs kg M4 4 10 lb in 1 2 Nm 0 8 0 35 Environmental requirements Table 2...

Страница 3: ...TOB010BC1 XTOE020BCS XTPR010BC1 XTPAXTPCB DS7 340SX012NO N DS7 342SX012NO N Product selection kW ratings according to IEC 60947 4 2 Please refer to Application Note AP03901006E for additional informat...

Страница 4: ...13 A2 TOR Start and stop ramp functions Figure 5 Terminal designations Table 8 Terminal Description Us Control ground or circuit common Us Power of AC load A2 Common with Us A1 Run command 13 Top of...

Страница 5: ...will be performed Adjusting the soft start controller parameters There are three adjustments to the DS7 soft start controller t Start ramp time u Start initial voltage torque t Stop stop ramp time DS7...

Страница 6: ...ce failure if power is applied to these terminals and no LED s are illuminated Initialization GREEN 4x s pulse 1 8s RED 4x s pulse 1 8s alternating Control power is applied to terminals Us and A2 If t...

Страница 7: ...move the controller to an optimum location to reduce operating temperatures Over under temperature heat sink GREEN Continuous RED Continuous Temperature of the SCR heat sink is not within operating sp...

Страница 8: ...ers Instructional Leaflet IL03901003E Effective May 2011 DS7 series soft start controllers Frame 1 4 12A Service For additional information on this product please call the Eaton Technical Resource Cen...

Отзывы: