background image

3

Instructional Leafl et 

IL03901003E

Effective May 2011

DS7 series soft start controllers, Frame 1 (4–12A) 
  
  

EATON CORPORATION

 www.eaton.com

Product selection—horsepower ratings

Please refer to Application Note AP03901006E for additional information on proper size selection.

10 second ramp, one start per hour, 300% current limit at 40°C 

Table 4. 

Rated 
Current 
(A)

Motor Power (hp)

Maximum 
Allowable 
Breaker Size

Maximum 
Allowable 
Fuse Size

Recommended 
XTOB Overload 
(Direct Connect) 

Recommended 
XTOE Overload 

MMP 

Connection 
Kit to MMP

Catalog
Number

200V

230V

480V

3.7

0.75

0.75

2

HFD3015

15A Class RK5

XTOB004BC1

XTOE005BCS

XTPR004BC1

XTPAXTPCB

DS7-340SX004NO-N

 

DS7-342SX004NO-N

 

6.9

1.5

2

3

HFD3015

15A Class RK5

XTOB006BC1 

XTOE020BCS

XTPR6P3BC1

XTPAXTPCB

DS7-340SX007NO-N

 

DS7-342SX007NO-N

 

7.8

2

2

5

HFD3020

20A Class RK5

XTOB010BC1

XTOE020BCS

XTPR010BC1

XTPAXTPCB

DS7-340SX009NO-N

 

DS7-342SX009NO-N

 

11

3

3

7.5

HFD3030

20A Class RK5

XTOB012BC1

XTOE020BCS

XTPR012BC1

XTPAXTPCB

DS7-340SX012NO-N

 

DS7-342SX012NO-N

 

10 second ramp, one start per hour, 400% current limit at 40°C 

Table 5. 

Rated 
Current 
(A)

Motor Power (hp)

Maximum 
Allowable 
Breaker Size

Maximum 
Allowable 
Fuse Size

Recommended 
XTOB Overload 
(Direct Connect) 

Recommended 
XTOE Overload 

MMP 

Connection 
Kit to MMP

Catalog
Number

200V

230V

480V

3

0.5

0.5

1.5

HFD3015

15A Class RK5

XTOB004BC1

XTOE005BCS

XTPR004BC1

XTPAXTPCB

DS7-340SX004NO-N

 

DS7-342SX004NO-N

 

4.8

1

1

3

HFD3015

15A Class RK5

XTOB006BC1 

XTOE020BCS

XTPR6P3BC1

XTPAXTPCB

DS7-340SX007NO-N

 

DS7-342SX007NO-N

 

6.9

1.5

2

3

HFD3020

20A Class RK5

XTOB006BC1

XTOE020BCS

XTPR6P3BC1

XTPAXTPCB

DS7-340SX009NO-N

 

DS7-342SX009NO-N

 

9

2

2

5

HFD3030

20A Class RK5

XTOB010BC1

XTOE020BCS

XTPR010BC1

XTPAXTPCB

DS7-340SX012NO-N

 

DS7-342SX012NO-N

 

Product selection—kW ratings according to IEC 60947-4-2

Please refer to Application Note AP03901006E for additional information on proper size selection.

10 second ramp, one start per hour, 300% current limit at 40°C 

Table 6. 

Rated 
Current 
(A)

Motor Power (kW)

Maximum 
Allowable 
Breaker Size

Maximum 
Allowable 
Fuse Size

Recommended 
XTOB Overload 
(Direct Connect) 

Recommended 
XTOE Overload 

MMP 

Connection 
Kit to MMP

Catalog
Number

230V

400V

3.8

0.75

1.5

HFD3015

15A Class RK5

XTOB004BC1

XTOE005BCS

XTPR004BC1

XTPAXTPCB

DS7-340SX004NO-N

 

DS7-342SX004NO-N

 

7

1.5

3

HFD3015

15A Class RK5

XTOB006BC1 

XTOE020BCS

XTPR6P3BC1

XTPAXTPCB

DS7-340SX007NO-N

 

DS7-342SX007NO-N

 

9

2.2

4

HFD3020

20A Class RK5

XTOB010BC1

XTOE020BCS

XTPR010BC1

XTPAXTPCB

DS7-340SX009NO-N

 

DS7-342SX009NO-N

 

12

3

5.5

HFD3030

20A Class RK5

XTOB012BC1

XTOE020BCS

XTPR012BC1

XTPAXTPCB

DS7-340SX012NO-N

 

DS7-342SX012NO-N

 

10 second ramp, one start per hour, 400% current limit at 40°C 

Table 7. 

Rated 
Current 
(A)

Motor Power (kW)

Maximum 
Allowable 
Breaker Size

Maximum 
Allowable 
Fuse Size

Recommended 
XTOB Overload 
(Direct Connect) 

Recommended 
XTOE Overload 

MMP 

Connection 
Kit to MMP

Catalog
Number

230V

400V

2.5

0.33

1

HFD3015

15A Class RK5

XTOB004BC1

XTOE005BCS

XTPR004BC1

XTPAXTPCB

DS7-340SX004NO-N

 

DS7-342SX004NO-N

 

3.8

0.75

1.5

HFD3015

15A Class RK5

XTOB006BC1 

XTOE020BCS

XTPR6P3BC1

XTPAXTPCB

DS7-340SX007NO-N

 

DS7-342SX007NO-N

 

7

1.5

3

HFD3020

20A Class RK5

XTOB006BC1

XTOE020BCS

XTPR6P3BC1

XTPAXTPCB

DS7-340SX009NO-N

 

DS7-342SX009NO-N

 

9

2.2

4

HFD3030

20A Class RK5

XTOB010BC1

XTOE020BCS

XTPR010BC1

XTPAXTPCB

DS7-340SX012NO-N

 

DS7-342SX012NO-N

 

Notes

Actual motor FLAs vary. Verify these devices cover the motor specific FLA.

 

Selections are based on motor FLA value at 480V.

 

Not to be used with 230V.

 

24 Vac/Vdc device.

 

120/230 Vac device.

 

Содержание DS7 Series

Страница 1: ...specifications set forth by UL 508 IEC 60947 4 2 CE C Tick and CSA This leaflet covers basic installation and setup No publication can take into account every possible situation If you require further...

Страница 2: ...ARD Mounting hardware and torque specifications Table 1 Screw Size Flat and Lock Washer Quantity Torque Requirements Unit Weight Lbs kg M4 4 10 lb in 1 2 Nm 0 8 0 35 Environmental requirements Table 2...

Страница 3: ...TOB010BC1 XTOE020BCS XTPR010BC1 XTPAXTPCB DS7 340SX012NO N DS7 342SX012NO N Product selection kW ratings according to IEC 60947 4 2 Please refer to Application Note AP03901006E for additional informat...

Страница 4: ...13 A2 TOR Start and stop ramp functions Figure 5 Terminal designations Table 8 Terminal Description Us Control ground or circuit common Us Power of AC load A2 Common with Us A1 Run command 13 Top of...

Страница 5: ...will be performed Adjusting the soft start controller parameters There are three adjustments to the DS7 soft start controller t Start ramp time u Start initial voltage torque t Stop stop ramp time DS7...

Страница 6: ...ce failure if power is applied to these terminals and no LED s are illuminated Initialization GREEN 4x s pulse 1 8s RED 4x s pulse 1 8s alternating Control power is applied to terminals Us and A2 If t...

Страница 7: ...move the controller to an optimum location to reduce operating temperatures Over under temperature heat sink GREEN Continuous RED Continuous Temperature of the SCR heat sink is not within operating sp...

Страница 8: ...ers Instructional Leaflet IL03901003E Effective May 2011 DS7 series soft start controllers Frame 1 4 12A Service For additional information on this product please call the Eaton Technical Resource Cen...

Отзывы: