12.1.2 What to Inspect
First withdraw the breaker from the compartment.
Remove barriers. Remove arc chutes. If there is a
deposit of dust, blow clean with compressed air, if avail-
able. Wipe accessible areas with a clean dry cloth.
Inspect contacts.
Note: Switching and fault interruptions and the mak-
ing of motor inrush currents will cause some pitting
of the breaker contact parts. A large accumulation of
operations will give the contacts, especially the arc-
ing contacts, a mottled, dirty, eroded appearance.
This appearance is the normal result of arc burning
and in itself is no cause for concern.
Fig. 86 Contacts and Their Adjustment: DS-632 Breaker.