Instruction Booklet
IB 33-790-1J
Effective November 2010
Instructions for Low Voltage Power
Circuit Breakers Types DS and DSL
EaToN CorPoraTIoN www.eaton.com
8.7.6 Amptector Trip Unit Test Kit
8.7.6.1 General
The Amptector Trip Unit Test Kit consists of an external
power supply, current measuring device, and a precision
timer for field checking the operation of the unit. These
three functions have been combined into a single porta-
ble device housed in a convenient carrying case. It is
powered from a standard 120 volt, single phase, 60 Hz
outlet; and will furnish the high secondary currents to the
input of the Amptector unit to simulate primary fault con-
ditions on the circuit breaker.
8.7.6.2 Description
A long flexible cable terminated by an 11 prong polarized
plug connects to the test terminals of the Amptector trip
unit. A second cable connects to the source of input
power. Figures 75 and 76 show the tester and operating
controls. The ammeter is dual range and controlled by
the “Hi-Lo” switch. In the low range it reads 0-8 amps,
while the high range covers 0-80 amps. The timer reads
in seconds with the right hand digit (white) in tenths of
seconds. An external ammeter may be connected in the
output circuit through the terminals designated for this
purpose and the shorting link removed.
WHEN USING THE TEST KIT, THE BREAKER
MUST
NOT
BE IN THE CONNECTED POSITION BECAUSE
BREAKER WILL BE TRIPPED AND CAUSE DISRUP-
TION OF SERVICE. IT MAY BE IN EITHER THE TEST
OR DISCONNECTED POSITION, OR REMOVED
FROM ITS COMPARTMENT.
8.7.6.3 Operation
The complete testing and calibration of the Amptector trip
unit by means of the Test Kit is covered by the instruction
sheet (I.L. 33-791) included with the Test Kit.
Fig. 75 Amptector Trip Unit Test Kit (For Amptector I-A and II-A).
CAUTION