background image

Effective 8/2006

Page 5

I.L. 66A7534H04

1.4   Installing the CH Type-V Current Sensors

The internal components of the circuit breaker, and how
they are wired out to the breaker secondary contacts are
shown in Figures 1.4, 1.5, 1.6 and 2.3. Also refer to the
master connection diagram provided in Appendix C.

1.4.1   Installation Procedure

The CH Type-V Current Sensors/Rating Plug Kit supplied
with this breaker  must be installed and wired by the user.
The installation steps are as follows:

a. PRIMARY - Mount one CH Type-V current sensor on the
insulated bushing behind the circuit breaker. The bushing
must be rated for the system Lightning Impulse Withstand
Voltage (LIWV), and the ground (earth) shield terminal or
ground (earth) shield surface must be connected to the
ground (earth) bus. Confirm that the polarity mark (red dot)
on the front of the current sensor faces the circuit breaker.

b. SECONDARY - Connect secondary terminals of the
current sensor to the correct terminals in the switchgear
control circuit using #14 AWG Type SIS wire. Terminal X1
is the one nearest to the polarity mark. Refer to Appendix
C for distinction between Fixed and Drawout variations.
Consult manufacturer if length of wire to device exceeds 12
feet (3.7m).

c. Use ring terminals on current sensor terminals. Use
AMP #66598-2 female sockets to connect to breaker’s
secondary connector.

d. Ground (Earth) the non polarity terminal of each sensor.
Also Ground the bushing shield surfaces.

e. Install rating plug into the Digitrip 520V and 520MCV trip
units for the matching CH Type-V current sensors. Also
attach the  additional rating plug label to the circuit breaker
enclosure as a future reference indicating which CH Type-V
current sensors used in this application.

1.4.2   CH Type-V Current Sensor Functionality

The three CH Type-V current sensors are installed external
to the circuit breaker over the main circuit conductors by
means of  bushings equipped with a ground shield. The
current sensor rating defines the breaker rating (

I

n)... i.e.

1200A:1A sensors are used on a 1200A rated breaker.
There are four auxiliary current transformers with a ratio of
10:1 which further step down the rated current to 100 milli-
amperes, which is equivalent to 100% (

I

n) to the Digitrip.

The primary current sensors produce an output signal
proportional to the load current and furnish the Digitrip trip
units with the information and energy required to trip the

circuit breaker when functional protection settings are
exceeded.

If the CH Type-V current sensors and circuit breaker
enclosure label are changed to a different ratio, the rating
plug must also be changed. The associated rating plug
must match the  current sensors installed and as specified
on the circuit breaker enclosure label. Refer to Figure 2.3
for CH Type-V current sensors available.

1.5    Plexiglass Cover

A clear, tamper-proof, plexiglass door sits on the breaker
cover. This door allows the settings to be viewed but not
changed, except by authorized personnel. The plexiglass
cover meets applicable tamper-proof requirements. The
cover is held in place by two screws. Security is insured
by the insertion of a standard meter seal through the holes
in both of the cover retention screws. The plexiglass cover
has an access hole for the 

Reset/Battery Test 

push

button.

1.6   Ground Alarm/Power Supply Module (520MCV
Models Only)

The Ground Alarm/Power Supply Module 

(See Figure 1.7)

is a required accessory to enable communications on the
Digitrip 520MCV model. The module can be installed
beneath the metal mounting plate of the trip unit in the
Magnum Circuit Breaker. The module covers the following
input voltage ratings: 120 VAC (7802C83G11), 230 VAC
(7802C83G12), 24-48 VDC (7802C82G12) and 125VDC
(7802C8213).  The burden of the Power/Relay Module is
10VA.

Figure 1.4  CH Type-V Current Sensor Installation

Содержание Digitrip 520MCV

Страница 1: ...ime Setting 15 4 6 Instantaneous Current Setting 15 4 7 Ground Fault Current Setting 16 4 8 Ground Fault Time Delay Setting 16 4 9 INCOM 520MCV 16 4 9 1 Breaker Interface Module BIM 16 4 9 2 Remote Ma...

Страница 2: ...questions or need additional information or instructions concerning the operation or installation of this device please contact your local representative or the Cutler Hammer Customer Support Center 1...

Страница 3: ...rnal control power to operate their protection systems They operate from current signal levels derived through the CH Type V current sensors Status LED will also blink at a faster rate if the Digitrip...

Страница 4: ...SECURE THE PLUG AND THE TRIP UNIT TO THE CIRCUIT BREAKER See Figure 1 3 CLOSE THE RATING PLUG DOOR CAUTION THE M4 SCREW SHOULD BE TIGHTENED ONLY UNTIL IT IS SNUG BECAUSE THERE IS NO STOP DO NOT USE A...

Страница 5: ...sensors are installed external to the circuit breaker over the main circuit conductors by means of bushings equipped with a ground shield The current sensor rating defines the breaker rating In i e 12...

Страница 6: ...Effective 8 2006 Page 6 I L 66A7534H04 Figure 1 5 Secondary Block A Connections Figure 1 6 Secondary Block B Connections...

Страница 7: ...d setting The ground fault alarm relay is energized when the ground current continuously exceeds the ground fault pickup setting for a time in excess of a 0 1 second delay The alarm relay will reset a...

Страница 8: ...ible cause of this would be the lack or loss of auxilary power during the trip event Figure 1 8 Wiring Diagram for 520MCV with Ground Alarm Power Supply Module This message could also indicate that th...

Страница 9: ...secondary contact inputs B 6 B 7 that were shown in Figure 1 6 are used to configure the breaker cell positions for the two schemes Having no jumper from B 6 to B 7 programs the unit for a residual gr...

Страница 10: ...K1 9 CSA1 A 4 A 19 CSA2 A 5 CSB1 A 20 CSB2 A 6 CSC1 A 21 CSC2 X1 X2 B 5 B 4 R 1 R 1 CAUTION IF THE PHASE CONNECTIONSARE INCORRECT A NUISANCE TRIP MAY OCCUR ALWAYS OBSERVE THE POLARITY MARKINGS ON THE...

Страница 11: ...55 19 1 1200 1250A 3 42 5 35 1 55 19 1 1250 1600A 2000A 3 42 3 42 5 35 5 35 1 55 1 55 20 21 1 1600 1 2000 3 06 1 17 4 67 7 25 2 29 2 93 1 87 1 21 0 47 0 61 0 56 0 31 0 09 Rdc Ohms 15 RATIO WIRE GAUGE...

Страница 12: ...Interlocking function on the Digitrip has combined the logic interlocking of Short Delay and Ground Fault A zone out signal is sent whenever the ground fault pick up is exceeded or when the short dela...

Страница 13: ...Circuit Battery 3V FET Trip See Section 1 2 Trip LEDs Rating Plug Integrated Processor Custom Designed TA Unit Status LED See Section 3 2 See Section 7 0 See Section 2 3 See Section 3 3 Zone Interlock...

Страница 14: ...n The nominal current pickup value is 110 of the setting NOTE Ir is also the basis for the Short Delay Current Setting see Section 4 4 Figure 4 1 Long Delay Current Settings 4 3 Long Delay Time Settin...

Страница 15: ...x settings are in the range from 2 to 10 x In the rating plug value and the other two settings are M1 x In and Off The value that M1 has depends upon the plug rating of the circuit breaker and is spec...

Страница 16: ...heI2 t response reverts to the FLAT response NOTE Also see Section 3 3 Zone Interlocking M1 value is specified on rating plug Setting Inst x n I 6 Available Settings 2 3 4 6 8 10 M1 OFF In Multiples o...

Страница 17: ...es are daisy chained interconnect shielding but do not ground the connection 100 ohm 1 2 watt carbon terminating resistor required at last breaker See T D 17 513 See Section 4 9 for programming INCOM...

Страница 18: ...itrip trip unit and the mechanical trip assembly of the circuit breaker The testing can determine the accuracy of the desired trip settings by performing Long Delay Short Delay and Ground Fault functi...

Страница 19: ...eries are located on a separate board in the test kit and serve to power up the Digitrip trip unit Battery status LED s A and B function to represent sufficient voltage from both the single lithium ce...

Страница 20: ...e to each primary phase current is correct The secondary injection current source is able to deliver up to 5x 1 ampere is 1 per unit into the breaker s secondary contacts This can produce a 300 overlo...

Страница 21: ...contacts Hook up a circuit breaker Aux Switch to the MS 2 tester s Contacts terminals to stop the clock and the source of current TEST 2 Continue ramping up current and the circuit breaker should trip...

Страница 22: ...ED should flash Test Procedure TEST 1 Turn power switch ON and ramp up current slowly looking for the Digitrip s Unit Status LED to flash consistently at one second intervals This power up should occu...

Страница 23: ...d The main body of the battery is the positive side CAUTION EXERCISE CARE WHEN REPLACING THE BATTERY TO ENSURE THAT THE CORRECT POLARITIESARE OBSERVED POLARITY MARKINGS ARE SHOWN ON THE RATING PLUG WH...

Страница 24: ...ES NOT MATCH THE SENSOR RATING CAN PRODUCE SERIOUS MISCOORDINATION AND OR FAILURE OF THE PROTECTION SYSTEM 7 0 FRAME RATINGS SENSOR RATINGS AND RATING PLUGS The frame rating of a circuit breaker is th...

Страница 25: ...Shop Order Reference PER UNIT MULTIPLIERS Rating Plug Amperes In Ir Continuous Ampere Rating LDS x In Trip Function Per Unit Setting Multi Ampere Equivalent Setting Time Delay Inst In Long Delay In Se...

Страница 26: ...TION RECORD Circuit No Address Breaker Shop Order Reference Settings Reference Trip Function Orig 0 Rev 1 Rev 2 Rev 3 Instantaneous Long Delay Setting Long Delay Time Short Setting Short Time Ground F...

Страница 27: ...M Ground Fault Test Record should be retained by those in charge of the building s electrical installation in order to be available to the authority having jurisdiction Test Date Circuit Breaker Numbe...

Страница 28: ...aint signal to the feeder trip unit the feeder will send a restraint interlocking signal to Z1 Main and feeder trip units will begin to time out and in the event that the branch breaker does not clear...

Страница 29: ...power conductors DO NOT GROUND EARTH any Zone Interlock Wiring A2 The maximum distance between two farthest breakers on different zones from the ZO downstream to ZI upstream terminals is 250 feet 76m...

Страница 30: ...ce battery LED does not come on when battery check button is pressed Trip unit is malfunctioning Replace trip unit There actually is a ground fault Find location of the fault CH Type V current sensors...

Страница 31: ...y or permanently adding Aux Power and then depress Reset pushbutton to fully clear trip buffer See also Note in Section 5 3 2 2 Light load Check breaker ordering information Refer to Sections 1 6 and...

Страница 32: ...12 FEET 3 66 METERS OF 14 AWG WIRE NOTE SEE DETAIL ON RIGHT FOR DRAWOUT CIRCUIT BREAKER INFORMATION H R 1 H X1 R 1 X1 R 1 H X1 DETAIL PARTIAL FOR DRAWOUT BREAKER R 1 WIRE LENGTH MAXIMUM FOR DRAWOUT GE...

Страница 33: ...ODBUS uses a 4 pin connector which consist of signals A B COMmon and SHielD Three Baud rates of 1200 9600 or 19200 are selectable via programming switch for the MODBUS network The INCOM Baud rate is f...

Страница 34: ...ectri cal Inc selling policies or other contractual agreement be tween Eaton and the purchaser THERE ARE NO UNDERSTANDINGS AGREEMENTS WARRANTIES EXPRESSED OR IMPLIED INCLUDING WARRANTIES OF FITNESS FO...

Отзывы: