manualshive.com logo in svg
background image

Effective 8/2006

Page 16

I.L. 66A7534H04

Figure 4.6  Instantaneous Current Settings

4.7  Ground Fault Current Setting

The eight “Ground Fault Current Settings” are labeled with
values from .25 to .75 x (

I

n) and the other one is OFF.

(See Figure 4.7)

. The specific “Ground Current Settings” for

each model are listed in Figure 4.7 and on the applicable
time-current curve for the circuit breaker.

Figure 4.7  Ground Fault Current Settings

4.8  Ground Fault Time Delay Setting

As illustrated in Figure 4.8, there are two different Ground
Fault curve shapes: fixed time (FLAT) or I

2

t response. The

shape selected depends on the type of selective coordina-
tion chosen. The I

2

t response will provide a longer time

delay for current below 0.625 x 

I

n than will the FLAT

response.

Five FLAT (.1, .2, .3, .4, .5 seconds) and three I

2

t (.1*, .3*,

.5* seconds) response time delay settings are available.
The I

2

t response settings are identified by an asterisk (*).

The I

2

t response is applicable to currents less than 0.625

times the ampere rating of the installed rating plug (

I

n). For

currents greater than 0.625 x 

I

 

the

 

I

2

t response reverts to

the FLAT response.

NOTE: 

 Also see Section 3.3 - Zone Interlocking.

M1 value is specified on rating plug.

Setting Inst.

x n

I

6

Available Settings

2, 3, 4, 6, 8,
10, M1, OFF

In Multiples of
Rating Plug
Amperes ( n)

I

Available Settings

0.25, .3, .35, .4,
.5, .6, .75, OFF

Gnd-Fault
Setting

x n

I

.4

Figure 4.8  Ground Fault Time Delay Settings

4.9   INCOM  (Digitrip 520MCV Models only)

INCOM communication to a host computer or a BIM is
possible with the Digitrip 520MCV unit. The address range
is 001 through 999. The factory default address is 999 hex.

To set the desired address or to view the address, depress
and hold the RESET/BATTERY TEST button for five
seconds. Depress the STEP button to select a new
address. Users may simultaneously depress and hold in
the STEP and RESET/BATTERY TEST buttons for fast
advance.

4.9.1  Breaker Interface Module (BIM)

The Breaker Interface Module (BIM) can be used to
monitor up to 31 Digitrip 520MCV trip units. The accept-
able addresses are 001 through 031.

4.9.2 Remote Master Computer

When desired, Digitrip 520MCV Trip Units can communi-
cate with a BIM or remote master computer (IBM PC
compatible with Cutler Hammer Inc. CONI card or MINT )
and using PowerNet communication software version 3.20
or greater. 

(See Figure 4.9 for typical wiring.)

Содержание Digitrip 520MCV

Страница 1: ...ime Setting 15 4 6 Instantaneous Current Setting 15 4 7 Ground Fault Current Setting 16 4 8 Ground Fault Time Delay Setting 16 4 9 INCOM 520MCV 16 4 9 1 Breaker Interface Module BIM 16 4 9 2 Remote Ma...

Страница 2: ...questions or need additional information or instructions concerning the operation or installation of this device please contact your local representative or the Cutler Hammer Customer Support Center 1...

Страница 3: ...rnal control power to operate their protection systems They operate from current signal levels derived through the CH Type V current sensors Status LED will also blink at a faster rate if the Digitrip...

Страница 4: ...SECURE THE PLUG AND THE TRIP UNIT TO THE CIRCUIT BREAKER See Figure 1 3 CLOSE THE RATING PLUG DOOR CAUTION THE M4 SCREW SHOULD BE TIGHTENED ONLY UNTIL IT IS SNUG BECAUSE THERE IS NO STOP DO NOT USE A...

Страница 5: ...sensors are installed external to the circuit breaker over the main circuit conductors by means of bushings equipped with a ground shield The current sensor rating defines the breaker rating In i e 12...

Страница 6: ...Effective 8 2006 Page 6 I L 66A7534H04 Figure 1 5 Secondary Block A Connections Figure 1 6 Secondary Block B Connections...

Страница 7: ...d setting The ground fault alarm relay is energized when the ground current continuously exceeds the ground fault pickup setting for a time in excess of a 0 1 second delay The alarm relay will reset a...

Страница 8: ...ible cause of this would be the lack or loss of auxilary power during the trip event Figure 1 8 Wiring Diagram for 520MCV with Ground Alarm Power Supply Module This message could also indicate that th...

Страница 9: ...secondary contact inputs B 6 B 7 that were shown in Figure 1 6 are used to configure the breaker cell positions for the two schemes Having no jumper from B 6 to B 7 programs the unit for a residual gr...

Страница 10: ...K1 9 CSA1 A 4 A 19 CSA2 A 5 CSB1 A 20 CSB2 A 6 CSC1 A 21 CSC2 X1 X2 B 5 B 4 R 1 R 1 CAUTION IF THE PHASE CONNECTIONSARE INCORRECT A NUISANCE TRIP MAY OCCUR ALWAYS OBSERVE THE POLARITY MARKINGS ON THE...

Страница 11: ...55 19 1 1200 1250A 3 42 5 35 1 55 19 1 1250 1600A 2000A 3 42 3 42 5 35 5 35 1 55 1 55 20 21 1 1600 1 2000 3 06 1 17 4 67 7 25 2 29 2 93 1 87 1 21 0 47 0 61 0 56 0 31 0 09 Rdc Ohms 15 RATIO WIRE GAUGE...

Страница 12: ...Interlocking function on the Digitrip has combined the logic interlocking of Short Delay and Ground Fault A zone out signal is sent whenever the ground fault pick up is exceeded or when the short dela...

Страница 13: ...Circuit Battery 3V FET Trip See Section 1 2 Trip LEDs Rating Plug Integrated Processor Custom Designed TA Unit Status LED See Section 3 2 See Section 7 0 See Section 2 3 See Section 3 3 Zone Interlock...

Страница 14: ...n The nominal current pickup value is 110 of the setting NOTE Ir is also the basis for the Short Delay Current Setting see Section 4 4 Figure 4 1 Long Delay Current Settings 4 3 Long Delay Time Settin...

Страница 15: ...x settings are in the range from 2 to 10 x In the rating plug value and the other two settings are M1 x In and Off The value that M1 has depends upon the plug rating of the circuit breaker and is spec...

Страница 16: ...heI2 t response reverts to the FLAT response NOTE Also see Section 3 3 Zone Interlocking M1 value is specified on rating plug Setting Inst x n I 6 Available Settings 2 3 4 6 8 10 M1 OFF In Multiples o...

Страница 17: ...es are daisy chained interconnect shielding but do not ground the connection 100 ohm 1 2 watt carbon terminating resistor required at last breaker See T D 17 513 See Section 4 9 for programming INCOM...

Страница 18: ...itrip trip unit and the mechanical trip assembly of the circuit breaker The testing can determine the accuracy of the desired trip settings by performing Long Delay Short Delay and Ground Fault functi...

Страница 19: ...eries are located on a separate board in the test kit and serve to power up the Digitrip trip unit Battery status LED s A and B function to represent sufficient voltage from both the single lithium ce...

Страница 20: ...e to each primary phase current is correct The secondary injection current source is able to deliver up to 5x 1 ampere is 1 per unit into the breaker s secondary contacts This can produce a 300 overlo...

Страница 21: ...contacts Hook up a circuit breaker Aux Switch to the MS 2 tester s Contacts terminals to stop the clock and the source of current TEST 2 Continue ramping up current and the circuit breaker should trip...

Страница 22: ...ED should flash Test Procedure TEST 1 Turn power switch ON and ramp up current slowly looking for the Digitrip s Unit Status LED to flash consistently at one second intervals This power up should occu...

Страница 23: ...d The main body of the battery is the positive side CAUTION EXERCISE CARE WHEN REPLACING THE BATTERY TO ENSURE THAT THE CORRECT POLARITIESARE OBSERVED POLARITY MARKINGS ARE SHOWN ON THE RATING PLUG WH...

Страница 24: ...ES NOT MATCH THE SENSOR RATING CAN PRODUCE SERIOUS MISCOORDINATION AND OR FAILURE OF THE PROTECTION SYSTEM 7 0 FRAME RATINGS SENSOR RATINGS AND RATING PLUGS The frame rating of a circuit breaker is th...

Страница 25: ...Shop Order Reference PER UNIT MULTIPLIERS Rating Plug Amperes In Ir Continuous Ampere Rating LDS x In Trip Function Per Unit Setting Multi Ampere Equivalent Setting Time Delay Inst In Long Delay In Se...

Страница 26: ...TION RECORD Circuit No Address Breaker Shop Order Reference Settings Reference Trip Function Orig 0 Rev 1 Rev 2 Rev 3 Instantaneous Long Delay Setting Long Delay Time Short Setting Short Time Ground F...

Страница 27: ...M Ground Fault Test Record should be retained by those in charge of the building s electrical installation in order to be available to the authority having jurisdiction Test Date Circuit Breaker Numbe...

Страница 28: ...aint signal to the feeder trip unit the feeder will send a restraint interlocking signal to Z1 Main and feeder trip units will begin to time out and in the event that the branch breaker does not clear...

Страница 29: ...power conductors DO NOT GROUND EARTH any Zone Interlock Wiring A2 The maximum distance between two farthest breakers on different zones from the ZO downstream to ZI upstream terminals is 250 feet 76m...

Страница 30: ...ce battery LED does not come on when battery check button is pressed Trip unit is malfunctioning Replace trip unit There actually is a ground fault Find location of the fault CH Type V current sensors...

Страница 31: ...y or permanently adding Aux Power and then depress Reset pushbutton to fully clear trip buffer See also Note in Section 5 3 2 2 Light load Check breaker ordering information Refer to Sections 1 6 and...

Страница 32: ...12 FEET 3 66 METERS OF 14 AWG WIRE NOTE SEE DETAIL ON RIGHT FOR DRAWOUT CIRCUIT BREAKER INFORMATION H R 1 H X1 R 1 X1 R 1 H X1 DETAIL PARTIAL FOR DRAWOUT BREAKER R 1 WIRE LENGTH MAXIMUM FOR DRAWOUT GE...

Страница 33: ...ODBUS uses a 4 pin connector which consist of signals A B COMmon and SHielD Three Baud rates of 1200 9600 or 19200 are selectable via programming switch for the MODBUS network The INCOM Baud rate is f...

Страница 34: ...ectri cal Inc selling policies or other contractual agreement be tween Eaton and the purchaser THERE ARE NO UNDERSTANDINGS AGREEMENTS WARRANTIES EXPRESSED OR IMPLIED INCLUDING WARRANTIES OF FITNESS FO...

Отзывы: