manualshive.com logo in svg
background image

Effective 8/2006

Page 12

I.L. 66A7534H04

3.0  PRINCIPLES OF OPERATION

3.1  General

The Digitrip 520V and 520MCV trip units are designed for
circuit breaker environments where the ambient tempera-
tures can range from –30

°

C to +85

°

C, but rarely exceed

70

°

 to 75

°

C. If, however, temperatures in the neighborhood

of the trip unit exceed 85

°

C, the trip unit performance may

be degraded. In order to insure that the tripping function is
not compromised due to an over-temperature condition, the
Digitrip trip unit has a built-in over-temperature protection
feature, factory set to trip the breaker if the chip tempera-
ture is excessive. If over-temperature is the reason for the
trip the red “Long Delay Time” LED will flash.

The Digitrip 520V and 520MCV use an integrated circuit
that includes a microcomputer to perform its numeric and
logic functions. The principles of operation of the trip unit
are shown in Figure 3.1.

All power required to operate the protection function is
derived from the CH Type-V current sensors in the enclo-
sure behind the circuit breaker. 

(See Figure 1.4)

 The

secondary currents from these sensors provide the correct
input information for the protection functions, as well as
tripping power, whenever the circuit breaker is carrying
current. These current signals develop analog voltages
across the “current viewing” resistors. The resulting analog
voltages are digitized by the microprocessor.

The microcomputer continually digitizes these signals.
This data is used to calculate true RMS current values,
which are then continually compared with the protection
settings. The embedded software then determines whether
to initiate protection functions, including tripping the
breaker through the Trip Actuator.

3.3  Zone Interlocking

 

 CAUTION

IF ZONE INTERLOCKING IS NOT TO BE USED (I.E.,
ONLY STANDARD TIME-DELAY COORDINATION IS
INTENDED), THE ZONE INTERLOCKING TERMINALS
MUST BE CONNECTED BY A JUMPER FROM TERMI-
NAL B8 TO B9 OF THE BREAKER SECONDARY TERMI-
NALS SO THAT THE TIME-DELAY SETTINGS WILL
PROVIDE THE INTENDED COORDINATION.

Zone Selective Interlocking (or Zone Interlocking) is
standard for the Digitrip trip unit on the “Short Delay” and
“Ground Fault” protection functions 

(See Figure 3.1)

. The

zone interlocking signal is wired via a single set of wires
labeled 

Zone In

 (Zin) and 

Zone Out

 (Zout) along with a

“Zone Common” wire. The Zone Selective Interlocking
function on the Digitrip has combined the logic interlocking
of “Short Delay” and “Ground Fault.”  A zone out signal is
sent whenever the ground fault pick-up is exceeded or
when the short delay pickup is exceeded. Zone Selective
Interlocking provides the fastest possible tripping for faults
within the zone of protection of the circuit breaker and yet
also provides positive coordination among all breakers in
the system (mains, ties, feeders, and downstream break-
ers) to limit a power outage to only the affected parts of the
system. When Zone Interlocking is employed, a fault
within the zone of protection of the circuit breaker will
cause the Digitrip 520V and 520 MCV to simultaneously:

1) 

Trip the affected circuit breaker immediately

2)

Send a signal to upstream Digitrip units to restrain from
tripping immediately. The restraining signal causes the
upstream breakers to follow their set coordination times,
so that the service is only minimally disrupted while the
fault is cleared in the shortest time possible.

For an example of how Zone Selective Interlocking may be
used, see Appendix A of this Instructional Leaflet.

3.2  Trip and Operation Indicators

The LEDs on the face of the trip unit, shown in Figures 1.1
flash red to indicate the reason for any automatic trip
operation. Each LED is strategically located in the related
segment of the time-current curve depicted on the face of
the trip unit. The reason for the trip is identified by the
segment of the time-current curve where the LED is
illuminated. Following an automatic trip operation, the
backup battery continues to supply power to the LEDs as
shown in Figure 3.1. The LED pulse circuit, shown in
Figure 3.1, is provided to reduce battery burden and will
supply a quick flash of the trip LED approximately every 4
seconds. It is therefore important to view the unit for at
least 5 seconds to detect a flashing cause of trip indicator.

Following a trip operation, push the 

Reset/Battery Test

button, shown in Figure 1.1, to turn off the LEDs and reset
the trip unit.

The green 

Unit Status

 LED, shown in Figure 1.1, flashes at

one second intervals to indicate the operational status of
the trip unit. Once the load current through the circuit
breaker exceeds approximately 10 percent (3 phase
power) of the current sensor rating, the green LED will
flash on and off once each second to indicate that the trip
unit is energized and operating properly.

NOTE:

 A steady green 

Unit Status

 LED typically indicates

that a low level of load current, on the order of 5% of full
load, exists.

Содержание Digitrip 520MCV

Страница 1: ...ime Setting 15 4 6 Instantaneous Current Setting 15 4 7 Ground Fault Current Setting 16 4 8 Ground Fault Time Delay Setting 16 4 9 INCOM 520MCV 16 4 9 1 Breaker Interface Module BIM 16 4 9 2 Remote Ma...

Страница 2: ...questions or need additional information or instructions concerning the operation or installation of this device please contact your local representative or the Cutler Hammer Customer Support Center 1...

Страница 3: ...rnal control power to operate their protection systems They operate from current signal levels derived through the CH Type V current sensors Status LED will also blink at a faster rate if the Digitrip...

Страница 4: ...SECURE THE PLUG AND THE TRIP UNIT TO THE CIRCUIT BREAKER See Figure 1 3 CLOSE THE RATING PLUG DOOR CAUTION THE M4 SCREW SHOULD BE TIGHTENED ONLY UNTIL IT IS SNUG BECAUSE THERE IS NO STOP DO NOT USE A...

Страница 5: ...sensors are installed external to the circuit breaker over the main circuit conductors by means of bushings equipped with a ground shield The current sensor rating defines the breaker rating In i e 12...

Страница 6: ...Effective 8 2006 Page 6 I L 66A7534H04 Figure 1 5 Secondary Block A Connections Figure 1 6 Secondary Block B Connections...

Страница 7: ...d setting The ground fault alarm relay is energized when the ground current continuously exceeds the ground fault pickup setting for a time in excess of a 0 1 second delay The alarm relay will reset a...

Страница 8: ...ible cause of this would be the lack or loss of auxilary power during the trip event Figure 1 8 Wiring Diagram for 520MCV with Ground Alarm Power Supply Module This message could also indicate that th...

Страница 9: ...secondary contact inputs B 6 B 7 that were shown in Figure 1 6 are used to configure the breaker cell positions for the two schemes Having no jumper from B 6 to B 7 programs the unit for a residual gr...

Страница 10: ...K1 9 CSA1 A 4 A 19 CSA2 A 5 CSB1 A 20 CSB2 A 6 CSC1 A 21 CSC2 X1 X2 B 5 B 4 R 1 R 1 CAUTION IF THE PHASE CONNECTIONSARE INCORRECT A NUISANCE TRIP MAY OCCUR ALWAYS OBSERVE THE POLARITY MARKINGS ON THE...

Страница 11: ...55 19 1 1200 1250A 3 42 5 35 1 55 19 1 1250 1600A 2000A 3 42 3 42 5 35 5 35 1 55 1 55 20 21 1 1600 1 2000 3 06 1 17 4 67 7 25 2 29 2 93 1 87 1 21 0 47 0 61 0 56 0 31 0 09 Rdc Ohms 15 RATIO WIRE GAUGE...

Страница 12: ...Interlocking function on the Digitrip has combined the logic interlocking of Short Delay and Ground Fault A zone out signal is sent whenever the ground fault pick up is exceeded or when the short dela...

Страница 13: ...Circuit Battery 3V FET Trip See Section 1 2 Trip LEDs Rating Plug Integrated Processor Custom Designed TA Unit Status LED See Section 3 2 See Section 7 0 See Section 2 3 See Section 3 3 Zone Interlock...

Страница 14: ...n The nominal current pickup value is 110 of the setting NOTE Ir is also the basis for the Short Delay Current Setting see Section 4 4 Figure 4 1 Long Delay Current Settings 4 3 Long Delay Time Settin...

Страница 15: ...x settings are in the range from 2 to 10 x In the rating plug value and the other two settings are M1 x In and Off The value that M1 has depends upon the plug rating of the circuit breaker and is spec...

Страница 16: ...heI2 t response reverts to the FLAT response NOTE Also see Section 3 3 Zone Interlocking M1 value is specified on rating plug Setting Inst x n I 6 Available Settings 2 3 4 6 8 10 M1 OFF In Multiples o...

Страница 17: ...es are daisy chained interconnect shielding but do not ground the connection 100 ohm 1 2 watt carbon terminating resistor required at last breaker See T D 17 513 See Section 4 9 for programming INCOM...

Страница 18: ...itrip trip unit and the mechanical trip assembly of the circuit breaker The testing can determine the accuracy of the desired trip settings by performing Long Delay Short Delay and Ground Fault functi...

Страница 19: ...eries are located on a separate board in the test kit and serve to power up the Digitrip trip unit Battery status LED s A and B function to represent sufficient voltage from both the single lithium ce...

Страница 20: ...e to each primary phase current is correct The secondary injection current source is able to deliver up to 5x 1 ampere is 1 per unit into the breaker s secondary contacts This can produce a 300 overlo...

Страница 21: ...contacts Hook up a circuit breaker Aux Switch to the MS 2 tester s Contacts terminals to stop the clock and the source of current TEST 2 Continue ramping up current and the circuit breaker should trip...

Страница 22: ...ED should flash Test Procedure TEST 1 Turn power switch ON and ramp up current slowly looking for the Digitrip s Unit Status LED to flash consistently at one second intervals This power up should occu...

Страница 23: ...d The main body of the battery is the positive side CAUTION EXERCISE CARE WHEN REPLACING THE BATTERY TO ENSURE THAT THE CORRECT POLARITIESARE OBSERVED POLARITY MARKINGS ARE SHOWN ON THE RATING PLUG WH...

Страница 24: ...ES NOT MATCH THE SENSOR RATING CAN PRODUCE SERIOUS MISCOORDINATION AND OR FAILURE OF THE PROTECTION SYSTEM 7 0 FRAME RATINGS SENSOR RATINGS AND RATING PLUGS The frame rating of a circuit breaker is th...

Страница 25: ...Shop Order Reference PER UNIT MULTIPLIERS Rating Plug Amperes In Ir Continuous Ampere Rating LDS x In Trip Function Per Unit Setting Multi Ampere Equivalent Setting Time Delay Inst In Long Delay In Se...

Страница 26: ...TION RECORD Circuit No Address Breaker Shop Order Reference Settings Reference Trip Function Orig 0 Rev 1 Rev 2 Rev 3 Instantaneous Long Delay Setting Long Delay Time Short Setting Short Time Ground F...

Страница 27: ...M Ground Fault Test Record should be retained by those in charge of the building s electrical installation in order to be available to the authority having jurisdiction Test Date Circuit Breaker Numbe...

Страница 28: ...aint signal to the feeder trip unit the feeder will send a restraint interlocking signal to Z1 Main and feeder trip units will begin to time out and in the event that the branch breaker does not clear...

Страница 29: ...power conductors DO NOT GROUND EARTH any Zone Interlock Wiring A2 The maximum distance between two farthest breakers on different zones from the ZO downstream to ZI upstream terminals is 250 feet 76m...

Страница 30: ...ce battery LED does not come on when battery check button is pressed Trip unit is malfunctioning Replace trip unit There actually is a ground fault Find location of the fault CH Type V current sensors...

Страница 31: ...y or permanently adding Aux Power and then depress Reset pushbutton to fully clear trip buffer See also Note in Section 5 3 2 2 Light load Check breaker ordering information Refer to Sections 1 6 and...

Страница 32: ...12 FEET 3 66 METERS OF 14 AWG WIRE NOTE SEE DETAIL ON RIGHT FOR DRAWOUT CIRCUIT BREAKER INFORMATION H R 1 H X1 R 1 X1 R 1 H X1 DETAIL PARTIAL FOR DRAWOUT BREAKER R 1 WIRE LENGTH MAXIMUM FOR DRAWOUT GE...

Страница 33: ...ODBUS uses a 4 pin connector which consist of signals A B COMmon and SHielD Three Baud rates of 1200 9600 or 19200 are selectable via programming switch for the MODBUS network The INCOM Baud rate is f...

Страница 34: ...ectri cal Inc selling policies or other contractual agreement be tween Eaton and the purchaser THERE ARE NO UNDERSTANDINGS AGREEMENTS WARRANTIES EXPRESSED OR IMPLIED INCLUDING WARRANTIES OF FITNESS FO...

Отзывы: