Technical Data

Page 6

               Effective: July 2003

PRC100 - Universal System Controller
& Enclosures

TD01412013E

                          For More Information Visit www.cutler-hammer.com

Network Maximum Distance 4000-Feet

Networking Pow-R-Command 100 Nodes

Figure 6 

shows a typical Pow-R-Command

100 network.  The network begins at the
Pow-R-Command 100 Network Access
Device.  The Pow-R-Command 100 Network
Access Device is used to interface between
the Pow-R-Command 100 system PC
workstation or Ethernet network.  The
maximum distance of the Pow-R-Command
100 network is 4,000-Feet from the Network
Access Device to the furthest controller on
the network using a shielded twisted pair
network cable.

SHLD

          -

Network In:    +

SHLD

        -

Network Out: +

Universal System Controller Mounted
In 5X Control Chassis

Power Supply

Power
Connection

Power Switch

Line Filter

-

Network Access
Device

RS-485 Network
Maximum Distance of Network 4000-Feet from
Network Access Device to Furthest Node Using
Twisted Shielded Pair Network Cable

Pow-R-Command 100 Controller 1

Figure 6: Pow-R-Command 100 Network

Pow-R-Command 100
Controller 2

Pow-R-Command 100
Controller 3

Pow-R-Command 100
Controller 120

Содержание Cuttler-Hammer Pow-R-Command 100

Страница 1: ...uts 3 USC Input Output Specification 3 Integrated Timing Scheduling Features 3 Grouping Devices 3 Control Command Functions 3 On Board Indicator LED s 4 Networking Controllers 4 Locally Accessing A US...

Страница 2: ...he capabilities offered by the Pow R Command 100 controller the system would not have a great deal of use without enclosures Currently there are five general type of enclosures used in the Pow R Comma...

Страница 3: ...o use a master clock function in order to assure coordination of all USC s on a network The master clock is found on the Network Access Device For further information on Network Access Devices see Tec...

Страница 4: ...the Pow R Command 100 software installed For more information on using PC s with the Pow R Command 100 network see Technical Document TD01412016E For more information on the types of Pow R Command 10...

Страница 5: ...Thermostats may also be connected to analog inputs outputs Figure 4 Analog Output Wiring Common Analog Output 1 Analog Output 2 Black White Red Power Dimming Pigtail Red Black Universal System Contro...

Страница 6: ...t network The maximum distance of the Pow R Command 100 network is 4 000 Feet from the Network Access Device to the furthest controller on the network using a shielded twisted pair network cable SHLD...

Страница 7: ...ocally terminate the Pow R Command 100 network Breaker Termination Boards The Breaker Termination Boards are a control bus that runs underneath the load side terminals of the branch circuit breakers o...

Страница 8: ...BR BABRS BAB GHQRS 3 4 GHBS GHB BABR BABRS BAB GHQRS 3 4 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 13X PRC100 Smart Chassis 18 Single Pole Spaces for GHBS GHB BABR BABRS BAB GHQ...

Страница 9: ...s a control power bus to all devices attached to it Application Specific Controller Ports Located on the Relay Termination Board are three 3 sets of white connection ports These connection ports are u...

Страница 10: ...R Command 100 Control Cabinet is sold complete with all of the standard components of the Pow R Command 100 Relay Cabinet with the exception of the USC In addition the Pow R Command 100 Control Cabin...

Страница 11: ...former capable of operating at either 120 V ac or 277V ac Power to the trans former is drawn directly from the bus Additionally line protection is supplied to both the primary and secondary side of th...

Страница 12: ...Data Page 12 Effective July 2003 PRC100 Universal System Controller Enclosures TD01412013E For More Information Visit www cutler hammer com Panelboard T ypes M ain Breaker T ypes M ounting H Horizonta...

Страница 13: ...ox Pull box is furnished without knockouts Standard Dimensions 12 inches 304 8 mm high 16 inches 406 4 mm wide 6 inches 152 4 mm deep Panelboard T ypes M ain Breaker T ypes M ounting H Horizontal V V...

Страница 14: ...e mounted in a single section it must have a main device amperage rating of 250A or less for main lugs or 100A or less for main breaker A Pow R Command 100 Panelboard intended to mount in a cell of an...

Страница 15: ...TD01412015E PRC100 Human Machine Interfaces TD01412016E PRC100 JCI 100 Controller TD01412017E PRC100 Protocol Exchanges TD01412018E PRC100 0 10V dc Dimming Electronic Ballasts Control TD01412019E PRC...

Отзывы: