Effective 11/2003
Page 77
I.L. 66A7535H02
Digitrip 1150V Settings (continued)
Setting
Description
Activate Block Close Relay B on Trip
The trip conditions upon which Block Close Relay B is activated:
Long Delay
Short Delay
Instantaneous
Ground Fault
Ampere Unbalance
Phase Loss
Over Temperature
Rating Plug
External Communications
Accessory Bus (when applicable)
Under Voltage
Over Voltage
Under Frequency
Over frequency
Phase Unbalance
Activate Latch Relay C on Trip
The trip conditions upon which Latch Relay C is activated:
Long Delay
Short Delay
Instantaneous
Ground Fault
Ampere Unbalance
Phase Loss
Over Temperature
Rating Plug
External Communications
Accessory Bus (when applicable)
Under Voltage
Over Voltage
Under Frequency
Over frequency
Phase Unbalance
Return to Metered Current Display
When set to Automatic, returns the trip unit display to the metered phase A, B
and C current screen if the unit keypad is idle for 5 minutes.
INCOM Address
Communication address 001 through FFE.