1.3.2 Rating Plug Installation
WARNING
DO NOT ENERGIZE THE CIRCUIT BREAKER WITH THE
DIGITRIP REMOVED OR DISCONNECTED FROM ITS
CONNECTOR. DAMAGE TO ASSOCIATED CURRENT
TRANSFORMERS MAY OCCUR DUE TO AN OPEN
CIRCUIT CONDITION. THERE IS NO PROTECTION FOR
THE LOAD CIRCUIT.
Figure 1.2 Installation of the Digitrip Unit into a Type VCP-T, VCP-TR, T-VAC or T-VACR Circuit Breaker (Side View)
CAUTION
IF A RATING PLUG IS NOT INSTALLED IN THE TRIP
UNIT, THE UNIT WILL INITIATE A TRIP WHEN IT IS
ENERGIZED. IN ADDITION THE INSTANTANEOUS LED
WILL LIGHT ON A PLUG TRIP DUE TO A MISSING OR
BAD RATING PLUG.
Insert the rating plug into the cavity on the right-hand side
of the trip unit. Align the three pins on the plug with the
sockets in the cavity. The plug should fit with a slight
insertion force.