Effective 11/2003
Page 64
I.L. 66A7535H02
Appendix D Page D-16
Program
Alarms
(Continued from D-15)
Notes:
Front Panel Display of NEUTral AMPere ALARM will be in amperes. Equation used is:
Amperes = In (amperes) x Neutral Alarm Pickup Setting ( 0.10 to 1.0 x In is range )
The Neutral alarm function is not possible on breakers used in a Source Ground or Zero Sequence Ground Fault application.
Save
(Page D-19)
If IEC style
"EARTH" will replace
"GROUND"
GROUND
ALARM
A
HighLOAD
ALARM
A
VIEW
range
(0.50 to 1.00 xIr)
OFF
(steps of 0.05)
OFF
0.10 to 1.00
OFF
(steps of 0.01)
1 to 65,500
OFF
(steps of 1)
1 to 65,500
OFF
(steps of 1)
1 to 12,500
OFF
(steps of 1)
1 to 60 s
0.50 to 0.95
OFF
(steps of 0.05)
10% to 30%
OFF
(steps of 1%)
ENABLED
DISABLED
See Note
below
NEUT AMP
ALARM
A
HighLOAD
TIME
s
OP COUNT
ALARM
kVA
DEMAND
kW
DEMAND
THD
ALARM
%
ALARM TO
EventLOG
LOW PF
ALARM
.
VOLT UN-
BALANCE
s
UNdrVOLT
ALARM
V
UNdrVOLT
TIME
s
OverVOLT
ALARM
V
OverVOLT
TIME
s
UndrFREQ
ALARM
. Hz
UndrFREQ
TIME
. s
OverFREQ
ALARM
. Hz
OverFREQ
TIME
. s
ALARM ON
ROTATION
VOLT UN-
BALANCE
%
45 to 110% of Vpri
OFF
(steps of 1V)
80 to 110% of Vpri
OFF
(steps of 1V)
1 to 250s
(steps of 1s)
1 to 250s
(steps of 1s)
58 to 62 (60Hz) or
48 to 52 (50Hz)
0.2 to 5.00 s
(steps of 0.02)
58.0 to 62.0 (60Hz)
48.0 to 52.0 (50Hz)
0.2 to 5.00 s
(steps of 0.02)
ABC, CBA
OFF
5 to 50 %
(steps of 1%)
1 to 250
(steps of 1s)