Effective 11/2003
Page 61
I.L. 66A7535H02
Appendix D Page D-13
INST PU
. xIn
XXXXX A
GROUND
SLOPE
GND PU
.
XXXX A
GROUND
TIME
. s
EXT GND
CT RATIO
AMP UN-
BALANCE
%
AMP UN-
BALANCE
s
PHASE
LOSS
2.0 - M1
OFF
(steps of 0.5)
0.10 - 1.00 and OFF (IEC style only)
0.24 - 1.00 and OFF (IEEE)
(steps of 0.01)
0.10 - 0.50
(steps of 0.05)
FLAT
I2T
none
1000/1
800/1
400/1
200/1
100/1
50/1
25/1
10/1
5% - 25%
OFF
(steps of 1%)
0 - 240 s
(steps of 1 s)
1 - 30 s
OFF
(steps of 1 s)
Program
CURRENT Curve
LSIG
(Continued from D-12)
Save
(Page D-19)
LONG
SLOPE
I T
0.40 - 1.00
(steps of 0.05)
LONG PU
.
Ir=XXXXA
I2T:
2.0 - 24.0
(steps of 0.5)
LongTIME
@ 6x Ir
. s
2
4
LONG
MEMORY
ON
OFF
SHORT
SLOPE
1.5 - 12x or
1.5 - 14x
(steps of 0.5)
(and additional
setting M1 x In)
SHORT PU
. xIr
XXXXX A
0.10 - 0.50s or
0.10 - 1.0s or
0.10 - 2.0s
(steps of 0.05)
SHORT
TIME
. s
FLAT
I2T
VIEW
Screen is skipped if
first AMP UN-
BALANCE is set to
"OFF"
I4T:
1.0 - 5.0
(steps of 0.5)
If LONG SLOPE =
none denotes default
to In value
= 12x or
= 14x
M1
If IEC style
"EARTH" will replace
"GROUND"
(See Section 4.2.2)
Screen
skipped if
breaker
contacts B-6
is not
connected to
B-7