Effective 11/2003
Page 4
I.L. 66A7535H02
Current Metering
Units
Tolerance
Notes
IA, IB, IC, IN,
IG
IA, IB, IC (AVG)
IN, IG (AVG)
IA, IB, IC (Max)
IN, IG (Max)
IA, IB, IC (Min)
IN, IG (Min)
Amperes
Amperes
Amperes
Amperes
Amperes
Amperes
Amperes
Amperes
±1% FS
±2% FS
Real time data, FS = In rating
Real time data, FS = In rating
5 MINUTE AVERAGE
5 MINUTE AVERAGE
(Tolerance applicable for 5 to 100% of In)
Group values held until Reset.
Based on approximately 1 second
time interval
Voltage Metering
VAB, VBC, VCA
Volts
±3% FS
FS (Full Scale) Primary
Power Metering
Power
kVA
kvar
DEMAND kW
DEMAND Max kW
DEMAND kVA
DEMAND Max kVA
kW
kVA
kvar
kW
kW
kVA
kVA
±4% FS
±4% FS
±4% FS
±4% FS
±4% FS
±4% FS
±4% FS
Approximately 1 second update
LAST AVG - 5 MIN INTERVAL
SLIDING or FIXED 15 MIN INTERVAL*
LAST AVG - 5 MIN INTERVAL
SLIDING or FIXED 15 MIN INTERVAL*
Energy Metering
ENERGY kWh
ENERGY Rev kWh
KVAh
kWh
kWh
kVAh
±4% FS
±4% FS
±4% FS
Metering Related Alarm s
kVA DEMAND ALARM
kW DEMAND ALARM
KVA
kW
1 to 65000
1 to 65000
LAST AVG - 5 min fixed interval
LAST AVG - 5 min fixed interval
Other
kVAh PULSE INITIATE
kWh PULSE INITIATE
kVAh
kWh
See section
4.7
INITIATE is an abbreviation for INITIATOR
INITIATE is an abbreviation for INITIATOR
* Only one of DEMAND Max kW or DEMAND Max kVA can be SLIDING INTERVAL
Table 1.1b Metering Data for Digitrip 1150V/1150Vi Trip Units
Harmonic
Units
Notes
THD (Total Harmonic Distortion)
THDA
THDB
THDC
THDN
Per Harmonic Data
HARMON A
HARMON B
HARMON C
HARMON N
CF (Crest Factor)
CFA
CFB
CFC
CFN
0 to 99 percent
0 to 99 percent
0 to 99 percent
0 to 99 percent
0 to 99 percent
0 to 99 percent
0 to 99 percent
0 to 99 percent
1.0 to 25.5
1.0 to 25.5
1.0 to 25.5
1.0 to 25.5
Phase A current
Phase B current
Phase C current
Neutral current
Fundamental through 27
th
Phase A current
Phase B current
Phase C current
Phase N current
Phase A current
Phase B current
Phase C current
Phase N current
Power Factor / Frequency
PF (Power Factor)
PF MIN
PF MAX
0 to 1.00
0 to 1.00
0 to 1.00
Located in METER menu, real time data
Value held until Reset
Value held until Reset
Hz (Frequency)
Hz
Located in METER menu
Power Quality Related Alarms (Programmable)
LOW PF ALARM
THD ALARM
50 to 95 percent
10 to 30 percent
OFF setting available
OFF setting available
Table 1.1c Power Quality Data for Digitrip 1150V/1150Vi Trip Units