Intelligent Technologies Modbus to QCPort Adapter Manual
January 2006
MN05002002E (C)
For more information visit
www.eatonelectrical.com
Page 61
Appendix C: Register Mapping
Production (holding register area)
Description Modbus
Register
Size
(Reg)
Usage Read/
Write
QCPort Channel
Status
0001
1
Status of QCPort channel A and B
R
Production Data 1
st
Device
0002 1023
Production
Data
area
R
Production Last
Register
1024
1
Production Data Last Register
R
Consumption (holding register area)
Description Modbus
Register
Size
(Reg)
Usage Read/
Write
QCPort Channel
Control
1025
1
Control of QCPort channel A and B R
Consumption Data
1
st
Device
1026
1023
Consumption Data area
R/W
Consumption Last
Register
2048
1
Consumption Data Last Register
R/W
Control (holding register area)
Description Modbus
Register
Size
(Reg)
Usage Read/
Write
QCPort Channel A
Command
2049
1
0 disable scan
1 enable scan
R/W
QCPort Channel B
Command
2050
1
0 disable scan
1 enable scan
R/W
Status (holding register area)
Description Modbus
Register
Size
(Reg)
Usage Read/
Write
Faults
2305
6
Modbus Adapter Faults 6 registers –
raw hex representing faults.
See Appendix D Modbus Adapter
Fault List
R