Intelligent Technologies Modbus to QCPort Adapter Manual
January 2006
MN05002002E (C)
For more information visit
www.eatonelectrical.com
Page 21
Configuration Tab
The configuration tab is only used for setting up the Modbus Pass-Through parameters, if
Modbus Pass-Through is not going to be used then it is not necessary to set any of these
parameters. If Modbus Pass-Through is going to be used, it is important to set up the
Serial Modbus baud rate and parity of the Modbus network devices. All the Serial
Modbus devices must be set to the same baud rate as the D77D-EMA Pass-Through
settings. If a device takes more than 100 ms to respond to a Serial Modbus message, it
is important to set the Allow slow response check box.
Table 19 Configuration Tab