Pass Through 0x41 (65)
Request PDU
Function code
1 byte
0x41
QCPort Channel
1 byte
0 = channel A
1 = channel B
QCPort request message
n bytes
Response PDU
Function code
1 byte
0x41
QCPort response message
n bytes
Error
Function code
1 byte
0xC1
Exception code
1 byte
0x03: Illegal data value
0x0B: Modbus Adapter target device
failed to respond
0x0A: Modbus Adapter path
unavailable – if an illegal
channel is specified
Reset Services 0x42 (66)
Request PDU
Function code
1 byte
0x42
QCPort Channel
1 byte
0 = Channel A; 1 = Channel B
Modbus Adapter/Node ID
2 bytes
0xffff = Modbus Adapter, any other =
QCPort device id
Reset type
1 byte
0 = Reset processor
1 = Hard Reconfiguration
2 = Soft Reconfiguration
3 = Regather
4 = Set to Factory Defaults
Response PDU
Function code
1 byte
0x42
Asynchronous channel
0 or 1
bytes
Asynchronous reset type
0 or 1
bytes
If the reset occurs asynchronously
(reset type 1,2,3,4), these are copies
of Channel and Reset type from the
Request PDU; otherwise, these are
omitted.
Asynchronous completion status
0 or 1
bytes
If reset type is 1,2,3,4:
0 = In progress
1 = Complete
Otherwise, omitted.
Error
Function code
1 byte
0xC2
Exception code
1 byte
0x03: Illegal data value