Instruction Leaflet 

I. L. 29-885D

Effective August 2011

 Instructions for Digitrip RMS 510 Trip Unit

 

 

EATON CORPORATION

 www.eaton.com

• 

The "Must Use With Frame Rated" current value (or "Sensor 

Rated", if applicable),

and

• 

" I

n

 (rated I)=" current value .

This latter value (I

n

) is the basis for the Trip Unit current settings:

• 

The instantaneous and Ground Current Settings (if applicable) are 

multiples of (I

n

) (see Sections 3 .6 and 3 .8 .) .

• 

The Long Delay Current Setting, 

I

r

  is a multiple of (I

n

) .  Long 

Delay Current Setting = 

I

r

 = LD x (I

n

) (see Section 3 .2 .) .

• 

The Short Delay Current Setting (if provided) is a multiple of 

I

r

 

which in turn is a multiple of (I

n

) .  Short Delay Current Setting = 

SD x 

I

r

 = SD x LD x (I

n

) (see Section 3 .4) .

If the rating plug is missing or not well connected the instanta-

neous / override LED will be lit .  If the circuit breaker is closed, it 

will trip .  If the rating plug condition is not corrected, as soon as the 

three-phase current through the circuit breaker reaches 20% (40% 

if single-phase current) of the frame / current sensor rating, the Trip 

Unit will trip the breaker again .
As indicated in Figures 2 and 9, a back-up battery is provided to 

maintain the mode of trip LED indication in the Digitrip RMS 510 Trip 

Unit when external control power to the Power / Relay module is not 

available .  The back-up battery is located in the rating plug along with 

a battery check push-button and a green battery check LED .  The bat-

tery in the rating plug is "OK" if the LED lights "Green" when the "bat-

tery check" button next to it is pushed (see Section 4 .5) .

otee:

N

The back-up battery is used only to maintain the cause of TRIP LED 

indication .  It has NO part in the PROTECTION FUNCTION of the Trip Unit .

1.3  Auxiliary Power Module

The Auxiliary Power Module or APM (Cat . No . PRTAAPM), illustrated 

in Figure 10, is an encapsulated power supply that requires a 120 Vac 

input at either 50 or 60 Hz .  It provides an output of 32 Vdc (nomi-

nal 40 Vdc open circuit) which is used during testing of the Digitrip 

RMS 510 Trip Unit,  When a drawout circuit breaker is equipped with 

a Digitrip RMS 510 Trip Unit, it can be conveniently set and tested 

while the circuit breaker is either out of its cell or in its cell in the 

"Test", "Disconnect", or "Withdrawn" positions by using the Auxiliary 

Power Module .
The Auxiliary Power Module is equipped with a unique plug-in con-

nector suitable only for plugging in to the keyed receptacle in the 

upper right corner of a Digitrip RMS Trip Unit as shown in Figure 2 .  

This avoids the inadvertent use of an incorrect type power module .
The APM is suitable for use with older Digitrip RMS 500, 600, 700, 

800, as well as newer RMS 510, 610, 810, and 910 Models .

Figure 10. Auxiliary Power Module.

2  UL Listed Devices

Digitrip RMS 510 Trip Units are "Listed" by the Underwriters 

Laboratories, Inc .

®

 under UL File E7819, for use in types DS, DSL, 

SPB, and Series C

®

 R-Frame circuit breakers .

Plug for 120Vac 

Receptacle

Trip Unit Connector (Fits into Keyed 

Cavity in Top Right Corner of Trip 

Unit . See Figure 2)

Содержание Cutler-Hammer Digitrip RMS 510

Страница 1: ...Effective August 2011 Supersedes I L 29 885C 12 10 Instruction Leaflet I L 29 885D Instructions for Digitrip RMS 510 Trip Unit...

Страница 2: ...Back up Battery Check 14 4 5 2 Replacing the Back up Battery 14 5 References 15 5 1 Digitrip RMS Trip Assemblies 15 5 2 Type DS Low Voltage AC Power Circuit Breakers 15 5 3 Type DS II Low Voltage AC P...

Страница 3: ...cuit breakers and type SPB Systems Pow R circuit breakers and Series C R Frame molded case circuit breakers The Digitrip RMS 510 Trip Unit pro vides three basic functions Function Section Protection 1...

Страница 4: ...round Protection SPB Rating Plug View Settings in Window Adjust Protection Settings for Desired Values with Rotary Switches Trip Unit Operation Status Blinking Green OK See Section 1 1 1 R Frame Ratin...

Страница 5: ...inte grally mounted in the circuit breaker The Digitrip RMS 510 Trip Unit is available in six different types Each Trip Unit may be equipped with a maximum of five phase and two ground time current se...

Страница 6: ...fective August 2011 Instructions for Digitrip RMS 510Trip Unit EATON CORPORATION www eaton com Figure 5 Digitrip RMS 510 Type LSI Figure 6 Digitrip RMS 510 Type LIG Figure 7 Digitrip RMS 510 Type LSG...

Страница 7: ...show DIS in the window ONLY ONE position shows blank Note N When the OVERRIDE window shows blank the only fast acting high short circuit protection available is the OVERRIDE Fixed Instantaneous see Se...

Страница 8: ...an carry continuously However for proper coordination of over current pro tection it is often desirable to choose different levels of In for differ ent circuit breakers of the same frame rating An ass...

Страница 9: ...ck LED The bat tery in the rating plug is OK if the LED lights Green when the bat tery check button next to it is pushed see Section 4 5 Note N The back up battery is used only to maintain the cause o...

Страница 10: ...otect load circuits from the effects of repeated overload condi tions If a breaker is re closed soon after a Long Delay Trip and the current again exceeds the Long Delay Current Setting Ir the LTM aut...

Страница 11: ...Plug In Setting Inst I n 5 6 M M 2 2 5 3 4 1 2 3 7 No Instantaneous Current Setting For types LS and LSG Trip Units please see Sections 1 1 3 DlScriminator High initial Current Release and 1 1 4 OVERR...

Страница 12: ...IZED DEATH OR SEVERE PERSONAL INJURY CAN RESULT FROM CONTACT WITH ENERGIZED EQUIPMENT DE ENERGIZE THE CIRCUIT AND DISCONNECT THE CIRCUIT BREAKER BEFORE PERFORMING MAINTENANCE OR TESTS REFER TO THE APP...

Страница 13: ...MS 510 Trip Unit also has a Long Time Memory function LTM which serves to protect load circuits from the effects of repeated overload conditions see Note 1 under Section 3 3 Long Delay Time Setting Th...

Страница 14: ...S 510 Trip Unit The battery is located in the rating plug along with a battery check push button and a green battery check LED see Figure 9 4 5 1 Back up Battery Check The battery is a long life lithi...

Страница 15: ...lemental Digitrip RMS and Optim Trip Units with Type DS II I L 8700C39 and DSL II Low Voltage AC Power Circuit Breakers AD 32 870 Typical Time Current Characteristic Curves for Types DS II and DSL II...

Страница 16: ...the event that the feeder breaker Z2 would not clear the fault the main breaker Z1 will clear the fault in 0 5 s as above Fault 1 There are no interlocking signals The main breaker trip unit will init...

Страница 17: ...17 Instruction Leaflet I L 29 885D Effective August 2011 Instructions for Digitrip RMS 510Trip Unit EATON CORPORATION www eaton com Notes...

Страница 18: ...18 Instruction Leaflet I L 29 885D Effective August 2011 Instructions for Digitrip RMS 510Trip Unit EATON CORPORATION www eaton com Notes...

Страница 19: ...19 Instruction Leaflet I L 29 885D Effective August 2011 Instructions for Digitrip RMS 510Trip Unit EATON CORPORATION www eaton com Notes...

Страница 20: ...between the parties This literature is not intended to and does not enlarge or add to any such contract The sole source governing the rights and remedies of any purchaser of this equipment is the con...

Отзывы: