background image

3

Instruction Leaflet 

I. L. 29-885D

Effective August 2011

 Instructions for Digitrip RMS 510 Trip Unit

 

 

EATON CORPORATION

 www.eaton.com

Important Safety Instructions

WARNING

DO NOT ATTEMPT TO INSTALL OR PERFORM MAINTENANCE ON 

EQUIPMENT WHILE IT IS ENERGIZED.  DEATH OR SEVERE PERSONAL 

INJURY CAN RESULT FROM CONTACT WITH ENERGIZED EQUIPMENT.  

ALWAYS VERIFY THAT NO VOLTAGE IS PRESENT BEFORE PROCEEDING 

WITH THE TASK, AND ALWAYS FOLLOW GENERALLY ACCEPTED 

SAFETY PROCEDURES.  EATON CORPORATION IS NOT LIABLE FOR THE 

MISAPPLICATION OR MISINSTALLATION OF ITS PRODUCTS. 

It is strongly urged that the User observe all recommendations, 

warnings and cautions relating to the safety of personnel and equip-

ment, as well as all general and local health and safety laws, codes, 

and procedures .
The recommendations and information contained herein are based 

on experience and judgment, but should not be considered to be 

all-inclusive or covering every application or circumstance which 

may arise .  If you have any questions or need further information 

or instructions, please contact your local representative, or the 

Customer Support Center for the type of circuit breaker you have .

1  General Description - Digitrip RMS 510  

     Trip Unit

1.1  Basic Digitrip RMS 510 Trip Unit

The Digitrip RMS 510, illustrated in Figure 2, is a Trip Unit suitable 

for use in types DS and DSL Low-Voltage AC power circuit breakers 

and type SPB Systems Pow-R circuit breakers and Series C R-Frame 

molded case circuit breakers .  The Digitrip RMS 510 Trip Unit pro-

vides three basic functions:

Function 

Section

Protection 

1 .1 .2 – 1 .1 .5 and 3

Information 

1 .1 .1

Testing 

4

Digitrip RMS 510 provides true RMS current sensing for proper cor-

relation with thermal characteristics of conductors and equipment . 

Interchangeable rating plugs are provided to establish the continuous 

current rating of each circuit breaker .  The Digitrip RMS 510 Trip Unit 

is designed for use in industrial circuit breaker environments where 

the ambient temperatures can range from -20°C to +85°C (-4°F to 

185°F) and rarely exceed 70 to 75°C (158 to 167°F)  .  If, however, 

temperatures in the neighborhood of the Trip Unit do exceed this 

range, the Trip Unit performance may be degraded .  In order to 

insure that the tripping function is not compromised due to an over-

temperature condition, the Digitrip RMS 510 microcomputer chip has 

a built-in over-temperature protection feature, factory set to trip the 

breaker if the chip temperature is excessive .  If over-temperature is 

the reason for the trip, the Long Delay Time LED will light "RED" .
The Trip Unit employs the Eaton custom designed integrated circuit 

microprocessor which includes a micro-computer to perform its 

numeric and logic functions .  The principle of operation is described 

by the block diagram shown in Figure 1 .

Figure 1. RMS Digitrip 510 Trip Unit - Block Diagram.

Microprocessor

Custom Designed

Integrated Circuit

Auxiliary Power Module Input

(When Used - See Section 1.3)

Содержание Cutler-Hammer Digitrip RMS 510

Страница 1: ...Effective August 2011 Supersedes I L 29 885C 12 10 Instruction Leaflet I L 29 885D Instructions for Digitrip RMS 510 Trip Unit...

Страница 2: ...Back up Battery Check 14 4 5 2 Replacing the Back up Battery 14 5 References 15 5 1 Digitrip RMS Trip Assemblies 15 5 2 Type DS Low Voltage AC Power Circuit Breakers 15 5 3 Type DS II Low Voltage AC P...

Страница 3: ...cuit breakers and type SPB Systems Pow R circuit breakers and Series C R Frame molded case circuit breakers The Digitrip RMS 510 Trip Unit pro vides three basic functions Function Section Protection 1...

Страница 4: ...round Protection SPB Rating Plug View Settings in Window Adjust Protection Settings for Desired Values with Rotary Switches Trip Unit Operation Status Blinking Green OK See Section 1 1 1 R Frame Ratin...

Страница 5: ...inte grally mounted in the circuit breaker The Digitrip RMS 510 Trip Unit is available in six different types Each Trip Unit may be equipped with a maximum of five phase and two ground time current se...

Страница 6: ...fective August 2011 Instructions for Digitrip RMS 510Trip Unit EATON CORPORATION www eaton com Figure 5 Digitrip RMS 510 Type LSI Figure 6 Digitrip RMS 510 Type LIG Figure 7 Digitrip RMS 510 Type LSG...

Страница 7: ...show DIS in the window ONLY ONE position shows blank Note N When the OVERRIDE window shows blank the only fast acting high short circuit protection available is the OVERRIDE Fixed Instantaneous see Se...

Страница 8: ...an carry continuously However for proper coordination of over current pro tection it is often desirable to choose different levels of In for differ ent circuit breakers of the same frame rating An ass...

Страница 9: ...ck LED The bat tery in the rating plug is OK if the LED lights Green when the bat tery check button next to it is pushed see Section 4 5 Note N The back up battery is used only to maintain the cause o...

Страница 10: ...otect load circuits from the effects of repeated overload condi tions If a breaker is re closed soon after a Long Delay Trip and the current again exceeds the Long Delay Current Setting Ir the LTM aut...

Страница 11: ...Plug In Setting Inst I n 5 6 M M 2 2 5 3 4 1 2 3 7 No Instantaneous Current Setting For types LS and LSG Trip Units please see Sections 1 1 3 DlScriminator High initial Current Release and 1 1 4 OVERR...

Страница 12: ...IZED DEATH OR SEVERE PERSONAL INJURY CAN RESULT FROM CONTACT WITH ENERGIZED EQUIPMENT DE ENERGIZE THE CIRCUIT AND DISCONNECT THE CIRCUIT BREAKER BEFORE PERFORMING MAINTENANCE OR TESTS REFER TO THE APP...

Страница 13: ...MS 510 Trip Unit also has a Long Time Memory function LTM which serves to protect load circuits from the effects of repeated overload conditions see Note 1 under Section 3 3 Long Delay Time Setting Th...

Страница 14: ...S 510 Trip Unit The battery is located in the rating plug along with a battery check push button and a green battery check LED see Figure 9 4 5 1 Back up Battery Check The battery is a long life lithi...

Страница 15: ...lemental Digitrip RMS and Optim Trip Units with Type DS II I L 8700C39 and DSL II Low Voltage AC Power Circuit Breakers AD 32 870 Typical Time Current Characteristic Curves for Types DS II and DSL II...

Страница 16: ...the event that the feeder breaker Z2 would not clear the fault the main breaker Z1 will clear the fault in 0 5 s as above Fault 1 There are no interlocking signals The main breaker trip unit will init...

Страница 17: ...17 Instruction Leaflet I L 29 885D Effective August 2011 Instructions for Digitrip RMS 510Trip Unit EATON CORPORATION www eaton com Notes...

Страница 18: ...18 Instruction Leaflet I L 29 885D Effective August 2011 Instructions for Digitrip RMS 510Trip Unit EATON CORPORATION www eaton com Notes...

Страница 19: ...19 Instruction Leaflet I L 29 885D Effective August 2011 Instructions for Digitrip RMS 510Trip Unit EATON CORPORATION www eaton com Notes...

Страница 20: ...between the parties This literature is not intended to and does not enlarge or add to any such contract The sole source governing the rights and remedies of any purchaser of this equipment is the con...

Отзывы: