background image

10

Instruction Leaflet 

I. L. 29-885D

Effective August 2011

 Instructions for Digitrip RMS 510 Trip Unit

 

 

EATON CORPORATION

 www.eaton.com

3  Protection Settings

3.1  General

Prior to placing any circuit breaker in operation, each Trip Unit pro-

tection setting must be set to the values specified by the person 

responsible for the installation .  The number of settings that must 

be made is determined by the protection supplied as illustrated in 

Figures 11 through 18 .  Each setting is made with a rotary switch, 

using a small screwdriver .  The selected setting for each adjustment 

appears in its respective rectangular viewing window as illustrated in 

Figure 2 .
The installed rating plug establishes the maximum continuous cur-

rent rating (I

n

), up to, but not exceeding the Frame Rating of the cir-

cuit breaker .  Instantaneous and ground current settings are defined 

in multiples of (I

n

) .

To illustrate the effect of each protection curve setting, simulated 

Time-Current curves are pictured on the face of the Trip Unit .  The 

rotary switch used to make each setting is located nearest that 

portion of the simulated Time-Current curve it controls .  Should an 

automatic "TRIP" occur (as a result of the current exceeding the 

pre-selected value), the LED in the appropriate segment of the simu-

lated Time-Current curve will light "RED", indicating the reason for 

the "TRIP" .
The available settings, along with the illustrated effect of changing 

the settings are given in Figures 11 through 18 .

3.2  Long Delay Current Setting

There are eight (8) available Long Delay "Pick-up" Current Settings, as 

illustrated in Figure 11 .  Each setting, called "

 I

r

, is expressed as a 

multiple (ranging from 0 .5 to 1) of the rating plug current (I

n

) .

otee:

N

I

r

"

 is also the basis for the Short-Delay Current Setting (see 

Section 3 .4) .

Figure 11. Long Delay Current Settings.

3.3  Long Delay Time Setting

There are eight (8) available Long Delay Time Settings, as illustrated 

in Figure 12, ranging from 2 to 24 seconds .  These settings are the 

total clearing times in seconds, when the current value equals six 

(6) times 

I

r

 .  The (LS) Time-Current Curve applicable for your circuit 

breaker gives complete details (see Section 5) .

Figure 12. Long Delay Time Settings.

Long Delay

Available Settings 

Setting

.5, ,6, .7, .8,

.85, .9, .95, 1

In Multiples of

Rating Plug

Amperes

I

r

I

r

I

r

I

n

(I  )

n

I

r

.

,

,

Available Settings 

12, 15, 20, 24

I...

Seconds at

6 Times

,

.

. .

.

.

6

x

Long

Time

Delay

Sec.

at 6 x

I

r

I

r

4

(I  )

r

Long Delay Setting

2, 4, 7, 10,

otee:

N

In addition to the standard Long Delay Protection Element, the Digitrip 

RMS 510 Trip Unit also has a Long Time Memory (LTM) function, which 

serves to protect load circuits from the effects of repeated overload condi-

tions .  If a breaker is re-closed soon after a Long Delay Trip, and the current 
again exceeds the Long Delay Current Setting, 

I

r

, the 

LTM

 automatically 

reduces the time to trip, to allow for the fact that the load circuit temperature 

is already higher than normal, due to the prior overload condition . Repeated 

overload can cause LTM to trip the breaker after a time delay less than the 

“Long Delay Time Setting” . When the load current returns to normal, the 

LTM

 begins to reset; and after about 10 minutes it has reset fully, so that 

next Long Delay trip time will again be the "Setting" value .  To reset the LTM 

quickly, see Section 4 .4, Item 3 .

In certain applications it may be desirable to disable the LTM function . The 

LTM function can be disabled by (first opening the breaker and then) remov-

ing the Rating Plug and lastly moving the LTM jumper (inside the rating plug 

cavity, see Figure 13) to its "INACTIVE" connection . (You can enable the LTM 

function again any time you wish by moving the LTM jumper back to its origi-

nal "ACTIVE" connection .)
The action of the LTM is a factor to consider in performing multiple Long 

Delay Time tests . (See Section 4 .4 .)

Figure 13. Long Time Memory "LTM" Jumper.

otee:

N

There is a condition under which the Long Delay Trip LED can errone-

ously indicate a LDT has occurred, even though the breaker is still closed . 

This can happen when an overload current momentarily exceeds the Long 

Delay Current Setting, Ir, so that the Long Delay LED flashes "RED" to indicate 

the overload condition . Then if, at the very moment when the LED is "ON", 

the load current would then suddenly drop to a value less than 10% of the 

breaker frame (or current sensor) rating, the trip unit stops functioning while 

the "4bit Latch Chip" (See Fig . 1) is set and the LED remains lit . If the current 

would again increase to a value above the Long Delay Current Setting, I,, and 

then return to normal, the LDT will reset itself . You can of course, manually 

clear the LDT (or any other trip indication) at any time, by pushing the "PUSH 

to RESET" button . (See Figure 2 .)

3.4  Short Delay Current Setting

There are eight (8) available Short Delay "Pick-up" Current Settings, 

as illustrated in Figure 14 .  Six settings are in the range from 2 

to 6 times 

I

r

 and the other two settings are "S1" or "S2" times 

I

r

 

(REMEMBER: 

I

r

 

is the Long Delay Current Setting) .  The values that 

"S1" and "S2" have depend upon the type of circuit breaker, and are 

specified both on the rating plug label (see Figure 9) and on the 

applicable (LS) Time-Current Curve referenced in Section 5 .

Figure 14. Short Delay Current Settings.

Rating Plug Cavity 

LTM

Active

.  . 

S1 and S2

2, 2.5, 3, 4

Available Settings 

.  . 

.

Setting

In Multiples of

Long Delay Setting

Values are Specified on Rating Plug

5, 6, S  , S

1

2

I

r

(I  )

r

Содержание Cutler-Hammer Digitrip RMS 510

Страница 1: ...Effective August 2011 Supersedes I L 29 885C 12 10 Instruction Leaflet I L 29 885D Instructions for Digitrip RMS 510 Trip Unit...

Страница 2: ...Back up Battery Check 14 4 5 2 Replacing the Back up Battery 14 5 References 15 5 1 Digitrip RMS Trip Assemblies 15 5 2 Type DS Low Voltage AC Power Circuit Breakers 15 5 3 Type DS II Low Voltage AC P...

Страница 3: ...cuit breakers and type SPB Systems Pow R circuit breakers and Series C R Frame molded case circuit breakers The Digitrip RMS 510 Trip Unit pro vides three basic functions Function Section Protection 1...

Страница 4: ...round Protection SPB Rating Plug View Settings in Window Adjust Protection Settings for Desired Values with Rotary Switches Trip Unit Operation Status Blinking Green OK See Section 1 1 1 R Frame Ratin...

Страница 5: ...inte grally mounted in the circuit breaker The Digitrip RMS 510 Trip Unit is available in six different types Each Trip Unit may be equipped with a maximum of five phase and two ground time current se...

Страница 6: ...fective August 2011 Instructions for Digitrip RMS 510Trip Unit EATON CORPORATION www eaton com Figure 5 Digitrip RMS 510 Type LSI Figure 6 Digitrip RMS 510 Type LIG Figure 7 Digitrip RMS 510 Type LSG...

Страница 7: ...show DIS in the window ONLY ONE position shows blank Note N When the OVERRIDE window shows blank the only fast acting high short circuit protection available is the OVERRIDE Fixed Instantaneous see Se...

Страница 8: ...an carry continuously However for proper coordination of over current pro tection it is often desirable to choose different levels of In for differ ent circuit breakers of the same frame rating An ass...

Страница 9: ...ck LED The bat tery in the rating plug is OK if the LED lights Green when the bat tery check button next to it is pushed see Section 4 5 Note N The back up battery is used only to maintain the cause o...

Страница 10: ...otect load circuits from the effects of repeated overload condi tions If a breaker is re closed soon after a Long Delay Trip and the current again exceeds the Long Delay Current Setting Ir the LTM aut...

Страница 11: ...Plug In Setting Inst I n 5 6 M M 2 2 5 3 4 1 2 3 7 No Instantaneous Current Setting For types LS and LSG Trip Units please see Sections 1 1 3 DlScriminator High initial Current Release and 1 1 4 OVERR...

Страница 12: ...IZED DEATH OR SEVERE PERSONAL INJURY CAN RESULT FROM CONTACT WITH ENERGIZED EQUIPMENT DE ENERGIZE THE CIRCUIT AND DISCONNECT THE CIRCUIT BREAKER BEFORE PERFORMING MAINTENANCE OR TESTS REFER TO THE APP...

Страница 13: ...MS 510 Trip Unit also has a Long Time Memory function LTM which serves to protect load circuits from the effects of repeated overload conditions see Note 1 under Section 3 3 Long Delay Time Setting Th...

Страница 14: ...S 510 Trip Unit The battery is located in the rating plug along with a battery check push button and a green battery check LED see Figure 9 4 5 1 Back up Battery Check The battery is a long life lithi...

Страница 15: ...lemental Digitrip RMS and Optim Trip Units with Type DS II I L 8700C39 and DSL II Low Voltage AC Power Circuit Breakers AD 32 870 Typical Time Current Characteristic Curves for Types DS II and DSL II...

Страница 16: ...the event that the feeder breaker Z2 would not clear the fault the main breaker Z1 will clear the fault in 0 5 s as above Fault 1 There are no interlocking signals The main breaker trip unit will init...

Страница 17: ...17 Instruction Leaflet I L 29 885D Effective August 2011 Instructions for Digitrip RMS 510Trip Unit EATON CORPORATION www eaton com Notes...

Страница 18: ...18 Instruction Leaflet I L 29 885D Effective August 2011 Instructions for Digitrip RMS 510Trip Unit EATON CORPORATION www eaton com Notes...

Страница 19: ...19 Instruction Leaflet I L 29 885D Effective August 2011 Instructions for Digitrip RMS 510Trip Unit EATON CORPORATION www eaton com Notes...

Страница 20: ...between the parties This literature is not intended to and does not enlarge or add to any such contract The sole source governing the rights and remedies of any purchaser of this equipment is the con...

Отзывы: