Effective 10/2004
Page 67
I.L. 70C1036H05
Appendix D - Display Menu Diagrams Continued
VIEW
OFF
58.0 to 62.0 (60Hz)
48.0 to 52.0 (50Hz)
steps of 0.1Hz
1 to 250s
90 t0 670V
OFF
(steps of 1V)
0.2 to 5.0 s
180 to 720V
OFF
(steps of 1V)
OFF,
1 to 65500 kW
(steps of 1)
1 to 250s
OverVOLT
TRIP
V
RevPower
TRIP
UndrVOLT
TIME
s
UndrVOLT
TRIP
V
VOLTAGE
SETTING
ENABLED
*
DISABLED
1 to 250s
UndrFREQ
TRIP
. Hz
OverFREQ
TRIP
. Hz
OverVOLT
TIME
s
UndrFREQ
TIME
. s
OverFREQ
TIME
. s
OFF
58.0 to 62.0 (60Hz)
48.0 to 52.0 (50Hz)
steps of 0.1Hz
0.2 to 5.0 s
5% to 50%
OFF
(steps of 1%)
VOLT UN-
BALANCE
%
RevPower
TIME
s
1 to 250s
VOLT UN-
BALANCE
s
* This is the Master Setting that will disable (enable) all the following trip functions.
It also disables (enables) the associated voltage alarm functions.
Appendix D - Page D-17B
Program
VOLTAGE