Effective 10/2004
Page 61
I.L. 70C1036H05
Appendix D - Display Menu Diagrams Continued
LSIG XX
IEC XX
LSIG XX
IEEE XX
IEEE XX
LSIG XX
VIEW
Program
LSIG Curve
(Page D-13)
SHORT PU
. xIr
XXXXX A
INST PU
. x In
XXXXX A
GROUND
SLOPE
GND PU
.
XXXX A
PHASE
SLOPE
PICKUP
.
Ir=XXXXA
PHASE
TimeDial
.
GROUND
TIME
s
EXT GND
CT RATIO
NEUTRAL
PROTECT
%
AMP UN-
BALANCE
%
AMP UN-
BALANCE
s
PHASE
LOSS
0.40 - 1.00
(steps of
0.05)
0.1 - 5.0
0.2 - 5.0
0.2 - 5.0
(steps of 0.1)
1.5 - 10.0x or
1.5 - 12x or
1.5 - 14x
(steps of 0.5)
(and additional
setting M1)
0.10 - 0.50
(steps of
0.05)
50%
100%
5% - 25%
OFF
(steps of
1%)
0 - 240 s
(steps of 1 s)
1 to 30 s
OFF
(steps of 1 s)
none
1000/1
800/1
400/1
200/1
100/1
50/1
25/1
10/1
IEC-A
IEC-B
IEC-C
Program
Current Curve
IEEE/IEC
Represents the active
curve.
"ON" or left blank,
automatically. (Not editable.)
Set to "ON" if settings are
saved within that curve.
Only one "ON" at a time.
XX =
SHORT
TIME
. s
2.0 - M1
OFF
(steps of 0.5)
IEC XX
LSIG XX
MOD INV
VERY INV
EXT INV
Screen is
skipped if first
AMP UN-
BALANCE is set
to "OFF"
Screen is skipped
if LSI curve is
selected.
Screen is skipped if
LSIG factory style. Also
requires 4 pole circuit
breaker or separately
wired Neutral Sensor
Screens are
skipped if LSI
factory style
0.05 - 1.00
0.10 - 1.00
0.20 - 1.00
(steps of 0.05)
0.10 - 0.50
(steps of
0.05)
IEEE
0.24 - 1.00 x In
or x Ext GND CT
(steps of 0.01)
FLAT
I
2
T
MOD INV
VERY INV
EXT INV
IEC-A
IEC-B
IEC-C
= 10x or
= 12x or
= 14x
M1
none denotes
default
to In value
If IEC -EF style
"EARTH" will
replace
"GROUND"
*
VIEW
SEL
SEL
SEL
SEL
IEC
0.10 - 1.00 x In
or x Ext GND CT
(steps of 0.01) and
OFF setting
.
11LSIG or
11PLSIG
Catalog #
11IEC-EF or
11PIECEF
Catalog #
Screen
skipped if
breaker
contacts B-6
is not
connected
to B-7
Appendix D - Page D-12