Series CEP7
Solid State Overload Relay

Operating Modes

 

Figure 3. Contact Status

 

Adjustments

 

Figure 4. Trip Current Adjustment

Figure 5. Motor Current Rating

ATTENTION: Do not use automatic reset mode in applications where unexpected automatic restart of the
motor can cause injury to persons or damage to equipment.

CEP7-M32__
CEP7-M37__
CEP7-M45__
CEP7-M85__
CEP7-M110__
CEP7-M180__

CEP7-A32__
CEP7-A37__
CEP7-A45__
CEP7-A85__
CEP7-A110__
CEP7-A180__

Man (Manual): Reset by pushing 
button in. (Standard Offering)

Trip: Push and turn reset button 
counterclockwise to manually trip. 
This action causes N.O. and N.C. 
contacts to change state. Releas-
ing button reverts device to 
manual mode.

Auto: Push and turn reset button 
to auto position. The relay resets 
automatically — approximately 
2 minutes after tripping. 
(Optional Offering)

Trip: Push and turn reset button 
counterclockwise to manually trip. 
This action causes N.O. and N.C. 
contacts to change state. Releas-
ing button reverts device to 
manual mode.

To adjust trip current, turn dial until the desired current is 
aligned with the 

 pointer. Trip rating is 120% of dial setting.

Trip Indicator Window
Yellow indicator not visible: Not Tripped
Yellow indicator visible: Tripped

Push to Test