15
9.1.1
Battery change nLLK 15 LED N 1/6
-
Open the second reflector flap. (fig. 3)
-
Remove both plugs from the battery.
-
Open fixing screw approx. one turn. Move
battery cover along to the open gap. (fig.4)
-
Remove the cover together with the battery
from the light fitting.
Now the battery is not secured against
falling!
-
Insert a new battery (fig. 16) in reverse order.
-
Observe the polarisation of the battery,
when installing.
LED funktion display
LED on:
normal charging operation
LED off:
emergency ligth
/
no charging
/
charging fault
LEDflasching:
error
fluorescent lamps
(z.B.: EOL cut off)
- both
fluorescent lamps off
- emergency ligth out of order
Troubleshooting:
change fluorescent lamps
After troubleshooting the light fitting have to be reset .
by turning off the charging circuit
9.1.2 Battery change nLLK 15 LED N 2/6
Open the light fitting protective bowl
before opening the battery compartment.
This interrupts the emergency lighting circuit.
-
Cover of the battery box unscrew with an
Allen key (Fig11).
-
Disconnect cables on the connectors
-
remove trop down holder (Fig 13).
-
Solve the holder for battery with a Phillips
screwdriver (Fig 14).
-
Remove holder and remove battery
(Fig15).
-
Include battery (Fig 16) in reverse order.
9.2 Taking into operation after
Battery change
After the battery has been changed, take the
light fitting into operation as described under
Chapter 5, „taking into operation“.
Explosion protected light fittings zone 2 and zone 22
Series: nLLK 15 LED N
GB
10. Disposal / Recycling
When the apparatus is disposed of, the
respective national regulations on waste disposal
will have to be observed.
In case of disposal you can obtain additional
information from your Cooper Crouse-Hinds /
EATON branch.
Subject to modifications or supplement of the
product range.