12
Explosion protected light fittings zone 2 and zone 22
Series: nLLK 15 LED N
2. Technical data
GB
1. Safety instructions:
Target group:
For skilled electricians and
suitable qualified, instructed
personnel in accordance with national
legislation, including the relevant
standards and, where applicable, in acc.
with IEC/EN 60079-14 on electrical
apparatus for explosive atmospheres.
– The light fitting is not suitable for use in
hazardous areas of zone 0, 1, 21 and zone
20!
– The requirements of the IEC/EN 60079-31
regarding excessive dust deposits and
temperature to be considered from the
user.
– The technical data indicated on the light
fitting are to be observed!
– Disconnect equipment before opening!
– Avoid powering up repeatedly for short
periods of time.
– Changes of the design and modifications
to the light fitting are not permitted!
– The light fitting shall be operated as
intended and in undamaged and perfect
condition!
– Only genuine Cooper Crouse-Hinds (CCH) /
EATON spare parts may be used for
replacement!
– Repairs may only be carried out by CCH /
EATON or a qualified “electrician”!
– Do not keep these operating instructions
inside the light fitting during operation!
Observe the national safety rules and
regulations for prevention of accidents and
the following safety instructions which are
marked with an ( ) in these operating
instructions!
nLLK 15 LED N 600
1,5 h
nLLK 15 LED N 1200
1,5 h
ATEX type examination certificate zone 2/22
CCH 15 ATEX 1044
Marking acc. to 2014/34/EU and standard: IEC/EN 60079
Zone 2
D
II 3G__see table 1
Zone 22
D
II 3D__see table 1
Rated voltage
see table 1
cos
ϕ
0.95 cap.
Lamps to be fitted
Fluorescent lamps with G13 bi-pin cap to
nLL* 15 N 600
8 W
Aura UltiLED Long Life
nLL* 15 N 1200
17 W
26 W
Aura UltiLED Long Life /
Aura UltiLED pro Long Life
Protection acc. to IEC/EN 60529
IP 66
Insulation class to IEC/EN 61140
I
max. permissible ambient temperature
1)
see table 1
Storage temperature in original packing
-25 °C to +55 °C
Supply terminal clamping capacity per clamp
terminal (2.5 mm²)
2 x 2.5 mm²
Supply terminal clamping capacity
2 x per screw-terminal
single-wire
multi-wire
min.
1.5 mm
2
1.5 mm
2
max.
6.0 mm
2
6.0 mm
2
Conductor cross-section with through-wiring
2.5 mm
2
for max. 16 A
Cable entries moulded plastics
M25 x 1.5
suitable cables and test torques of the pressure
screw
Ø cable
Nm pressure screw
Seal 1+2+3
1 2
3
min.
8.0
1.5
max.
(2)
10.0
2.0
Seal 1+2
1 2
3
min.
10.0
2.3
max.
(2)
13.0
2.6
Seal 1
1 2
3
min.
13.5
1.3
max.
(2)
17.5
2.3
Test torque for screw in thread cable entry
3.0 Nm
For permanently laid cables only
Cable entries metal thread
M20 x 1.5
Test torque for breathing plug M25 x 1,5:
3.0 Nm
Dimensions of light fittings and for mounting
see fig. 2
Lamp weight
1/6
2/6
nLLK 15 LED N 600
approx. 5.5 kg
approx. 6.5 kg
nLLK 15 LED N 1200
approx. 7.5 kg
approx. 8.5 kg
Rated emergency light duration
1.5 h /
Luminous flux factor for 1 lamp in emergency
operation
1.5 h
nLLK 15 LED N 600
1/6
1030 lm (50 %)
nLLK 15 LED N 600
2/6
1030 lm (50 %)
nLLK 15 LED N 1200
1/6
1050 lm (25 %)
Batterytype/ Order No:
see spare parts list
Charging period of a totally discharged
battery > 90 % of rated capacity
approx. 24 h
(1)
Intensive sun radiation in areas of high ambient temperatures may cause inadmissible temperature rise inside
of the luminaire. This may result a decrease in lifetime of the electronic ballast (EVG). Therefore those
luminaires should be switched off during daytime by a photocell control.
(2)
The tests of clamping ranges and torque values were performed with metal mandrel. The clamping range can
vary by using cables with different manufacturing tolerances and material properties. Please use a suitable
combination of seals in the intermediate area, so that the cap nut can be tightened in future maintenance work
on the cable entry.