12
Explosion protected light fittings zone 2 and zone 21/22
Series: nLLK N 08
2. Technical data
GB
1. Safety instructions:
Target group:
For skilled electricians and
suitable qualified, instructed
personnel in accordance with national
legislation, including the relevant
standards and, where applicable, in acc.
with IEC/EN 60079-14 on electrical
apparatus for explosive atmospheres.
– The light fitting is not suitable for use in
hazardous areas of zone 0, 1 and zone 20!
– The requirements of the IEC/EN 60079-31
regarding excessive dust deposits and
temperature to be considered from the
user.
– The technical data indicated on the light
fitting are to be observed!
– Disconnect equipment before opening!
– Avoid powering up repeatedly for short
periods of time.
– Changes of the design and modifications
to the light fitting are not permitted!
– The light fitting shall be operated as
intended and in undamaged and perfect
condition!
– Only genuine Cooper Crouse-Hinds (CCH) /
EATON spare parts may be used for
replacement!
– Repairs may only be carried out by CCH /
EATON or a qualified “electrician”!
– Do not keep these operating instructions
inside the light fitting during operation!
Observe the national safety rules and
regulations for prevention of accidents and
the following safety instructions which are
marked with an ( ) in these operating
instructions!
Light fittings with G13 bi-pin cap
nLLK 08 018/18 N 1,5 h
2 x 18 W
nLLK 08 018/18 N 3,0 h
2 x 18 W
nLLK 08 036/36 N 1,5 h
2 x 36 W
nLLK 08 036/36 N 3,0 h
2 x 36 W
ATEX type examination certificate zone 2/22
BVS 09 ATEX E 147
Marking acc. to 2014/34/EU and standard: IEC/EN 60079-0
Zone 2
D
II 3G__see table 1
Zone 22
D
II 3D__see table 1
ATEX EC- type examination certificate zone 21
BVS 09 ATEX E 162
Marking acc. 2014/34/EU
and standard:
IEC/EN 60079-0
Zone 21
D
II 2D__see table 1
IECEx Certification of conformity zone 2/22
IECEx BVS 11.0065
IECEx Category of application
Zone 2
Ex nA ... see table 1 ... Gc
Zone 22
Ex tc ... see table 1 ... Dc
IECEx Certification of conformity zone 21
IECEx BVS 12.0069
IECEx Category of application
Zone 21
Ex tb ... see table 1 ... Db
Rated voltage
see table 1
cos
ϕ
0.95 cap.
Lamps to be fitted
Fluorescent lamps with G13 bi-pin cap to
18 W
IEC/EN 60081-2220
36 W
IEC/EN 60081-2420
Protection acc. to IEC/EN 60529
IP 66
Insulation class to IEC/EN 61140
I
max. permissible ambient temperature
1)
see table 1
Storage temperature in original packing
-25 °C to +45 °C
Supply terminal clamping capacity per clamp
terminal (2.5 mm²)
2 x 2.5 mm²
Supply terminal clamping capacity
2 x per screw-terminal
single-wire
multi-wire
min.
1.5 mm
2
1.5 mm
2
max.
6.0 mm
2
6.0 mm
2
Conductor cross-section with through-wiring
2.5 mm
2
for max. 16 A
Cable entries moulded plastics
M25 x 1.5
suitable cables and test torques of the pressure
screw
Ø cable
Nm pressure screw
Seal 1+2+3
1 2
3
min.
8.0
1.5
max.
(2)
10.0
2.0
Seal 1+2
1 2
3
min.
10.0
2.3
max.
(2)
13.0
2.6
Seal 1
1 2
3
min.
13.5
1.3
max.
(2)
17.5
2.3
Test torque for screw in thread cable entry
3.0 Nm
For permanently laid cables only
Cable entries metal thread
M20 x 1.5
Test torque for breathing plug M25 x 1,5:
3.0 Nm
Dimensions of light fittings and for mounting
see fig. 2
Lamp weight
1/6
2/6
nLLK N 08 018/18
approx. 5.5 kg
approx. 6.5 kg
nLLK N 08 036/36
approx. 7.5 kg
approx. 8.5 kg
Rated emergency light duration
1.5 h / 3.0 h
Luminous flux factor for 1 lamp in emergency
operation
1.5 h
3.0 h
nLLK 08018/18 N 1/6
880 lm (65 %)
415 lm (30 %)
nLLK 08018/18 N 2/6
880 lm (65 %)
415 lm (30 %)
nLLK 08036/36 N 1/6
1200 lm (36 %)
-
nLLK 08036/36 N 2/6
1200 lm (65 %)
1040 lm (30 %)
Batterytype/ Order No:
see table page 15 „Spare parts“
Charging period of a totally discharged
battery > 90 % of rated capacity
approx. 24 h
(1)
Intensive sun radiation in areas of high ambient temperatures may cause inadmissible temperature rise inside
of the luminaire. This may result a decrease in lifetime of the electronic ballast (EVG). Therefore those
luminaires should be switched off during daytime by a photocell control.
(2)
The tests of clamping ranges and torque values were performed with metal mandrel. The clamping range can
vary by using cables with different manufacturing tolerances and material properties. Please use a suitable
combination of seals in the intermediate area, so that the cap nut can be tightened in future maintenance work
on the cable entry.
Содержание Crouse-Hinds nLLK 08 N Series
Страница 16: ...16 ...
Страница 17: ...17 ...
Страница 18: ...18 Notizen Notes ...
Страница 19: ...19 Notizen Notes ...