Class 41 (0x29): Control Supervisor Object
Instance Count: 1
Instance List: 1
Table 62. S611 Control Supervisor Instance Attributes
Attrib NV Access
Data
Type Name
Description
3
V
Set/Get
BOOL
Run1
Run the softstarter.
7
V
Get
BOOL
Running1
Indicates if the motor is running.
10
V
Get
BOOL
Fault Status
A Fault has occurred. Faults are
latching and require a reset.
12
V
Set/Get BOOL
Fault Reset
0->1 Causes a reset.
13
V
Get
UINT
Fault Code
If in faulted state, faultcode indi-
cates the fault that caused the
transition to the faulted state.
15 V
Get BOOL
Control
from
Net
Control is coming from the
network.
101
V
Get
WORD Device Status
Device Bit Array, Bit:
0: Fault
1: Bypass
2: Running1
3: S611 Run/Aux Relay (Relay 1)
4: S611 Fault Relay (Relay 2)
5: CtrlFromNet
6: Permissive
7: Reserved
8: Output #1
9: Output #2
10: Input #1
11: Input #2
12: Input #3
13: Input #4
14: DeviceNet Low Power
15: S611 Intercom Lost
102
V
Get
UINT
Trip Reason
Bit = Description
0 = Overload
1 = Jam
2 = Stall
3 = Current Imbalance
4 = Load Disconnect
5 = Phase Loss
6 = Mains Fault
7 = Phase Reversal
8 = Shorted SCR
9 = SCR Not Firing
10 = Pole Overtemp
11 = Bypass Dropout
12 = SCR Overcurrent
13 = Contactor Overcurrent
14 = Communication Fault
15 = Other Device Fault
103
V
Get
UINT
Motor Status
Motor Control Status Bits:
Bit = Description
0 = Run
2 = In Bypass
5 = Fault
11 = Relay 1 State
12 = Relay 2 State
13 = Control From Network
14 = Permissive State
105 NV
Set/Get
UINT
Network
Timeout
Network Watchdog or Timeout
enable.
0 = Disable
1 = Enable
106 NV
Set/Get
UINT
Communication
Loss Behavior
1 = Fault
2 = Hold last state
3 = Stop (1)
Table 62
.
S611 Control Supervisor Instance Attributes (Cont.)
Attrib NV Access
Data
Type Name
Description
107 NV
Set/Get
BOOL
Motor
Ctrl
Com Loss Act
Disable
When this value is TRUE the
motor state will be unchanged
after a communication loss
event. A FALSE value will
cause the Motor Control
Communication Loss Value to be
applied on a com loss.
108
NV
Set/Get BOOL
Motor Ctrl Com
Loss Action Val
Action to execute when a com-
munication loss event occurs.
0 = Ignore (No Change)
1 = Stop
109
V
Get
UINT
Fault Code
Fault Code and Fault Code List.
When read as a single item it
is the most recent fault. When
read as a list, faults are listed in
history order. Newest are at the
beginning, oldest are at the end
of the list.
If the device is in the Faulted
state, Fault Code indicates the
fault that caused the transition
to Faulted state.
If not in the Faulted state, the
Fault Code indicates the fault
that caused the last transition to
the Faulted state.
110
V
Get
UINT
Fault Code
Entry 1
111
V
Get
UINT
Fault Code
Entry 2
112
V
Get
UINT
Fault Code
Entry 3
113
V
Get
UINT
Fault Code
Entry 4 .
114
V
Get
UINT
Fault Code
Entry 5
115
V
Get
UINT
Fault Code
Entry 6
116
V
Get
UINT
Fault Code
Entry 7
117
V
Get
UINT
Fault Code
Entry 8
118
V
Get
UINT
Fault Code
Entry 9
119 V
Set/Get
BOOL
Clear
Fault
Queue
Set this parameter to TRUE to
clear the fault queue.
120 NV
Set/Get
UINT
Fault
Enable
Bits
Fault Enable Bits:
Bit = Description
0 = Overload
1 = Jam
2 = Stall
3 = Current Imbalance
4 = Load Disconnect
5 = Phase Loss
6 = Under Voltage
7 = Over Voltage
8 = Voltage Unbalance
9 = Phase Reversal
10 = Ground Fault
11 = Overload On Start
12 = Shorted SCR
13 = SCR Not Firing
14 = Over Temperature
150
V
Set/Get UINT
Motor Control
Motor Control Bits:
Bit = Description
0 = Run
2 = Permissive
3 = Reset
151 NV
Set/Get
UINT
Start
Input
Behavior
Selects the behavior for the start
input. When edge is selected,
a start will only be performed
on the rising edge of the start
input. When level is selected,
a start will occur any time the
input is high.
0 = Edge
1 = Level
152 NV
Set/Get
UINT
Fault
Relay
Config
Fault Relay Configuration:
0 = Faulted
1 = Not Faulted