4
User Manual
MN04200002E
Effective January 2016
C441 Ethernet module user manual
(C441R, C441T, C441U, C441V)
EATON
www.eaton.com
The C441R and C441U provide connection for four AC Input points
the ratings for these inputs are:
Table 6. AC Input Ratings
Specification
Value
Number of Inputs
4
Nominal voltage
120 Vac
Nominal Current
15 mA
Operating Range
80 – 140 Vac
Operating Frequency
50/60 Hz
Signal Delay Max
30 ms
Input Type
IEC 61131-2, type 1 digital
The C441T and C441V provide connection for four DC Input points.
The ratings for these inputs are:
Table 7. DC Input Ratings
Specification
Value
Number of Inputs
4
Nominal voltage
24 Vdc
Nominal Current
5 mA
Type
Current Sinking
Input Type
IEC 61131-2, type 1 digital
All units provide two output relays. The ratings of the relay outputs
are:
Table 8. Relay Output Ratings
Specification
Value
Num Contacts
2 Independent Relays (1 Form C, 1 Form A)
Thermal Contact
5 A
Rated Insulation Voltage
300 Vac
Max Operating Voltage
120 Vac
Max Operation Current
5 A
Electrical Life
1
10
5
Operations
Mechanical Life
1
10
6
Operations
3 Mounting and Dimensions
3.1 C441R and C441T
The Ethernet module is designed to be installed on the right side of
the Motor Insight base unit.
Figure 1. Installation Diagram
1. Align module with side of Motor Insight base unit
2. Slide module bottom pegs in appropriate slots
3. Rotate module up and gently click the base unit and module
together.
The resulting dimensions of the Motor Insight base unit and
Ethernet module is shown in Figure 2.