IB140012EN
For more information visit: www.eaton.com
Instructional Booklet
Effective: March 2021
Page
27
Operation and Maintenance Manual,
Automatic Transfer Switch Controller, ATC-900
5.6 Programming Setpoints for Inputs (Rules)
There are some rules to follow when particular Inputs are pro-
grammed.
1. In the setpoints, Time Delay Neutral (TDN) must be set to
"n/a" when using "Load Decay." Conversely, "Load Decay"
must be set to "n/a" if "TDN" is being used.
2. The voltage unbalance protection can be disabled by the user
simply by setting them to "0".
3. With the Input of the controller programmed to the following
inputs, associated setpoints will also be required to be appro-
priately set.
48M1
I/O Module (1)
O
O
O
O
O
O
O
O
O
O
48M2
I/O Module (2)
O
O
O
O
O
O
O
O
O
O
48M3
I/O Module (3)
O
O
O
O
O
O
O
O
O
O
48M4
I/O Module (4)
O
O
O
O
O
O
O
O
O
O
48U
USB Port for Memory Stick
S
S
S
S
S
S
S
S
S
Programmable Outputs
80B
Input Terminal Blocks
0
0
0
S
S
0*
0*
S
S
80C
Output Terminal Blocks
0
0
0
S
S
O
O
S
S
81A
General Alarm Indication Contact (OUTPUT)
P
P
P
P
P
P
P
P
P
O
81B
Monitor Mode (OUTPUT)
P
P
P
P
P
P
P
P
P
O
81C
ATS in Test (OUTPUT)
P
P
P
P
P
P
P
P
P
O
81D
Engine Test Aborted (OUTPUT)
P
P
P
P
P
P
P
P
P
O
81E
Cooldown in Process (OUTPUT)
P
P
P
P
P
P
P
P
P
O
81F
Engine Start Contact Status Gen 1 & Gen 2 (OUTPUT)
P
P
P
P
P
P
P
P
P
O
81G
LOAD SHED - S2 Inhibit On (OUTPUT)
P
P
P
P
P
P
P
P
P
O
81GL
LOAD SHED - S2 Inhibit On w/white indicating light
OF
OF
OF
OF
OF
OF
OF
OF
OF
O
81H
ATS on Bypass (OUTPUT)
P
P
P
P
P
P
P
P
P
O
Only one type NO or NC may be programmed per system.
81J
Lockout
PF
PF
PF
PF
PF
PF
PF
PF
PF
I
81K
Monitor Mode (NC or NO)
P
P
P
P
P
P
P
P
P
I
81N Health
P
P
P
P
P
P
P
P
P
0
81P
BP Safety Interlock Alarm (Unit will not transfer)
P
P
P
P
P
P
P
P
P
I
81R
Waiting for Sync
P
P
P
P
P
P
P
P
P
0
81S
Closed Transition Inhibit (81T with Switch)
P
P
P
P
P
P
P
P
P
I
Three Source ATS Control (Primary/Secondary)
90A
Primary Control Gen 2 Start Status (OUTPUT)
P
P
P
P
P
P
P
P
P
O
90B
Secondary Input (INPUT)
P
P
P
P
P
P
P
P
P
I
* Contactor D & E Wallmount and D & E frame Closed Transition have Input Terminals Blocks with S2 Engine Start.
Table 8. ATC-900 Features and I/O (Cont.).
ATC-900 FEATURES
P = Programmable (Internal or I/O), PF = Prgammable Fixed I/O
O = Optional, OF = Optional Fixed, S = Standard
CONTACTOR
MCCB
MAGNUM
ATC9
BIC9
CBC9
CTC9
ATx9
ATV9
CBV9
C2
C3
C5
C/D
C/D
C3
BIV9
CTV9
I/O
INPUT
SETPOINT(S)
Manual Retransfer
Manual Retransfer, Preferred Source
Enable Manual Retransfer
Manual Retransfer
Preferred Source Selector
Preferred Source
Emergency Inhibit
Preferred Source
Go to Emergency
Preferred Source
Secondary
Operating Mode, # of Generators, Preferred Source
Engine Test Mode Select
Engine/PE Test Mode