Effective December 2009

Instructional Leaflet IB48041

Instructions for AMPGARD 400A

medium voltage starter

 Danger

reaD anD unDerstanD this manual in its  

entirety before installing or operating the 

controller. installation, aDjustment, repair, 

anD maintenance of these controllers  

must be performeD by qualifieD personnel.  

a qualifieD person is one who is familiar  

with the construction anD operation of  

this equipment anD the hazarDs involveD.

Introduction

This instruction book is intended to cover  

the handling, installation, operation, and mainte-

nance of AMPGARD

T

 400A, 7.2 kV starters and 

associated equipment. The function of these  

controllers is to start, stop, and protect medium 

voltage motors, transformers, capacitors, and  

other loads. Controllers may be of full voltage, 

reduced voltage reactor, reduced voltage  

autotransformer, reduced voltage solid-state, or 

two-speed type. They may control induction or  

synchronous machines, and they may be  

non-reversing or reversing.
While this instructional leaflet is dedicated primarily 

to full-voltage starting, the other applications listed 

are an expansion of the principles identified in this 

leaflet. This leaflet does not purport to cover all 

possible contingencies, variations, and details that  

may arise during operation or maintenance of this 

equipment. If further information is desired  

regarding this product, contact your local Eaton 

sales office. 

Identification

A rating nameplate is located on the door of each 

controller. Contained on this nameplate are the  

controller type and ratings as required by industry 

standards. Also contained on this nameplate is the 

factory’s general order number. This number should 

be given to the Eaton sales office if a question 

should arise concerning the equipment or if renew-

al parts are required. Refer to 

Figure 1

 for typical 

location of rating nameplates.

Содержание Ampgard 400

Страница 1: ...former reduced voltage solid state or two speed type They may control induction or synchronous machines and they may be non reversing or reversing While this instructional leaflet is dedicated primari...

Страница 2: ...ake Break Short time current 30 seconds 1 second 8 6 milliseconds 0 5 cycle Standard service altitude Optional service altitude Mechanical life Electrical life BIL Dielectric strength 60 Hz Closing ti...

Страница 3: ...oor The low voltage compartment is fabricated from steel sheets to provide iso lation from the medium voltage components mounted behind the low voltage compartment A window is provided in the low volt...

Страница 4: ...y equipped with high interrupting contactors to prevent the inadvertent installation of standard interrupting contactors into those cells Figure 7 SL Vacuum Contactor Contactors are typically three po...

Страница 5: ...closing at the same time Low voltage control The low voltage control compartment is located in a steel pocket in the medium voltage door A low voltage door with up to four device panels provides acce...

Страница 6: ...ass ropes or cables through the lift holes Use slings with safety hooks or shackles of adequate load rating Each controller is properly adjusted at the factory before shipment However vibration and me...

Страница 7: ...Compartment Control connections Control wires may enter the enclosure from either the top or the bottom For lineups with main bus a low voltage wireway is located in the left front of the bus compartm...

Страница 8: ...are must be taken to ensure no damage is inflicted on the controller control power transformer CPT potential transformers PT or to the controller load Removal of the primary fuses is sufficient to pro...

Страница 9: ...of the fuse If a fuse has blown due to a fault it is likely that the other fuses experienced a similar overcurrent condition In this case Eaton recommends that all three fuses be replaced Ensure that...

Страница 10: ...e fingers Inspect for any signs of mechanical wear or overheating To withdraw the removable portion 1 Remove the three main fuses 2 Remove the control plug 3 Remove the cotter pin and clevis pin from...

Страница 11: ...Reinstallation is the reverse of the procedure previously discussed Make sure that the shaft of the removable portion of the switch is rotated to the fully open position before reinstallation Danger I...