Instruction Manual 

IM01005021E

Effective April 2014

Installation Instructions for Eaton’s Aegis Surge

Protective Device AGPHxxxxx and AGPVxxxxx

EATON www.eaton.com

Installation

 

WARNING

INSTALLING AN SPD THAT IS IMPROPERLY RATED FOR THE ELECTRICAL 

SYSTEM VOLTAGE COULD CREATE A POTENTIALLY HAZARDOUS 

CONDITION, RESULTING IN INJURY OR EQUIPMENT DAMAGE.

 

CAUTION

EATON SPD PRODUCTS MUST BE INSTALLED OR REPLACED BY A 

QUALIFIED ELECTRICIAN TO AVOID INJURY OR EQUIPMENT DAMAGE.

 

WARNING

TURN OFF THE POWER SUPPLY BEFORE WORKING IN ANY ELECTRICAL 

CABINET OR ON ANY CIRCUIT BREAKER PANEL.  FAILURE TO DO SO 

COULD RESULT IN INJURY OR DEATH FROM ELECTRICAL SHOCK.

NOTICE

A POOR GROUND, OR GROUNDING/BONDING VIOLATIONS, COULD 

PREVENT THE SPD FROM PERFORMING AS SPECIFIED.

For optimal protection, place the Aegis PH and PV as close as possi-

ble to the load being protected .  Eaton recommends that the wiring 

from the Aegis PH and PV output terminals to the input terminals of 

the electronic equipment be kept as short and straight as possible .  

This will prevent the wiring from acting as an antenna that picks up 

high frequency noise from the environment .  Wiring length to the 

input terminals of the Aegis PH and PV is not critical .

• 

To prevent the risk of electrical shock, TURN OFF and Lock Out 

all power sources to the electrical circuit where the Aegis PH and 

PV is to be installed .

• 

Verify that the power has been disconnected with a portable volt-

meter or other measuring device .

Enclosure Mounting (New applications)

Every Aegis PH and PV includes a DIN Rail and two mounting 

screws (#8 Sheet metal screw) to mount the device .  Drill appropri-

ate hole sizes, based on material and thickness, at desired spacing 

using the DIN Rail slots as a template . After the DIN Rail has been 

secured, engage the Aegis PH or PV base (Output side, enclosure 

bottom) of the DIN Clip onto the DIN Rail and compress DIN clip 

spring by pushing the enclosure towards the Input terminal side of 

the enclosure bottom until the opposite side of the DIN Clip hook 

engages the DIN Rail . Then slowly release the spring pressure of the 

DIN clip securing the Aegis enclosure to the DIN Rail .  Proceed to 

the appropriate Wiring Instructions .

Enclosure Mounting (Existing Aegis HW  
applications)

Aegis HW devices were mounted either with the use of a DIN Rail 

or by the enclosure’s base feet with two screws .  If the device was 

mounted using the enclosure’s base feet, uninstall the Aegis HW 

and dispose of the old hardware .  If the Aegis HW was mounted 

using the DIN Rail feature, place a screwdriver in the slot on the DIN 

Clip (Output side at bottom of enclosure), pulling the DIN Clip out 

to release the enclosure from the DIN Rail .  If the previous device 

was DIN Rail mounted you can reuse the existing DIN Rail to mount 

the new Aegis PH device .  Engage the Aegis PH base (Output side, 

enclosure bottom) of the DIN Clip to the DIN Rail and compress 

DIN clip spring by pushing the enclosure towards the Input terminal 

side of the enclosure until the opposite side of the DIN Clip hook 

engages . Then slowly release the spring pressure securing the Aegis 

PH enclosure to the DIN Rail .

Wiring Instructions Aegis PH

 - Install an overcurrent protection 

device on the input side of the Aegis PH .  Wire from the overcur-

rent protection device to the input terminal(s) of the Aegis PH .  The 

terminals are marked L, N, and G .  Wire gauge should be selected 

to match the amperage of the overcurrent protection device .  Ensure 

that the proper color wire is used (green or green/yellow – ground, 

white or light blue – neutral, black and/or red – phase) .  Tighten all 

input and output terminal connections to 9 lb-in .  Wire from the 

Aegis PH output terminals to the input terminals of the protected 

load .  Tighten all input and output terminal connections to 9 lb-in .  

Install terminal block covers by pressing into place on both the input 

and output terminals . If the Form C contact is used for remote 

monitoring there will be one – N .O . and one – N .C . contact .  The 

terminal connections are labeled on the top of the enclosure .  To 

activate, connect the Form C output terminals to an alarm, light or 

building monitoring system .  Tighten all Form C terminal connections 

to 4 lb-in .  The relay is rated for a maximum of 250V and 8 amperes .  

Recheck all connections .  Restore power to the electrical circuit .  

Check that the status indicator (green LED) is illuminated .  If using 

the Form C relay contact, check to see that it is operating as desired .

Figure 1. Aegis PH Dimensions.

Содержание Aegis AGPHxxxxx series

Страница 1: ...y Precautions 2 Operation 2 Preparation 2 Installation Procedures 3 Enclosure Mounting New Applications Aegis PH and Aegis PV 3 Enclosure Mounting Existing Aegis HW applications 3 Wiring Instructions...

Страница 2: ...le for bonded systems that are L N G as shown in Figures 1 and 3 or for Unbonded systems that utilize L L G as shown in Figures 2 and 4 The amperage and voltage rating is also indicated in the catalog...

Страница 3: ...o the DIN Rail Proceed to the appropriate Wiring Instructions Enclosure Mounting Existing Aegis HW applications Aegis HW devices were mounted either with the use of a DIN Rail or by the enclosure s ba...

Страница 4: ...4 Installation Instructions for Eaton s Aegis Surge Protective Device AGPHxxxxx and AGPVxxxxx EATON www eaton com Figure 2 Aegis PH Premium Hybrid Filter Bonded System Block Diagram Figure 3 Aegis PH...

Страница 5: ...and compress DIN clip spring by pushing the enclosure towards the Input terminal side of the enclosure until the opposite side of the DIN Clip hook engages Then slowly release the spring pressure sec...

Страница 6: ...ril 2014 Installation Instructions for Eaton s Aegis Surge Protective Device AGPHxxxxx and AGPVxxxxx EATON www eaton com Figure 5 Aegis PV Premium Filter Bonded System Block Diagram Figure 6 Aegis PV...

Страница 7: ...he LED monitor or remote monitoring Form C contact indicates a failure check the overcurrent protection on the power supply Replace or reset the overcurrent protection If a problem still exists contac...

Страница 8: ...r s rights under the warranty shall consist solely of requir ing Eaton to repair or at Eaton s sole discretion replace free of charge F O B factory and defective items received at said factory within...