Instruction Manual 

IM01005021E

Effective April 2014

Installation Instructions for Eaton’s Aegis Surge

Protective Device AGPHxxxxx and AGPVxxxxx

EATON www.eaton.com

Diagnostics

The Aegis PH and PV are supplied with a green LED that will illumi-

nate and indicate power at the output terminals .  If the green LED is 

not illuminated, it indicates that power is not being supplied to the 

Aegis .  The LED will not illuminate if there has been a utility power 

failure, or an internal failure of the Aegis suppression components .  

If the internal suppression components fail, a short circuit will result .  

The short circuit will open the overcurrent device on the power sup-

ply, removing power to the Aegis .   Whenever power is removed 

from an Aegis PH or PV, the green LED will not illuminate, and the 

optional monitoring relay (Form C contact), if installed, will change 

state .

Maintenance

Preventive Maintenance (Inspection and Cleaning)

 – Periodic 

system inspections, cleaning, and connection checks are recom-

mended to ensure reliable system performance .  There is no defined 

schedule for preventive maintenance, as conditions will vary from 

installation to installation .

Corrective Maintenance (Repair or Replacement) 

– the Aegis 

PH and PV are designed to provide years of continuous service .  

However, even the most reliable equipment may fail .  In the unlikely 

case that the LED monitor or remote monitoring (Form C contact) 

indicates a failure, check the overcurrent protection on the power 

supply .  Replace or reset the overcurrent protection .  If a problem 

still exists, contact Eaton’s Surge Protection application support at: 

1-800-809-2772, option 4, option 2 .

Terms and Conditions of Sale

The Terms and Conditions of Sale are listed in the Eaton Selling 

Policy, Publication No . SP03000001E .

Specifications

Table 3.  Specifications

Application

Aegis PH 

2 W&G Grounded Systems

Aegis PV 

2 W&G Grounded Systems

Input Voltage

120V, 220V, 240Vac single-phase

120V, 220V, 240Vac single-phase

Amperage

3, 5, 10, 15, & 20 amperes

1, 3, 5 amperes

Frequency

50/60 Hz

50/60 Hz

Protection Modes

L-N, L-G, & N-G

L-N, L-G, & N-G

MCOV

150V & 275V

150V & 275V

Noise Attenuation (Normal Mode)

75dB @ 110 KHz

50dB @ 100 KHz

Filter Bandwidth

10 kHz to 100 MHz

10 kHz to 100 MHz

Total Peak Surge Current

30kA per mode

20kA per mode

Operating Temperature

-40°F to +122°F (-40°C to +50°C)

-40°F to +122°F (-40°C to +50°C)

Response Time

Less than one nanosecond

Less than one nanosecond

Agency Approvals

UL 1449 3

rd

 Edition, UL 1283 5

th

 Edition, CSA

UL 1449 3

rd

 Edition, UL 1283 5

th

 Edition , CSA

Warranty

10 years standard / 5 additional years if registered on-line **

10 years standard / 5 additional years if registered on-line **

Form C Contacts

Yes

No

External Circuit Breaker*

25A, 240V/415V, 10kA Min. AIC Rating

7A, 240V/415V, 10kA Min. AIC Rating

RoHS Compliant

Yes

Yes

  *External circuit breaker sold separately.

**Register products on-line at www.eaton.com/spd.  Then click on “Warranty Registration”.

Содержание Aegis AGPHxxxxx series

Страница 1: ...y Precautions 2 Operation 2 Preparation 2 Installation Procedures 3 Enclosure Mounting New Applications Aegis PH and Aegis PV 3 Enclosure Mounting Existing Aegis HW applications 3 Wiring Instructions...

Страница 2: ...le for bonded systems that are L N G as shown in Figures 1 and 3 or for Unbonded systems that utilize L L G as shown in Figures 2 and 4 The amperage and voltage rating is also indicated in the catalog...

Страница 3: ...o the DIN Rail Proceed to the appropriate Wiring Instructions Enclosure Mounting Existing Aegis HW applications Aegis HW devices were mounted either with the use of a DIN Rail or by the enclosure s ba...

Страница 4: ...4 Installation Instructions for Eaton s Aegis Surge Protective Device AGPHxxxxx and AGPVxxxxx EATON www eaton com Figure 2 Aegis PH Premium Hybrid Filter Bonded System Block Diagram Figure 3 Aegis PH...

Страница 5: ...and compress DIN clip spring by pushing the enclosure towards the Input terminal side of the enclosure until the opposite side of the DIN Clip hook engages Then slowly release the spring pressure sec...

Страница 6: ...ril 2014 Installation Instructions for Eaton s Aegis Surge Protective Device AGPHxxxxx and AGPVxxxxx EATON www eaton com Figure 5 Aegis PV Premium Filter Bonded System Block Diagram Figure 6 Aegis PV...

Страница 7: ...he LED monitor or remote monitoring Form C contact indicates a failure check the overcurrent protection on the power supply Replace or reset the overcurrent protection If a problem still exists contac...

Страница 8: ...r s rights under the warranty shall consist solely of requir ing Eaton to repair or at Eaton s sole discretion replace free of charge F O B factory and defective items received at said factory within...

Отзывы: