Input supply
line-to-line voltage [V]
UPS rating [kW]
30
40
50
80
100
400
Phase cables [mm
2
]
1 x 16
1 x 25
1 x 35
1 x 70
1 x 95
Protective bonding ca-
ble [mm
2
]
1 x 16
1 x 16
1 x 16
1 x 35
1 x 50
415
Phase cables [mm
2
]
1 x 16
1 x 25
1 x 35
1 x 70
1 x 95
Protective bonding ca-
ble [mm
2
]
1 x 16
1 x 16
1 x 16
1 x 35
1 x 50
440
Phase cables [mm
2
]
1 x 16
1 x 25
1 x 35
1 x 70
1 x 95
Protective bonding ca-
ble [mm
2
]
1 x 16
1 x 16
1 x 16
1 x 35
1 x 50
480
Phase cables [mm
2
]
1 x 10
1 x 25
1 x 35
1 x 70
1 x 95
Protective bonding ca-
ble [mm
2
]
1 x 10
1 x 16
1 x 16
1 x 35
1 x 50
690
Phase cables [mm
2
]
1 x 6
1 x 10
1 x 16
1 x 35
1 x 95
Protective bonding ca-
ble [mm
2
]
1 x 6
1 x 10
1 x 16
1 x 16
1 x 50
Note: Note that power upgrading of the UPS is possible only if the sizing of
external cables is sufficient. Alternatively, external cabling must be upgraded
as well. The type of the fuses is gG.
Cable sizing is based on IEC 60364-5-52. Sizing is for installation method C
(wall installation) of PVC insulated copper wires. Conductor temperature: 70
°C, ambient temperature: 30 °C.
When using aluminium cables, check sizing recommendations from Eaton
product support.
Table 9: Rated and maximum currents for rated power and voltage
Rated
power [kW]
Rated
voltage [V]
Rectifier input
Bypass input UPS output
Rated
current [A]
Maximum
current [A]
Rated
current [A]
Rated
current [A]
30
208
96
113
92
85
230
87
102
83
77
380
48
57
46
46
400
46
54
44
44
415
44
52
42
42
440
45
53
43
40
480
42
49
40
37
690
29
34
28
26
Eaton 9PHD Accessory Cabinets TFC-A, EBC-F
and EBC-G
User's and installation guide
©