• through the left side panel
• through the right side panel
• through the back panel
• through the bottom panel
By default, Eaton UPSs and battery cabinets should only be used with valve-
regulated lead-acid (VRLA) batteries. For the battery specification of your UPS,
see the User’s and Installation Guide of your UPS. Only use batteries that have
been approved by Eaton. If you have to connect other type of batteries or other
energy storage means, consult an authorized Eaton Customer Service Engineer
before you proceed with the installation.
The battery block configuration in the chosen battery cabinet must always match
the UPS requirement. The used battery configuration must be entered into the
UPS settings during commissioning or start-up. Refer to the UPS User’s and
Installation Guide for the UPS configuration.
Both battery cabinets have a temperature sensor (Harness 9PHD EBC
temperature sensor, P-152001325).
If you must use wiring other than that supplied with the cabinet, the following or
similar wiring is recommended.
Table 2: Wiring recommendations and cable connectors
EBC model
F
G
Breaker rating (A)
200
400
DC connector size (max. mm
2
)
1)
2 x 150
2 x 150
DC connector torque (Nm)
30
30
DC power cable cross area (min. mm
2
)
2)
vs.
UPS rating
(For a maximum of two cabinets in daisy chain)
30...50 kW 50
70
60...80 kW 70
70
90...100 kW 95
95
110...150 kW
2 x 70
160...200 kW
2 x 95
210...250 kW
2 x 120
260...300 kW
2 x 150
Protective bonding connector size (max. mm
2
)
1)
150
M10
Protective bonding connector torque (Nm)
30
41
Protective bonding cable cross area (min.
mm
2
)
2)
vs. UPS rating
30...50 kW 25
35
60...80 kW 35
35
Eaton 9PHD Accessory Cabinets TFC-A, EBC-F
and EBC-G
User's and installation guide
©