Main Menu
Submenu
Available settings
Default settings
Local settings
Language
[English] [Français] [Deutsch]
[Español] [Italiano] [Português]
[Polish]
Menus, status, notices and alarms,
UPS fault, Event Log data and
settings are in all supported
languages.
[English]
Automatic message for user
configuration when UPS is
powered for the first time.
Protected access
[Enabled] [Disabled]
Allow the user to lock the settings
modification. Password is: 0577
[Disabled]
Audible alarm
[Enabled] [Disabled on battery]
[Always Disabled]
Enable or disable the buzzer if an
alarm occurs.
[Enabled]
In/Out settings
Output voltage
[200V][208V][220V][230V][240V]
[230 V]
Output frequency
[Auto sensing]
[Frequency Converter 50Hz]
[Frequency Converter 60Hz]
[Auto sensing]
HE Mode
[Enabled] [Disabled]
[Disabled]
Overload prealarm
[50%] … [102%]
Load % when overload alarm
occurs
[102%]
ON/OFF settings
Cold Start
[Enabled] [Disabled]
[Enabled]
Auto Restart
[Enabled] [Disabled]
[Enabled]
Auto Start
[Enabled] [Disabled]
[Disabled]
Start On Bypass
[Enabled] [Disabled]
[Disabled]
Sleep Mode
[Enabled] [Disabled]
If Disabled, LCD and
communication will turn OFF
immediately after UPS is OFF.
If Enabled, LCD and
communication stay ON
[Enabled]
Site Wiring Fault
[Enabled] [Disabled]
Prevents the UPS from starting if
the phase and neutral wires are
swapped.
[Disabled]