UPS Operating Instructions
Eaton 9E UPS (20–30 kVA, 208/220V) Generation 3 Installation and Operation Manual P-164000301—Rev 1
www.eaton.com/powerquality
6-23
CAUTION
All power to the critical load is lost when the LOAD OFF is selected in the following step. You
should use this feature only when you want to de-energize the critical load.
4.
Select Yes or no, then press the
RETURN
pushbutton.
Selecting Yes will immediately shut down the UPS and de-energize the critical load. Selecting No will abort
the shutdown.
5.
If another UPS is to be shut down, proceed to that UPS and repeat Step 1 through Step 4.
CAUTION
Do not attempt to restart the system after Load Off until the cause of the shutdown has been
identified and cleared.
6.
To restart the UPS after pressing the
LOAD OFF
pushbutton, follow the procedure in paragraph 6.4.1 or
6.4.2.
WARNING
Power is present inside the UPS cabinet after the upstream input feeder circuit breakers are
opened because of the installed internal batteries.
6.4.13 Using the Remote Emergency Power-off Switch
A UPS emergency power-off is initiated by the REPO pushbutton switch. In an emergency, you can use this
switch to control the UPS output. The REPO switch de-energizes the critical load and powers down the UPSs
immediately, without asking for verification.
The UPSs, including Bypass, remains off until restarted.
CAUTION
All power to the critical load is lost when the REPO switch is activated in the following step. You
should use this feature only when you want to de-energize the critical load.
To use the REPO switch:
1.
Firmly push the red pushbutton until it locks into place. The switch latches into the activated state
(see Figure 6-8).
The rectifier, inverter, battery, and bypass switchgear open, and the power module is turned off
immediately, without asking for verification.
CAUTION
Do not attempt to restart the system after the REPO until the cause of the shutdown has been
identified and cleared.
NOTE
The following instructions are for the Eaton-supplied REPO switch. If a
customer-supplied REPO switch is used, it may not activate in the same manner;
refer to the operating instructions provided with the switch.
Содержание 9E
Страница 1: ...Eaton 9E UPS 20 30 kVA 208 220V Generation 3 Installation and Operation Manual ...
Страница 2: ......
Страница 3: ...Eaton 9E UPS 20 30 kVA 208 220V Generation 3 Installation and Operation Manual ...
Страница 21: ...Section 1 Installation ...
Страница 22: ......
Страница 65: ...Section 2 Operation ...
Страница 66: ......
Страница 113: ......
Страница 114: ... P 164000301 1 P 164000301 1 ...