Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03
37
Table 9. Input/Output Ratings and Wiring Recommendations: 10– 30 kW (208/208) (Continued)
Minimum Conductor Size (Ground)
Number
–
AWG or kcmil
(each)
10
(1)
8
(1)
6
(1)
NOTE
Callout letters
A
,
B
,
C
and
D
map to
, and
93PM-L System Oneline Schematics.
Line-up-and-match battery wiring with a 105°C rating is factory supplied with the Eaton 93PM-L Integrated Battery
Cabinet (IBC).
Eaton recommends installing the UPS using wiring and external overcurrent protection breakers sized for the fully rated
UPS kW frame size installed.