146
Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03
88..22..11
D
DA
AIILLYY M
Maaiinntteennaannccee
Perform the following steps daily:
1.
Check the area surrounding the UPS system. Ensure the area is not cluttered, allowing free access to the
unit.
2.
Ensure the air intakes (vents on the front door of the UPS cabinet and the exhaust openings (on the rear of
the UPS cabinet) are not blocked.
3.
Ensure the operating environment is within the parameters specified in
Chapter 9
Product
Specifications
.
4.
Ensure the UPS is in Normal mode (Normal status indicator is illuminated). If an alarm lamp is illuminated
or the Normal status indicator is not illuminated, contact an Eaton service representative.
88..22..22
M
MO
ON
NTTH
HLLYY M
Maaiinntteennaannccee
Perform the following steps monthly:
1.
Monitor system parameters as described in paragraph
2.
Check the UPS air filter (located behind the front door) and wash or replace as necessary. See
for
filter location. Contact an Eaton service representative for replacement filters.
CAUTION
Verify the spare washed filter is thoroughly dry before installing.
To remove the filters:
a.
Unfasten the front door by lifting the latch from the bottom and turning to the right (counterclockwise)
and swing the door open (see
).
b.
Remove the foam filters from the frame on the front door.
c.
Install the customer’s spare foam filters, either washed or new foam filters, into the frame on the
front door.
!
IMPORTANT
The foam filters are to be replaced with new or washed filter immediately. The ups is not meant to be run
without filters installed.
d.
Close the front door and secure the latch.
3.
Record maintenance results and any corrective actions in a suitable log.
Содержание 93PM-L 60-1
Страница 1: ...p n P 164000711 Revision 03 20 60 kW 208V UPS Installation and Operation Manual Eaton 93PM L UPS ...
Страница 4: ......
Страница 12: ...xii Eaton 93PM L 20 60 kW 208V UPS Installation and Operation Manual P 164000711 Rev 03 List of Tables ...
Страница 22: ...10 Eaton 93PM L 20 60 kW 208V UPS Installation and Operation Manual P 164000711 Rev 03 Introduction ...
Страница 112: ...100 Eaton 93PM L 20 60 kW 208V UPS Installation and Operation Manual P 164000711 Rev 03 UPS System Installation ...
Страница 156: ...144 Eaton 93PM L 20 60 kW 208V UPS Installation and Operation Manual P 164000711 Rev 03 Communication ...
Страница 164: ...P 16400071103 P 164000711 03 ...