
Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03
39
Table 10. Input/Output Ratings and Wiring Recommendations: 40–60 kW (208/208) (Continued)
Minimum Conductor Size (Ground)
Number
–
AWG or kcmil
(each)
6
(1)
6
(1)
4
(1)
NOTE
Callout letters
A
,
B
,
C
and
D
map to
, and
93PM-L System Oneline Schematics.
Line-up-and-match battery wiring with a 105°C rating is factory supplied with the Eaton 93PM-L Integrated Battery
Cabinet (IBC).
Eaton recommends installing the UPS using wiring and external overcurrent protection breakers sized for the fully rated
UPS kW frame size installed.
Содержание 93PM-L 60-1
Страница 1: ...p n P 164000711 Revision 03 20 60 kW 208V UPS Installation and Operation Manual Eaton 93PM L UPS ...
Страница 4: ......
Страница 12: ...xii Eaton 93PM L 20 60 kW 208V UPS Installation and Operation Manual P 164000711 Rev 03 List of Tables ...
Страница 22: ...10 Eaton 93PM L 20 60 kW 208V UPS Installation and Operation Manual P 164000711 Rev 03 Introduction ...
Страница 112: ...100 Eaton 93PM L 20 60 kW 208V UPS Installation and Operation Manual P 164000711 Rev 03 UPS System Installation ...
Страница 156: ...144 Eaton 93PM L 20 60 kW 208V UPS Installation and Operation Manual P 164000711 Rev 03 Communication ...
Страница 164: ...P 16400071103 P 164000711 03 ...