Figure 18. Battery trip wiring for 93PM G2 UPS
A
UPS
5
Shunt trip coil -
B
External battery breaker
6
Shunt trip coil +
C
External battery breaker
7
Aux contact return
1
BAT_Shunt_DET
8
Aux contact
2
GND
9
Shunt trip coil -
3
Aux contact return
10
Shunt trip coil +
4
Aux contact
5
5..4
4
IInnssttaalllliinngg U
UPPSS eexxtteerrnnaall b
baatttteerryy ccaab
biinneett aanndd b
baatttteerryy p
poow
weerr ccaab
blliinngg
There is a vast offering of different Eaton external battery cabinets available for the 93PM G2 UPSs.
Please refer to the three-phase accessories offering for further details. See a separate manual for
instructions on how to install Eaton external battery cabinets.
NOTE:
Do not connect battery strings with different battery quantity and voltage in parallel.
EATON 93PM G2 UPS
USER’S AND INSTALLATION GUIDE
P-164000956 - February 2021
www.eaton.eu
5
51
1