UPS CTO models
Phase cables [mm
2
]
Rectifier, bypass and
maintenance bypass input
fuse [A]
PE cable [mm
2
]
93PM G2 xxx(180) 0.9
pF
185
315
95
93PM G2 xxx(250)
2 x 120
500
120
93PM G2 xxx(300) 0.9
pF
2 x 185
630
185
CAUTION
Make sure that prospective short-circuit current resulting at the input terminals
of the UPS is equal or less than conditional short-circuit current declared on the
type plate (and technical specification) of the UPS. Also make sure that the
prospective short-circuit current meets the minimum requirements listed in
Table
Minimum required short circuit current ratings for AC source and battery
Table 9. Minimum required short circuit current ratings for AC source and battery supply
UPS model
Minimum short circuit current, AC ports
[kA]
Minimum short circuit current, battery
port [kA]
93PM G2 xxx(yyy)
4
4
Table 10. Minimum recommended multi-core cable and fuse sizes for battery connection
UPS standard models
Battery cable, pos. & neg.
line [mm
2
]
Battery PE cable
Battery fuse [A]
93PM G2 xxx(200)
2 x 95 per pole
95
630
93PM G2 xxx(240) 0.9
pF
2 x 95 per pole
95
630
93PM G2 xxx(300)
2 x 150 per pole
150
800
93PM G2 xxx(360) 0.9
pF
2 x 185 per pole
185
1000
UPS CTO models
Battery cable, pos. & neg.
line [mm
2
]
Battery PE cable
Battery fuse [A]
93PM G2 xxx(100)
95
50
315
93PM G2 xxx(120) 0.9
pF
150
95
400
93PM G2 xxx(150)
185
95
500