3
3..9
9
BBaassiicc ssyysstteem
m ccoonnffiigguurraattiioonnss
U
UPPSS p
poow
weerr rraattiinngg
The maximum attainable UPS system power rating is determined by the size of the UPS cabinet frame.
The number of UPM power modules determines the nominal power rating of the UPS. If upgradeability is
required, the UPS frame size should be chosen according to the future maximum load rating, and the
number of UPMs is chosen according to the capacity requirements on day one.
The following UPS configurations with different frame sizes and number of UPMs are possible.
Table 2. UPS configurations
Frame
Power rating
Static switch rating
# of power
modules
Power module
rating
Output power
factor
200 kW
50-200 kW
200 kW
1-4
50 kW
1.0
300 kW
50-300 kW
300 kW
1-6
240 kVA
60-240 kVA
240 kVA
1-4
60 kVA
0.9
360 kVA
60-360 kVA
360 kVA
1-6
The UPS frames can be connected in parallel to create even larger systems. A maximum of eight UPSs
can be connected in parallel.
U
UPPSS oop
pttiioonnss aanndd aacccceessssoorriieess
The following table shows different standard and optional UPS features.
Table 3. Standard and optional UPS features
Feature
Frame
200/240 kVA frame
300/360 kVA frame
Touch screen display
X
X
Battery start
X
X
Integrated backfeed protection
X
X
Static bypass protective fuses
X
X
Internal maintenance bypass switch (MBS)
O
—
Battery breaker for external batteries
O
O
Sync control interface
O
O
Top air exhaust kit
O
O
Parallel cable kit
O
O
Single feed kit
O
O
EATON 93PM G2 UPS
USER’S AND INSTALLATION GUIDE
P-164000956 - February 2021
www.eaton.eu