background image

Operates incandescent, magnetic and electronic ballast fluorescent, high power factor compact fluorescent, and high intensity discharge (HID) lamp types.

How to Specify:

Unit

14.0 kVA

Battery

2,995 lbs.

Cabinet

(1,358 kg)

Electronics

465 lbs.

Cabinet

(211 kg)

Total System

3,460 lbs.
(1,569 kg)

L1PH Series Uninterruptible Power Supplies

L1PH

Page 1 of 2

14.0 kVA Single Phase UPS System

Job Information

Type:

Job Name:
Cat. No.:

Lamp(s):
Notes:

Lightolier 

a Genlyte Thomas Company

www.lightolier.com

631 Airport Road, Fall River, MA 02720 • (508) 679-8131 • Fax (508) 674-4710
We reserve the right to change details of design, materials and finish.
© 2004 Genlyte Thomas Group LLC (Lightolier Division) • D0504

Overall Characteristics

• 86% throughput efficiency
• Operating temperature range 32°F (0°C) to 104°F (40°C)
• Internal maintenance by-pass is standard
• Main load disconnect switch standard
• Double conversion, no interruption
• Standard backup time of 90 minutes, other run times optional
• Output circuit breakers and normally-off loads optional

Housing

• Free standing, NEMA 1 enclosure
• Acid resistant powder coat finish
• Multiple conduit entries

Metering/Controls

Standard
• Alpha-numeric front panel display with 14 metered measurements and 

53 messages/alarms

• Normal, caution and alarm indicating LEDs
• Audible failure alarms with silence switch
• Dry contact for remote failure alarm
• “D” type 9-pin computer interface connector (see pin config. on back)
• Programmable battery monitor with alarm

Optional
• Diagnostics software for remote computer (PC) monitoring and control
• Stand-alone remote display mimics all measurements, indications and 

alarms shown on the front panel display

• Additional RS-232 input/output port for remote monitoring and system 

control

Electrical

• Sine Wave Output
• Completely solid-state Pulse Width Modulation (PWM) inverter
• 16-bit microprocessor control
• Input power factor correction maintains power factor at 0.99
• Transient response 

 

5%; Recovery time, 10 mS (100% load step)

• 3:1 crest factor capability
• Inverter output distortion

 

2.5% THD (at unity power factor)

• Output voltage regulation ±6% of nominal at full load
• Frequency within ±0.05% of nominal
• Inverter efficiency

 

84%

• Load power factor capability is 0.5 leading to 0.5 lagging

(Continued on page 2)

NOTE:

Input circuit

breaker not available.
Input switch is 
standard.

L1PH

I

14.0

S

SERIES

INPUT

SYSTEM

BASE

BATTERY

OUTPUT

OUTPUT

# ON 2ND

NORMALLY

# OF

NOL

VOLTAGE

TYPE

SIZE

TYPE

VOLTAGE

CKT BRKRS

1

VOLTAGE

OFF LOAD

NOL

VOLTAGE

L1PH = Single
Phase
Uninterruptible
Power
Supplies

14.0 = 14.0 kVa

2 = 208 V
3 = 240 V
4 = 277 V
Z = Special
Voltage

(Consult 
Factory)

1 = 120 V
2 = 208 V
3 = 240 V
4 = 277 V
5 = 120/208 V
6 = 120/240 V
7 = 120/277 V
Z = Special
Voltage

(Consult 
Factory)

Y = Hardwire
A = 1 0CB
B = 2 0CB
C = 3 0CB
D = 4 0CB
E = 5 0CB
F = 6 0CB
G = 7 0CB
H = 8 0CB
J = 9 0CB
K = 10 0CB
L = 11 0CB
M = 12 0CB
N = OCBA1
P = OCBA2
R = OCBA3
S = OCBA4
T = OCBA5
U = OCBA6
V = OCBA7
W = OCBA8
X = OCBA9

0
1
2
3
4
5
6
7
8
9

10
11

A = No
B = Yes
C = Yes w/ Time
Delay Timer

0 = No NOL
Y = Hardwire
Terminal
1 = 1
2 = 2
3 = 3
4 = 4
5 = 5
6 = 6
7 = 7
8 = 8
9 = 9
10 = 10
11 = 11 
12 = 12

X = None
A = 1st
B = 2nd

I = ETL Listed 
to UL 924 for
Emergency
Lighting
Applications

S = Sealed
Lead Calcium

34.0”

86.4 cm

33.0”

83.8 cm

70.0”

177.8 cm

Battery

Cabinet

33.0”

83.8 cm

30.0”

76.2 cm

43.5”

110.5 cm

Electronics

Cabinet