Eaton 93PM Emergency Lighting UPS (50 kW, 480V Three and Four-Wire UL 924) Installation and Operation Manual P-164000569—Rev 03
29
C
Chhaapptteerr 44 U
UP
PS
S S
Syysstteem
m IInnssttaallllaattiioonn
44..11
P
Prreelliim
miinnaarryy IInnssttaallllaattiioonn IInnffoorrm
maattiioonn
WARNING
Installation should be performed only by qualified personnel.
Refer to the following while installing the UPS system:
•
Review
UPS Installation Plan and Unpacking
for cabinet dimensions, equipment weight, wiring
and terminal data, and installation notes.
•
Do not tilt the cabinets more than ±10° during installation.
•
Remove conduit landing plates to add conduit landing holes as required.
•
If perforated floor tiles are required for ventilation, place them in front of the UPS.
44..22
U
Unnllooaaddiinngg tthhee U
UP
PS
S C
Caabbiinneett ffrroom
m tthhee P
Paalllleett
WARNING
•
The UPS cabinet is heavy (see
).
•
Do not tilt cabinet more than 10° from vertical.
•
Lift the cabinets only with a forklift or damage may occur.
•
Ensure the forklift is rated to handle the weight of the cabinet.
Failure to follow these instructions may result in severe injury or death.
NOTE
For the following steps, verify that the forklift or pallet jack is rated to handle the weight
of the cabinet (see
for cabinet weight).
The UPS cabinet is bolted to a pallet consisting of four metal angle supports secured to two wood supports.
To remove the pallet:
1.
If not already accomplished, use a forklift or pallet jack to move the UPS cabinet to the installation area, or
as close as possible, before unloading from the pallet. Insert the forklift or pallet jack forks between the
supports on the bottom of the pallet (see
or
and their corresponding tables for the UPS
cabinet center of gravity measurements).
2.
Open the front door by lifting the latch from the bottom and turning to the right (counterclockwise) and
swing the door open.
3.
Locate the four 1/2" jacking bolts from the parts kit and install them in the threaded holes in the front and
rear supports as shown in
. Place a floor protector from the parts kit underneath each jacking bolt,
and screw the bolts down against them.
The floor protectors protect the floor from being marred by the jacking bolts.