The UPS is housed in a free-standing cabinet with safety shields behind the door. The UPS is available in
50 or 60 Hz with various output power ratings.
Model
Power Rating
Frequency
Eaton 93PM-50-1
20 kW
50/60 Hz
Eaton 93PM-50-1
30 kW
50/60 Hz
Eaton 93PM-50-1
40 kW
50/60 Hz
1100..22
S
Sppeecciiffiiccaattiioonnss
The following sections detail the input, output, environmental, and battery specifications for the UPS.
1100..22..11 U
UP
PS
S IInnppuutt
Operating Input Voltage
Rectifier: 480 Vac Wye, 3W + ground. Neutral not used.
Bypass: 480 Vac Wye, 3W or 4W + ground.
Operating Input Frequency Range
50/60 Hz
Operating Input Current
See
.
Reduced for Generator
Adjustable
Input Current Harmonic Content
3% THD at full load
Power Factor
Minimum 0.99
Line Surges
6 kV OC, 3 kA SC per ANSI 62.41 and IEC 801 4
Battery Voltage
240 cell – 480 Vdc
Battery Charging Capacity
29.3 A maximum per 50 kW module at full load at nominal input voltage
1100..22..22 U
UP
PS
S O
Ouuttppuutt
UPS Output Capacity
100% rated current
Output Voltage Regulation
± 1% (10% to 100% load)
Output Voltage
480 Vac Wye, 3W or 4W + ground
Output Voltage Harmonic Content
1.5% maximum THD (linear load)
5% maximum THD (nonlinear load)
Output Current
See
.
Output Voltage Balance
< 2% for 100% maximum load imbalance (linear load)
Output Voltage Phase Displacement
< 2.5° for 100% maximum load imbalance (linear load)