background image

Eaton 93PM Emergency Lighting UPS (50 kW, 480V Three and Four-Wire UL 924) Installation and Operation Manual P-164000569—Rev 03

v

7.3.8 Transfer from Double Conversion to Bypass Mode and Shut Down the UPM .................................................. 86

7.3.9 UPS and Critical Load Shutdown ............................................................................................................ 87

7.3.10 Charger Control ................................................................................................................................ 87

7.3.11 Battery Test ..................................................................................................................................... 87

7.3.12 Using the UPS LOAD OFF Command .................................................................................................... 88

7.3.13 Using the Remote Emergency Power-off Switch ..................................................................................... 88

88 C

Coom

mm

muunniiccaattiioonn ...................................................................................................................................................................................................................................................................................... 8899

8.1 Minislot Cards.......................................................................................................................................... 89

8.2 Building Alarm Monitoring .......................................................................................................................... 89

8.3 General Purpose Relay Contact ................................................................................................................... 90

8.4 PredictPulse Remote Monitoring and Management Service............................................................................... 90

8.4.1 PredictPulse Service Features ............................................................................................................... 90

8.4.2 Installing PredictPulse ......................................................................................................................... 91

99 U

UP

PS

S M

Maaiinntteennaannccee................................................................................................................................................................................................................................................................................ 9933

9.1 Important Safety Instructions ...................................................................................................................... 93

9.2 Performing Preventive Maintenance ............................................................................................................. 93

9.2.1 DAILY Maintenance ............................................................................................................................ 94

9.2.2 MONTHLY Maintenance ...................................................................................................................... 94

9.2.3 PERIODIC Maintenance ....................................................................................................................... 95

9.2.4 ANNUAL Maintenance......................................................................................................................... 95

9.2.5 BATTERY Maintenance........................................................................................................................ 95

9.3 Installing Batteries .................................................................................................................................... 96

9.4 Recycling the Used Battery or UPS............................................................................................................... 96

9.5 Maintenance Training ................................................................................................................................ 96

1100 P

Prroodduucctt S

Sppeecciiffiiccaattiioonnss .............................................................................................................................................................................................................................................................. 9977

10.1 Model Numbers ..................................................................................................................................... 97

10.2 Specifications......................................................................................................................................... 97

10.2.1 UPS Input........................................................................................................................................ 97

10.2.2 UPS Output ..................................................................................................................................... 97

10.2.3 UPS Environmental ........................................................................................................................... 98

1111 W

Waarrrraannttyy...................................................................................................................................................................................................................................................................................................... 9999

11.1 Limited Factory Warranty for Three-Phase Eaton 93PM UPS and 93PM UPS Accessory Products ............................ 99

Table of Contents

Содержание 93PM-50-1

Страница 1: ...p n P 164000569 Revision 03 50 kW 480V Three Wire UL 924 50 kW 480V Four Wire UL 924 Installation and Operation Manual Eaton 93PM Emergency Lighting UPS ...

Страница 2: ...uced in any way without the express written approval of Eaton IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important instructions that you should follow during installation and maintenance of the UPS and batteries Please read all instructions before operating the equipment and save this manual for future reference CONSIGNES DE SÉCURITÉ IMPORTANTES CONSERVER CES INSTRU...

Страница 3: ...System Configurations 6 1 5 Using This Manual 6 1 6 Conventions Used in This Manual 6 1 7 Symbols Controls and Indicators 7 1 8 For More Information 7 1 9 Getting Help 8 1 10 Equipment Registration 8 2 2 S Sa af fe et ty y W Wa ar rn niin ng gs s 9 9 3 3 U UP PS S I In ns st ta alllla at tiio on n P Plla an n a an nd d U Un np pa ac ck kiin ng g 1 11 1 3 1 Creating an Installation Plan 11 3 2 Prep...

Страница 4: ... System Mode 57 5 2 3 Normal Mode 58 5 2 4 Bypass Mode 59 5 2 5 Battery Mode 60 6 6 U UP PS S O On ne elliin ne e S Sc ch he em ma at tiic cs s 6 61 1 7 7 U UP PS S O Op pe er ra at tiin ng g I In ns st tr ru uc ct tiio on ns s 6 67 7 7 1 UPS Controls and Indicators 67 7 1 1 Control Panel 67 7 1 2 Circuit Breakers 68 7 2 Using the Control Panel 68 7 2 1 Status Indicators 69 7 2 2 System Events 70 ...

Страница 5: ...90 8 4 1 PredictPulse Service Features 90 8 4 2 Installing PredictPulse 91 9 9 U UP PS S M Ma aiin nt te en na an nc ce e 9 93 3 9 1 Important Safety Instructions 93 9 2 Performing Preventive Maintenance 93 9 2 1 DAILY Maintenance 94 9 2 2 MONTHLY Maintenance 94 9 2 3 PERIODIC Maintenance 95 9 2 4 ANNUAL Maintenance 95 9 2 5 BATTERY Maintenance 95 9 3 Installing Batteries 96 9 4 Recycling the Used...

Страница 6: ...vi Eaton 93PM Emergency Lighting UPS 50 kW 480V Three and Four Wire UL 924 Installation and Operation Manual P 164000569 Rev 03 Table of Contents ...

Страница 7: ... Rear Shipping Bracket Eaton 93PM UPS 33 Figure 15 UPS Conduit and Wire Entry Locations 35 Figure 16 Sidecar Conduit and Wire Entry Locations 36 Figure 17 UPS Inter Cabinet Wiring Access Location 37 Figure 18 Power Terminal Locations 38 Figure 19 Power Terminal Detail 39 Figure 20 Interface Terminal Locations 41 Figure 21 Interface Terminal Detail 41 Figure 22 Bottom Access Interface Wiring Locati...

Страница 8: ...Screen 72 Figure 48 Typical Meters Summary Screen 74 Figure 49 Typical Active Events Screen 75 Figure 50 Typical System Log Screen 75 Figure 51 Typical Settings User Screen 76 Figure 52 Typical Information Screen 76 Figure 53 Typical About Screen 77 Figure 54 Typical Settings Configuration 1 Screen 77 Figure 55 Typical Settings Configuration 2 Screen 78 Figure 56 Typical Statistics Screen 78 Figur...

Страница 9: ...ons for the Eaton 93PM 50 1 23 Table 7 Power Cable Conduit Recommendations for the Eaton 93PM 50 1 24 Table 8 Recommended Input and Bypass Circuit Breaker Ratings 25 Table 9 Recommended Output Circuit Breaker Ratings 25 Table 10 Building Alarm Connections and Wire Terminations 43 Table 11 Relay Contact Connections and Wire Terminations 44 Table 12 External Battery Detect and Shunt Trip Connections...

Страница 10: ...x Eaton 93PM Emergency Lighting UPS 50 kW 480V Three and Four Wire UL 924 Installation and Operation Manual P 164000569 Rev 03 List of Tables ...

Страница 11: ...r available for top entry wiring Figure 1 shows the Eaton 93PM 50 kW Three or Four Wire UL 924 UPS and Figure 2 shows the Eaton 93PM 50 kW Three or Four Wire UL 924 UPS with a left or right mounted sidecar NOTE Startup and operational checks must be performed by an authorized Eaton Customer Service Engineer or the warranty terms specified in Chapter 11 Warranty become void This service is offered ...

Страница 12: ... Installation and Operation Manual P 164000569 Rev 03 Figure 1 Eaton 93PM UPS 50 kW Three or Four Wire UL 924 Figure 2 Eaton 93PM UPS 50 kW Three or Four Wire UL 924 with Left or Right Mounted Sidecar UPS with Left Mounted UPS with Right Mounted Sidecar Sidecar Introduction ...

Страница 13: ...tructions for additional information 1 1 1 1 5 5 I In nt te er rn na all R Re ed du un nd da an nc cy y To deliver greater reliability the Eaton 93PM UPS can be configured for internal redundancy When configured the UPS automatically becomes redundant if the load is at or below the capacity of the UPMs minus the capacity of one UPM Under normal conditions the UPMs in the UPS share the load equally...

Страница 14: ... feeder circuit breakers and battery breakers are opened 1 1 2 2 O Op pt tiio on ns s a an nd d A Ac cc ce es ss so or riie es s Contact an Eaton sales representative for information about the following options 1 1 2 2 1 1 I In nt te eg gr ra at te ed d B Ba at tt te er ry y C Ca ab biin ne et t Battery backup protection with additional runtime can be provided by equipping the UPS system with up t...

Страница 15: ...hts about past and current performance a list of all active alarms and asset management data i e battery date codes last and next scheduled service dates firmware versions The service notifies customers of critical alarms supports remote diagnostics and facilitates smart dispatch of technicians PredictPulse requires a Power Xpert Gateway Minislot PXGMS connectivity card in an Minislot communicatio...

Страница 16: ...ter 1 Introduction through Chapter 4 UPS System Installation and Chapter 7 UPS Operating Instructions should be examined Read through each procedure before beginning work Perform only those procedures that apply to the UPS system being installed or operated 1 1 6 6 C Co on nv ve en nt tiio on ns s U Us se ed d iin n T Th hiis s M Ma an nu ua all This manual uses these type conventions Bold type hi...

Страница 17: ...nformation contact your local recycling reuse or hazardous waste center This symbol indicates that you should not discard waste electrical or electronic equipment WEEE in the trash For proper disposal contact your local recycling reuse or hazardous waste center Eaton Powerware and BladeUPS are registered trademarks of Eaton Corporation or its subsidiaries and affiliates Phillips and Pozidriv are r...

Страница 18: ...estion this manual does not answer Please call the Customer Reliability Center at United States 1 800 843 9433 Canada 1 800 461 9166 ext 260 All other countries Call your local service representative Please use the following e mail address for manual comments suggestions or to report an error in this manual E ESSDocumentation eaton com 1 1 1 10 0 E Eq qu uiip pm me en nt t R Re eg giis st tr ra at...

Страница 19: ...inants Ambient temperature must not exceed 40 C 104 F Do not operate near water or excessive humidity 95 maximum The system is not intended for outdoor use As a result of the connected loads high leakage current is possible Connection to earth ground is required for safety and proper product operation Do not check UPS operation by any action that includes removal of the earth ground connection wit...

Страница 20: ...nside the unit Do not install or operate the UPS system close to gas or electric heat sources Lead acid batteries can present a risk of fire because they generate hydrogen gas Do not smoke when near batteries Do not cause flame or spark in battery area Discharge static electricity from body before touching batteries by first touching a grounded metal surface The operating environment should be mai...

Страница 21: ...tand how this manual applies to the system being installed Use the procedures and illustrations in paragraph 3 2 Preparing the Site and Chapter 4 UPS System Installation to create a logical plan for installing the system 3 3 2 2 P Pr re ep pa ar riin ng g t th he e S Siit te e For the UPS system to operate at peak efficiency the installation site should meet the environmental parameters outlined i...

Страница 22: ...Load Operation Model UPS Rating Input Output Voltage Heat Rejection BTU hr x1000 kg cal hr Minimum Required Cooling Air Flow Eaton 93PM 50 1 20 kW 480 480 2 55 643 189 liter sec 400 cfm Eaton 93PM 50 1 30 kW 480 480 3 58 903 Eaton 93PM 50 1 40 kW 480 480 4 56 1150 The UPS equipment operating environment must meet the weight requirements shown in Table 3 and the size requirements shown in Figure 3 ...

Страница 23: ...gure 4 457 2 mm 18 working space From Top of Cabinet with rear service access Zone 2 see Figure 4 Can be less than 457 2 mm 18 From Back of Cabinet with Rear Exhaust 254 mm 10 minimum clearance for ventilation From Back of Cabinet with Top Exhaust None Required From Back of Cabinet Seismic Installation 914 4 mm 36 working space From Right Side of Cabinet None Required From Left Side of Cabinet Non...

Страница 24: ...d Four Wire UL 924 Installation and Operation Manual P 164000569 Rev 03 Figure 4 UPS Cabinet Dimensions Top and Bottom Views FRONT FRONT TOP BOTTOM NOTE Top exhaust configuration shown Dimensions are in millimeters inches UPS Installation Plan and Unpacking ...

Страница 25: ...n and Operation Manual P 164000569 Rev 03 15 Figure 5 UPS Cabinet Front and Back Floor Mounting Bracket Mounting Dimensions Back Views UPS UPS with Left Mounted Sidecar NOTE Examples shown with top exhaust option Dimensions are in millimeters inches UPS Installation Plan and Unpacking ...

Страница 26: ...Operation Manual P 164000569 Rev 03 Figure 6 UPS Cabinet with Left Mounted or Right Mounted Sidecar Dimensions Front and Right Side Views 1880 74 762 30 762 30 UPS with Left Mounted Sidecar UPS with Right Mounted Sidecar Dimensions are in millimeters inches UPS Installation Plan and Unpacking ...

Страница 27: ...nual P 164000569 Rev 03 17 Figure 7 UPS Cabinet with Left Mounted or Right Mounted Sidecar Dimensions Top and Bottom Views Top Top Front Front Front Front Bottom Bottom UPS with Left Mounted Sidecar UPS with Right Mounted Sidecar Dimensions are in millimeters inches UPS Installation Plan and Unpacking ...

Страница 28: ...n Manual P 164000569 Rev 03 Figure 8 UPS Cabinet Center of Gravity Dimensions are in millimeters Inches Weight and Center of Gravity letters A B and C map to Figure 8 A mm in B mm in C mm in Installed Weight kg lb Eaton 93PM 50 1 UPS 985 38 7 560 22 273 10 7 318 702 UPS Installation Plan and Unpacking ...

Страница 29: ...m in C mm in Installed Weight kg lb Eaton 93PM 50 1 UPS with Top Entry Wiring Sidecar no breakers 961 37 8 561 22 406 16 0 402 887 Eaton 93PM 50 1 UPS with SIAC B 4 Breaker 964 37 9 586 23 386 15 2 429 947 Weight and Center of Gravity with Right Mounted Sidecar letters A B and C map to Figure 9 A mm in B mm in C mm in Installed Weight kg lb Eaton 93PM 50 1 UPS with Top Entry Wiring Sidecar no brea...

Страница 30: ...g only If wire is run in an ambient temperature greater than 30 C larger size wire may be necessary Wire sizes are based on using the specified breakers The AC output and output ground wiring to the critical load should be sized the same as the UPS rectifier bypass and rectifier and bypass ground wiring if the recommended output breaker listed in Table 9 is not installed in the system Recommended ...

Страница 31: ... the UPS and the maintenance bypass For external wiring recommendations including the minimum AWG size of external wiring see Table 5 Wire sizes listed are for copper wiring only Table 5 Input Output Ratings and External Wiring Recommendations for the Eaton 93PM 50 1 Basic Unit Rating Units Rating 50 60 Hz kW 20 30 40 Input and Output Voltage Volts 480 480 480 480 480 480 AC Input to UPS Rectifier...

Страница 32: ...d Neutral if 4 Wire Number per Phase AWG or kcmil each 8 1 6 1 4 1 Minimum Conductor Size Ground Number AWG or kcmil each 10 1 10 1 8 1 NOTE Callout letters A B C and D map to the Oneline Schematics detailed in Chapter 6 UPS Oneline Schematics NOTE Line up and match battery wiring with a 105 C rating is factory supplied with the Eaton 93PM Integrated Battery Cabinet IBC NOTE The neutral conductor ...

Страница 33: ... Input from Battery E4 Battery 4 6 300 kcmil 31 0 275 1 4 Hex E5 Battery 4 6 300 kcmil 31 0 275 1 4 Hex Customer Ground Ground Ground 6 14 1 0 kcmil 5 1 45 Slotted NOTE Customer ground sized in accordance with NEC Table 250 122 can be run in any conduit listed in Table 7 Conduit sizes were chosen from NEC Table 4 Electrical Metallic Tubing EMT See Table 7 for conduit requirements Per NEC article 3...

Страница 34: ...put to UPS Bypass A B C Neutral Ground 5 4 wire UPS or 4 3 wire UPS 1 1 4 1 AC Output A B C Neutral Ground 5 4 wire UPS or 4 3 wire UPS 1 1 4 1 DC Battery Positive Negative Ground 3 1 1 2 2 Eaton 93PM 50 1 40 kW 480 Vac AC Input to UPS Rectifier A B C Ground 4 1 1 4 1 AC Input to UPS Bypass A B C Neutral Ground 5 4 wire UPS or 4 3 wire UPS 1 1 4 1 AC Output A B C Neutral Ground 5 4 wire UPS or 4 3...

Страница 35: ...critical load shown in Table 5 The recommended line to line load unbalance is 50 or less Bypass and output overcurrent protection and bypass and output disconnect switches are to be supplied by the customer Table 9 lists the recommended rating for output circuit breakers Table 9 Recommended Output Circuit Breaker Ratings Output Rating UPS Model UPS Rating Load Rating 480V Eaton 93PM 50 1 20 kW 80 ...

Страница 36: ...ted for a minimum of 600V Use twisted pair wires for each input and return or common All interface wiring and conduit is to be supplied by the customer When installing external interface wiring between a building alarm relay output battery breaker trip or Minislot and the UPS interface terminals conduit must be installed between each device and the UPS cabinet If using conduit install the interfac...

Страница 37: ...wing step verify that the forklift or pallet jack is rated to handle the weight of the cabinet see Table 3 for cabinet weight 2 Use a forklift or pallet jack to move the packaged cabinet to the installation site or as close as possible before unpacking If possible move the cabinet using the pallet Insert the forklift or pallet jack forks between the supports on the bottom of the pallet see Figure ...

Страница 38: ...nstallation and Operation Manual P 164000569 Rev 03 Figure 10 UPS Cabinet as Shipped on Pallet Figure 11 UPS Cabinet with Left Mounted or Right Mounted Sidecar as Shipped on Pallet UPS with Left Mounted Sidecar UPS with Right Mounted Sidecar UPS Installation Plan and Unpacking ...

Страница 39: ... damage may occur Ensure the forklift is rated to handle the weight of the cabinet Failure to follow these instructions may result in severe injury or death NOTE For the following steps verify that the forklift or pallet jack is rated to handle the weight of the cabinet see Table 3 for cabinet weight The UPS cabinet is bolted to a pallet consisting of four metal angle supports secured to two wood ...

Страница 40: ... instructed Failure to follow these instructions may result in severe injury or death 4 Loosen but do not remove the skid mounting bolts holding the pallet skids to the front and rear supports and to the left and right side supports see Figure 12 5 If a sidecar is attached to the UPS loosen but do not remove the sidecar skid mounting bolts holding the sidecar pallet skids to the sidecar front and ...

Страница 41: ...Recycle the pallet skids and hardware in a responsible manner CAUTION CABINET MAY FALL Do not loosen the hardware attaching the front supports to the cabinet base The cabinet must be lowered by the jacking bolts before the supports can be removed 10 Carefully and evenly lower the cabinet by turning each jacking bolt consecutively two full turns maximum until the casters contact the floor and the c...

Страница 42: ...p panels Retain the hardware for later use 24 Install the top splice bracket between the adjacent cabinet and secure the tie strap with retained hardware NOTE Either front and back floor mounting brackets or left and right side floor mounting brackets are available for permanently mounting the UPS 25 If permanently mounting the UPS using the left and right side floor mounting brackets proceed to S...

Страница 43: ... IBC is installed proceed to paragraph 4 4 Sidecar Integrated Accessory Cabinet Bypass Wiring Installation if a Sidecar Integrated Accessory Cabinet Bypass SIAC B is attached to the UPS 4 4 4 4 S Siid de ec ca ar r I In nt te eg gr ra at te ed d A Ac cc ce es ss so or ry y C Ca ab biin ne et t B By yp pa as ss s W Wiir riin ng g I In ns st ta alllla at tiio on n If an SIAC B is attached to the UPS...

Страница 44: ...igure 16 from the top of the sidecar Identify all conduit requirements and mark their location Drill and punch all conduit holes in the top conduit plate prior to mounting on the sidecar Install the conduit plate and install all conduit runs into the plate Pull the wiring through the conduit into the wiring area 10 Route the input and output cables through the top of the UPS sidecar and the UPS in...

Страница 45: ...re 15 UPS Conduit and Wire Entry Locations Top Entry Conduit Landings for Customer Interface Wiring Bottom Entry Conduit Landings for Customer Interface Wiring Bottom Entry Conduit Landing for AC Input and Output and DC Input Front Bottom View Top View Front NOTE Remove panels to drill or punch conduit holes UPS System Installation ...

Страница 46: ...s Bottom Entry Conduit Landing for DC Input Bottom Entry Conduit Landings for Customer Interface Wiring Bottom Entry Conduit Landing for AC Input and Output Top Entry Conduit Landing for AC Input and Output and DC Input Top Entry Conduit Landings for Customer Interface Wiring Top View Front Bottom View NOTE Remove panels to drill or punch conduit holes UPS System Installation ...

Страница 47: ...l P 164000569 Rev 03 37 Figure 17 UPS Inter Cabinet Wiring Access Location Inter cabinet wiring access to route interface wiring between cabinets Inter cabinet wiring access knockouts Remove knockouts as required to route power wiring between cabinets Left Side View Right Side View UPS System Installation ...

Страница 48: ...UL 924 Installation and Operation Manual P 164000569 Rev 03 Figure 18 Power Terminal Locations AC Input to UPS Bypass DC Input from Battery A B C Neutral if 4 wire AC Input to UPS Rectifier AC Output to Critical Load A B C A B C Neutral if 4 wire UPS System Installation ...

Страница 49: ...d Battery Cabinet Installation Manual Large and Large High Rate the Eaton 93PM Integrated Battery Cabinet Installation Manual Small or the Eaton 93PM Integrated Battery Cabinet Installation Manual Small Welded listed in paragraph 1 8 For More Information See Figure 15 Figure 16 and Figure 17 for wiring access information and Figure 18 for terminal locations 2 Connect the positive negative and grou...

Страница 50: ...for wiring access information and Figure 20 and Figure 21 for UPS interface terminal locations 7 Proceed to Step 13 8 Bottom Entry Wiring Remove the bottom interface entry conduit landing plates to drill or punch holes see Figure 22 9 Reinstall the interface entry plates and install the conduit 10 Route the UPS building alarm and relay output interface wiring through the bottom interface entry con...

Страница 51: ...NTerminals Minislot Communication Bays InterfaceTerminals Top of UPS Figure 21 Interface Terminal Detail Minislot Communication Bay 2 Minislot Communication Bay 1 Minislot Communication Bay 3 Minislot Communication Bay 4 Cabinet Stiffener Bar RS 232 Host USB Pull Chain and CAN Terminals Device USB Relay Output Terminals REPO Terminals Building Alarm Terminals UPS System Installation ...

Страница 52: ...Four Wire UL 924 Installation and Operation Manual P 164000569 Rev 03 Figure 22 Bottom Access Interface Wiring Locations WireTie Anchors Bottom Access Interface Wiring Channel Bottom Entry Conduit Landings for Customer Interface Wiring UPS System Installation ...

Страница 53: ...ote dry contact closure Twisted Pair Wires 18 AWG 14 30 AWG 2 lb in 0 22 0 25 Nm 9 Building Alarm 1 Return 8 Building Alarm 2 Input Programmable UPS alarm activated by a remote dry contact closure 7 Building Alarm 2 Return 6 Building Alarm 3 Input Programmable UPS alarm activated by a remote dry contact closure 5 Building Alarm 3 Return 4 Building Alarm 4 Input Programmable UPS alarm activated by ...

Страница 54: ...eneral purpose normally closed NO relay contact Twisted Pair Wires 18 AWG 14 30 AWG 2 lb in 0 22 0 25 Nm 3 Relay Contact Common Figure 25 Relay Contact Terminal Block Connector Assignments UPS Relay Output 1 2 3 NO_Out NC_Out Com 4 4 7 7 2 2 I In ns st ta alllliin ng g B Ba at tt te er ry y D De et te ec ct t a an nd d S Sh hu un nt t T Tr riip p I In nt te er rf fa ac ce e C Co on nn ne ec ct tii...

Страница 55: ...he battery detect and shunt trip wiring from the battery cabinet or battery disconnect through the bottom of the UPS to the UPS battery detect and shunt trip terminals See Figure 15 for UPS wiring access information and Figure 26 for UPS terminal locations 8 Proceed to Step 10 9 Top Entry Wiring Route the battery detect and shunt trip wiring from the battery cabinet or battery disconnect through t...

Страница 56: ... Lighting UPS 50 kW 480V Three and Four Wire UL 924 Installation and Operation Manual P 164000569 Rev 03 Figure 26 Battery Detect and Shunt Trip Terminal Locations Battery Detect and ShuntTripTerminals UPS System Installation ...

Страница 57: ...Trip Connections and Wire Terminations Terminal Name Description Recommended Wire Size Size of Pressure Termination Tightening Torque 5 VCC Output Signal used to open battery breaker or disconnect Twisted Pair Wires 18 AWG Use wire rated for 600V and Class 1 wiring methods 12 22 AWG 5 7 lb in 0 56 0 79 Nm 6 Battery Shunt Trip 7 Battery Shunt Detect Input Signal used to indicate an open battery bre...

Страница 58: ...als See Figure 17 for UPS wiring access information and Figure 29 for UPS terminal locations Refer to the Eaton 93PM Integrated Battery Cabinet Installation Manual Large and Large High Rate the Eaton 93PM Universal Integrated Battery Cabinet Installation Manual Large and Large High Rate the Eaton 93PM Integrated Battery Cabinet Installation Manual Small or the Eaton 93PM Integrated Battery Cabinet...

Страница 59: ...moved reinstall the sidecar front panel and secure with the retained hardware 15 Close the UPS outside door and secure the latch Figure 29 Thermal Sensor Terminal Location Thermal Sensor Terminals Figure 30 Thermal Sensor Terminal Assignments Thermal Sensor Thermal Sensor Return Jumper Jumper Thermal Sensor TB11 UPS System Installation ...

Страница 60: ...g Torque 1 Jumper Used to select battery configuration Twisted Pair Wires 18 AWG Use wire rated for 600V and Class 1 wiring methods 12 22 AWG 5 7 lb in 0 56 0 79 Nm 2 Jumper 3 Thermal Sensor Input Used to signal a battery temperature out of specification and to turn off the battery charger to prevent thermal runaway 4 Thermal Sensor Return Figure 31 Thermal Sensor Jumper Assignments 1 2 3 4 UPS Th...

Страница 61: ...e interface terminals from the bottom of the UPS proceed to Step 8 otherwise proceed to Step 4 4 Top Entry Wiring Remove the top interface entry conduit landing plates to drill or punch holes see Figure 15 5 Reinstall the interface entry plates and install the conduit 6 Route the UPS building alarm interface wiring through the top interface entry conduit landing plates to the UPS building alarm te...

Страница 62: ...ot card locations 7 Proceed to Step 13 8 Remove the bottom interface entry conduit landing plate to drill or punch holes see Figure 22 9 Reinstall the interface entry plate and install the conduit 10 Route the Minislot card interface wiring through the bottom interface entry conduit landing plate to the bottom access interface wiring channel along the inside of the front door see Figure 22 11 Rout...

Страница 63: ...nduits and cables are properly routed to the UPS and any ancillary cabinets o All power cables are properly sized and terminated o Battery cables are terminated on E4 and E5 o Battery shunt trip signal wiring is connected from the UPS to the battery cabinet or battery disconnect o Battery detect signal wiring is connected from the UPS to the battery cabinet or battery disconnect o Battery thermal ...

Страница 64: ...____________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ ___________________________________________________________...

Страница 65: ...pter 9 Product Specifications the UPS uses a backup battery supply to maintain power to the critical load for a specified period of time or until the utility power returns For extended power outages the UPS allows you to either transfer to an alternative power system such as a generator or shut down your critical load in an orderly manner The emergency bypass consists of a continuous static switch...

Страница 66: ... different modes of operation In Energy Saver System ESS mode commercial AC power is supplied directly to the critical load through the internal bypass and transfers automatically to Normal mode double conversion on demand if an abnormal condition is detected The battery charger also provides charging current for the battery if needed In Normal double conversion mode the critical load is supplied ...

Страница 67: ...or incoming power quality and allow the fast engagement of power converters Typical transition time to double conversion is less than two milliseconds which is practically seamless If the UPS detects a fault condition while operating in ESS it is also able to detect and determine whether the fault is caused by the load or if it is upstream from the UPS A fault at the bypass source results in an im...

Страница 68: ... customer s load without the use of a transformer The inverter derives regulated DC from the rectifier and uses IGBT devices and pulse width modulation PWM to produce a regulated and filtered AC output The AC output of the inverter is delivered to the system output through the inverter switchgear If the utility AC power is interrupted or is out of specification the UPS automatically switches to Ba...

Страница 69: ... the Bypass mode of operation The internal bypass is comprised of a solid state silicon controlled rectifier SCR continuous static switch and bypass switchgear The static switch is used instantaneously anytime the inverter is unable to support the applied load The continuous static switch is wired in series with the bypass switchgear and together they are wired in parallel with the rectifier and i...

Страница 70: ... the input power fails to return or is not within the acceptance windows required for normal operation the battery continues discharging until a DC voltage level is reached where the inverter output can no longer support the connected loads When this event occurs the UPS issues another set of audible and visual alarms indicating SHUTDOWN IMMINENT Unless the rectifier has a valid AC input soon the ...

Страница 71: ...t to UPS Rectifier 3 Wire A B C Rotation AC Input to UPS Bypass 3 Wire A B C Rotation E1 E2 E3 A B D C UPS CABINET External Battery Cabinet Not supplied with the UPS E6 E7 E8 Optional Single Feed Jumper Fuse Fuse Fuse Fuse Rectifier Switchgear Rectifier Inverter Inverter Switchgear Battery Converter Battery Switchgear E4 E5 Battery Breaker Bypass Switchgear Static Swtich AC Output to Critical Load...

Страница 72: ...n E1 E2 E3 A B D C UPS CABINET External Battery Cabinet Not supplied with the UPS E6 E7 E8 E12 Optional Single Feed Jumper Fuse Fuse Fuse Fuse Rectifier Switchgear Rectifier Inverter Inverter Switchgear Battery Converter Battery Switchgear E4 E5 Battery Breaker Bypass Switchgear Static Swtich AC Output to Critical Load E9 E10 E11 E12 Interface Board CB1 Input Breaker UPM NOTE Dashed lines indicate...

Страница 73: ... B D C NOTE Dashed lines indicate optional features components AC Input to rectifier is not used in single feed configuration Pull Chain Parallel CAN Mini Slot Interface Interface Board External Battery Cabinet Not supplied with the UPS AC Output to Critical Load AC Input to UPS Bypass 3 Wire A B C Rotation AC Input to UPS Rectifier 3 Wire A B C Rotation TOP ENTRY UPS CABINET SIDECAR UPS Oneline S...

Страница 74: ...B D C NOTE Dashed lines indicate optional features components AC Input to rectifier is not used in single feed configuration Pull Chain Parallel CAN Mini Slot Interface Interface Board External Battery Cabinet Not supplied with the UPS AC Output to Critical Load AC Input to UPS Bypass 4 Wire A B C Rotation AC Input to UPS Rectifier 3 Wire A B C Rotation TOP ENTRY UPS CABINET SIDECAR UPS Oneline Sc...

Страница 75: ...tem Oneline UPM A B D C NOTE Dashed lines indicate optional features components AC Input to rectifier is not used in single feed configuration Pull Chain Parallel CAN Mini Slot Interface Interface Board External Battery Cabinet Not supplied with the UPS AC Output to Critical Load AC Input to UPS Bypass 3 Wire A B C Rotation AC Input to UPS Rectifier 3 Wire A B C Rotation UPS Oneline Schematics ...

Страница 76: ...em Oneline UPM A B D C NOTE Dashed lines indicate optional features components AC Input to rectifier is not used in single feed configuration Pull Chain Parallel CAN Mini Slot Interface Interface Board External Battery Cabinet Not supplied with the UPS AC Output to Critical Load AC Input to UPS Bypass 4 Wire A B C Rotation AC Input to UPS Rectifier 3 Wire A B C Rotation UPS Oneline Schematics ...

Страница 77: ...ates properly NOTE Read this section of the manual and have thorough knowledge of UPS operation before attempting to operate any of the controls 7 7 1 1 U UP PS S C Co on nt tr ro olls s a an nd d I In nd diic ca at to or rs s The controls and indicators identified and described in this section are used to set up control and monitor UPS operation Figure 43 shows the control panel location on the f...

Страница 78: ...reaker The Input circuit breaker is used to control the AC input to the UPS rectifier Figure 44 AC Input Circuit Breaker Location Input Breaker 7 7 2 2 U Us siin ng g t th he e C Co on nt tr ro oll P Pa an ne ell The following paragraphs describe the UPS control panel including controls and indicators and how to monitor UPS operation The control panel is shown in Figure 45 UPS Operating Instructio...

Страница 79: ... tu us s I In nd diic ca at to or rs s The four symbols on the bottom of the control panel are status indicators These colored light emitting diode LED lamps work with the alarm horn to provide the operating status of the UPS Table 14 describes the status indicators Table 14 Status Indicators Indicator Status Description Green On The UPS is in Double Conversion mode The power module is supplying p...

Страница 80: ... Operation System Event Horns The system event horn beeps to alert an operator that an event needing attention is taking place The horn cycles at a half second rate To silence the horn touch any control panel button System Event Indicators The status indicators on the UPS control panel work with the event horn to let the operator know when the UPS is operating in any mode other than double convers...

Страница 81: ...data operational controls acknowledgments action confirmations and screen prompts You can use the LCD touch screen to Look at a log of UPS events alarms notices and commands see paragraph 7 2 6 Display Menu Operation Monitor UPS operation see paragraph 7 2 6 Display Menu Operation Set UPS parameters see paragraph 7 2 6 Display Menu Operation Control UPS operation see paragraphs 7 2 6 Display Menu ...

Страница 82: ...nclude date and time for the time stamp display language the unit name meter subscripts password and view the firmware version numbers Used only by service personnel NOTE Screens shown are representative examples of system operation The screen data will vary based on system activity at the time of observation 7 7 2 2 5 5 M Miim miic c S Sc cr re ee en n Figure 47 shows the Main Menu and Mimic scre...

Страница 83: ...tab on the main menu navigation bar to display an overview of UPS operation including information on load efficiency and consumption If there is an error an error indicator is displayed next to the affected part Active events log can be opened by tapping the error indicator UPS Module Map Tap the UPS MODULE MAP tab on the secondary menu navigation bar to display the status of each UPM System Overv...

Страница 84: ...RATION tab on the secondary menu navigation bar to display the screen Tap the function to be changed Make and save the changes Follow screen prompts to accept or abort changes For additional functions tap the 2 button See Figure 54 and Figure 55 for configuration screens Statistics Statistics Summary Tap the STATISTICS tab on the main menu navigation bar to display a summary of UPS statistics see ...

Страница 85: ...rgency Lighting UPS 50 kW 480V Three and Four Wire UL 924 Installation and Operation Manual P 164000569 Rev 03 75 Figure 49 Typical Active Events Screen Figure 50 Typical System Log Screen UPS Operating Instructions ...

Страница 86: ...Emergency Lighting UPS 50 kW 480V Three and Four Wire UL 924 Installation and Operation Manual P 164000569 Rev 03 Figure 51 Typical Settings User Screen Figure 52 Typical Information Screen UPS Operating Instructions ...

Страница 87: ...ncy Lighting UPS 50 kW 480V Three and Four Wire UL 924 Installation and Operation Manual P 164000569 Rev 03 77 Figure 53 Typical About Screen Figure 54 Typical Settings Configuration 1 Screen UPS Operating Instructions ...

Страница 88: ...re 56 Typical Statistics Screen 7 7 2 2 7 7 S Siig gn n I In n The Controls and Setting screens are restricted The user must sign in using a password to gain access CAUTION To prevent inadvertent or unauthorized power disruption to the emergency lighting system change the Level 1 and Level 2 default passwords when system commissioning startup is performed UPS Operating Instructions ...

Страница 89: ...of the screen The sign in screen is displayed see Figure 57 2 Tap the password entry area on the screen 3 Enter the password using the keypad displayed and tap the return key see Figure 58 Level 1 default password is 1111 Settings Level 2 default password is 0101 4 Sign in is complete Tap continue to return to previous screen Figure 57 Sign In Password Screen UPS Operating Instructions ...

Страница 90: ...the typical System Status Screen Messages that are displayed during UPS operation For UPS operating instructions using the System Controls see paragraph 7 3 Single UPS Operation Figure 59 through Figure 63 show the major control screens Table 17 Controls Menu Operation Function Subfunction Operation System Controls The CONTROLS tab on the main menu navigation bar displays the System Controls scree...

Страница 91: ...24 Installation and Operation Manual P 164000569 Rev 03 81 Table 18 Typical System Status Messages Function Message UPS Double Conversion Bypass ESS Bypass Off On Available Charger Charger Resting Charger Figure 59 Typical System Control Screen UPS Operating Instructions ...

Страница 92: ... Emergency Lighting UPS 50 kW 480V Three and Four Wire UL 924 Installation and Operation Manual P 164000569 Rev 03 Figure 60 Typical UPS Control Screen Figure 61 Typical UPM Select Screen UPS Operating Instructions ...

Страница 93: ...he location of the Integrated Battery Cabinet s IBC battery breaker refer to the Eaton 93PM Integrated Battery Cabinet Installation Manual Large and Large High Rate the Eaton 93PM Universal Integrated Battery Cabinet Installation Manual Large and Large High Rate the Eaton 93PM Integrated Battery Cabinet Installation Manual Small or Eaton 93PM Integrated Battery Cabinet Installation Manual Small We...

Страница 94: ...IBCs are installed close the IBC battery breakers 8 Observe the UPS control panel display becoming active indicating logic power 9 Verify no alarms are active 10 Tap the CONTROLS tab on the main menu navigation bar The System Control screen is displayed 11 Tap the GO ONLINE button 12 If requested enter the Level 1 password Default password is 1111 The rectifier and inverter turn on The inverter co...

Страница 95: ...ve the UPS control panel becoming active indicating logic power 8 Verify no alarms are active 9 Tap the CONTROLS tab on the main menu navigation bar The System Control screen is displayed 10 Tap the MODULES CONTROLS tab on the secondary Control menu navigation bar The UPM Select screen is displayed 11 On the UPM Select screen select UPM 1 The UPM Control Screen is displayed 12 Tap the START MODULE...

Страница 96: ...o ou ub blle e C Co on nv ve er rs siio on n M Mo od de e t to o E ES SS S M Mo od de e To transfer the load to HE Normal mode 1 Tap the CONTROLS tab on the main menu navigation bar The Control screen is displayed 2 Tap the EAA CONTROLS tab on the secondary Control menu navigation bar The EAA CONTROLS screen is displayed 3 Tap the ENABLE ESS button The UPS transfers to ESS mode if no abnormal powe...

Страница 97: ... UPS bypass feeder circuit breaker 9 If IBCs are installed open all battery breakers 7 7 3 3 1 10 0 C Ch ha ar rg ge er r C Co on nt tr ro oll To turn the battery charger on 1 Tap the CONTROLS tab on the main menu navigation bar The Control screen is displayed 2 Tap the UPS CONTROLS tab on the secondary navigation bar The UPS Control screen is displayed 3 Tap the TURN ON CHARGER button To turn the...

Страница 98: ...l load Selecting NO will abort the shutdown CAUTION Do not attempt to restart the system after Load Off until the cause of the shutdown has been identified and cleared 3 To restart the UPS after using the LOAD OFF follow the procedure in paragraph 7 3 1 Starting the UPS in Double Conversion Mode or 7 3 2 Starting the UPS in Bypass Mode WARNING Power is present inside the UPS cabinet until the upst...

Страница 99: ...y Card Minislot IRC MS can be used to indicate the operating status of the UPS system using the customer s monitoring equipment The Industrial Relay Card uses five isolated normally open or normally closed dry relay contacts to indicate the UPS status Normal Bypass Battery and Alarm modes can be monitored See Table 19 for default triggers The contact ratings and wire range are listed in the IRC MS...

Страница 100: ...ter the initial warranty expires PredictPulse may also be subscribed to for free as part of a 90 day trial period PredictPulse availability and first year bundled offers may vary by market For more information visit www eaton com predictpulse 8 8 4 4 1 1 P Pr re ed diic ct tP Pu ulls se e S Se er rv viic ce e F Fe ea at tu ur re es s PredictPulse provides proactive monitoring an online dashboard m...

Страница 101: ... 4 2 2 I In ns st ta alllliin ng g P Pr re ed diic ct tP Pu ulls se e A quick start guide and self installation wizard tool are available at www eaton com predictpulse The latest updates installation tips and information on connecting PredictPulse are also available at that link For installation support or questions about PredictPulse contact predictpulsesupport eaton com PredictPulse relies on a ...

Страница 102: ...92 Eaton 93PM Emergency Lighting UPS 50 kW 480V Three and Four Wire UL 924 Installation and Operation Manual P 164000569 Rev 03 Communication ...

Страница 103: ...tions about the electrical state of any cabinet in the UPS system Each battery string is an energy source in itself DO NOT ATTEMPT TO ACCESS ANY INTERNAL AREA OF THE BATTERY STRING YOURSELF VOLTAGES ARE ALWAYS PRESENT IN THE BATTERY STRING If you suspect that a battery string needs service contact an Eaton service representative If the string requires service contact an Eaton service representativ...

Страница 104: ...sentative 9 9 2 2 2 2 M MO ON NT TH HL LY Y M Ma aiin nt te en na an nc ce e Perform the following steps monthly 1 Monitor system parameters as described in paragraph 7 2 Using the Control Panel 2 Check the UPS air filter located behind the front door and wash or replace as necessary See Figure 65 for filter location Contact an Eaton service representative for replacement filters CAUTION Verify wa...

Страница 105: ...nance procedures should specify that the compression lug connections be retorqued to values listed in this manual 9 9 2 2 4 4 A AN NN NU UA AL L M Ma aiin nt te en na an nc ce e Annual preventive maintenance should be performed only by authorized service personnel familiar with maintenance and servicing of the UPS system Contact an Eaton service representative for more information about service of...

Страница 106: ...ng are examples of symbols used on the UPS or accessories to alert you to important information RISK OF ELECTRIC SHOCK Observe the warning associated with the risk of electric shock symbol CAUTION REFER TO OPERATOR S MANUAL Refer to your operator s manual for additional information such as important operating and maintenance instructions This symbol indicates that you should not discard the UPS or...

Страница 107: ...np pu ut t Operating Input Voltage Rectifier 480 Vac Wye 3W ground Neutral not used Bypass 480 Vac Wye 3W or 4W ground Operating Input Frequency Range 50 60 Hz Operating Input Current See Table 5 Reduced for Generator Adjustable Input Current Harmonic Content 3 THD at full load Power Factor Minimum 0 99 Line Surges 6 kV OC 3 kA SC per ANSI 62 41 and IEC 801 4 Battery Voltage 240 cell 480 Vdc Batte...

Страница 108: ...erature is 25 C 77 F Operating Altitude Maximum 1500m 5000 ft at 30 C without derating Storage Temperature 25 to 55 C excluding batteries prolonged storage above 40 C causes rapid battery self discharge Relative Humidity operating and storage 5 to 95 noncondensing Acoustical Noise 50 kW at 100 load 65 dBA at a 1m distance per ISO 7779 Agency Markings UL 924 Emergency Lighting and Power Equipment S...

Страница 109: ...ined by Eaton Any parts that are replaced may be new or reconditioned All parts replaced by Eaton shall become the property of Eaton LIMITED WARRANTY PERIOD The period covered by this Warranty for Product installed and currently located in the fifty 50 United States and the District of Columbia is six 6 months from the date of Product purchase for labor coverage when no startup is performed by an ...

Страница 110: ...to receive the benefits of this Warranty the End User must register the product warranty via mail or online at www eaton com pq register product registration use the Product in a normal way follow the Product s user s guide and protect against further damage to the Product if there is a covered defect OTHER LIMITATIONS Eaton s obligations under this Warranty are expressly conditioned upon receipt ...

Страница 111: ...Eaton 93PM Emergency Lighting UPS 50 kW 480V Three and Four Wire UL 924 Installation and Operation Manual P 164000569 Rev 03 101 Warranty ...

Страница 112: ...P 16400056903 P 164000569 03 ...