Eaton 93PM Emergency Lighting UPS (50 kW, 480V Three and Four-Wire UL 924) Installation and Operation Manual P-164000569—Rev 03
25
Table 8. Recommended Input and Bypass Circuit Breaker Ratings
Input Rating
UPS Model
UPS Rating
Load Rating
480V
Eaton 93PM-50-1
20 kW
80% Rated
70A
100% Rated
50A
Eaton 93PM-50-1
30 kW
80% Rated
80A
100% Rated
70A
Eaton 93PM-50-1
40 kW
80% Rated
100A
100% Rated
80A
CAUTION
To reduce the risk of fire, connect only to a circuit provided with maximum input circuit breaker current ratings
from
in accordance with the NEC, ANSI/NFPA 70.
The line-to-line unbalanced output capability of the UPS is limited only by the full load per phase current values
for AC output to critical load shown in
. The recommended line-to-line load unbalance is 50% or less.
Bypass and output overcurrent protection and bypass and output disconnect switches are to be supplied by the
customer.
lists the recommended rating for output circuit breakers.
Table 9. Recommended Output Circuit Breaker Ratings
Output Rating
UPS Model
UPS Rating
Load Rating
480V
Eaton 93PM-50-1
20 kW
80% Rated
35A
100% Rated
25A
Eaton 93PM-50-1
30 kW
80% Rated
50A
100% Rated
40A
Eaton 93PM-50-1
40 kW
80% Rated
70A
100% Rated
50A
No manual DC disconnect device is provided within the UPS.
Battery voltage is computed at 2 volts per cell as defined by Article 480 of the NEC. Rated battery current is
computed based on 2 volts per cell.
For details on the type of batteries and number of battery cabinets required for the Eaton 93PM Emergency
Lighting UPS, refer to
.