22. Route output cables to the branch circuit breakers and wire the branch circuits according to the branch
circuit breaker manufacturer's ratings and instructions, and national and local electrical codes (input is
prewired to the panelboard). See Figure 4-17 for neutral and ground terminal locations, Table 3-3 for wiring
requirements, and Table 3-5 for termination requirements.
23. If wiring an IAC-D with subfeed breakers, continue to Step 24; otherwise, skip to Step 26.
24. Route output cables from subfeed breakers to the critical load. See Figure 4-17 for neutral and ground
terminal locations, Table 3-3 for wiring requirements and Table 3-5 for termination requirements.
25. Connect phase A, B, and C, Neutral, and Ground power wiring to the subfeed breakers (see Figure 4-18)
and the critical load. See Figure 4-17 for neutral and ground terminal locations, Table 3-3 for wiring
requirements, and Table 3-5 for termination requirements.
26. Reinstall the inside terminal cover plate removed in Step 20.
27. Close the inside door and secure with screws.
28. Close the outside door and secure the latch.
29. After the IAC-D is installed and wired, return to the applicable Eaton 93E UPS installation and operation
manual listed in paragraph 1.7 to complete the UPS wiring.
Figure 4-11. Input Power Terminal Locations – 93E 30IAC-D
NOTE
When wiring subfeed branch circuits, begin adding conduits at the back of the
bottom or top of the rear conduit landing plates to simplify future circuit additions.
Ground Terminals
(See Figure 4-12 for detail.)
Neutral Terminals
(See Figure 4-12 for detail.)
AC Input to IAC-D (A, B, C)
(See Figure 4-12 for detail.)