background image

I.B. 3A74499B

Page 12

Effective 11/97

SECTION 4: INSTALLATION

BEFORE PLACING THE BREAKER IN SERVICE,
CAREFULLY FOLLOW THE INSTALLATION PROCE-
DURE GIVEN BELOW. NOT FOLLOWING THE PRO-
CEDURE CAN FAIL TO UNCOVER SHIPPING DAM-
AGE THAT MAY RESULT IN INCORRECT BREAKER
OPERATION LEADING TO DEATH, BODILY INJURY,
AND PROPERTY DAMAGE.

4-1  INITIAL INSPECTION AND OPERATION

Before attempting to put the breaker in service, it should
be carefully examined and operated manually and elec-
trically. Examine a breaker for loose or obviously dam-
aged parts.

4-2  MANUAL OPERATION CHECK

Place the maintenance tool into the manual charge
socket opening and charge the closing springs with
about 3 up and down strokes of the handle. When
charging is complete, the closing crank goes over center
with an audible "click" and the springs Charged /
Discharged indicator shows "Charged".

If the springs are to be charged on a closed breaker,
no click is heard at the end of charging operation.
Discontinue charging and remove the maintenance
tool as soon as "Charged" flag is fully visible.
Continued attempts to further charge may result in
damage to the mechanism. Remove the mainte-
nance tool. Close and trip the breaker several
times (Figure 4.1).

4-3  VACUUM INTERRUPTER INTEGRITY

Using a dry lint free cloth or paper towel, clean all the
insulating surfaces of the pole units. Conduct a vacuum
interrupter integrity check as described in Section 6.4.

4-4  INSULATION

Check breaker primary and secondary insulation per
Section 6.7.

4-5  CONTACT EROSION AND WIPE

Manually charge the closing springs and close the

breaker. Check contact erosion and wipe as described
in Section 6.5.

4-6  PRIMARY CIRCUIT RESISTANCE

Check the primary circuit resistance as described in
Section 6.8  The resistance should not exceed the val-
ues specified. Record the values obtained for future ref-
erence.

4-7  NAMEPLATE

Compare the breaker nameplate information with
switchgear drawings for compatibility.

4-8  ELECTRICAL OPERATIONS CHECK

After going through the above steps, the breaker is now
ready to be operated electrically. It is preferred that this
check be made with the breaker in a test position or by
using a test cable.

EXAMINE THE INSIDE OF THE CELL BEFORE
INSERTING THE BREAKER FOR EXCESSIVE DIRT
OR ANYTHING THAT MIGHT INTERFERE WITH THE
BREAKER TRAVEL.

EXTREME CAUTION MUST BE EXERCISED TO
INSURE THAT PRIMARY CIRCUITS ARE NOT ENER-
GIZED WHILE CHECKS ARE PREFORMED IN THE
BREAKER COMPARTMENT. FAILURE TO DO SO
MAY RESULT IN PERSONAL INJURY OR DEATH.

When testing the breaker electrically, a TEST position
is accomplished using several methods. The method
used depends on the switchgear structure approach
being utilized.

a1) If the breaker is being used in the behind the door
configuration, the structure mounted secondary contact
blocks can be manually engaged with the breaker's sec-
ondary contacts. This is accomplished with the breaker
still inside the  structure and the primary contacts dis-
connected.

a2) If the breaker is being used in a flushmounted con-
figuration, the breaker must be moved to the discon-
nected position for testing. It is recommended that a test
cable be used to connect the female and male sec-

!

CAUTION

!

WARNING

!

WARNING

NOTICE

Содержание 36W-VAC25

Страница 1: ...1993 Cutler Hammer Instructions for Installation Operation and Maintenance of Type W VAC Vacuum Circuit Breakers W VAC Breaker Element W VAC Breaker with Carriage Assembly for SIngle Tier Switchgear W...

Страница 2: ......

Страница 3: ...LD BE ATTEMPTED ONLY BY QUALIFIED PERSONNEL THIS INSTRUCTION BOOK SHOULD NOT BE CON SIDERED ALL INCLUSIVE REGARDING INSTALLA TION OR MAINTENANCE PROCEDURES IF FUR THER INFORMATION IS REQUIRED YOU SHOU...

Страница 4: ...t Interface Check 13 SECTION 5 DESCRIPTION AND OPERATION 5 1 Interrupter Assembly 16 5 1 1 Vacuum Interrupter 16 5 1 2 Contact Erosion Indicator 17 5 1 3 T Cutout Loading Spring Indicator 17 5 1 4 Con...

Страница 5: ...Warning 25 6 2 Frequency 25 6 3 Inspection and Maintenance Procedures 26 6 4 Vacuum Interrupter Integrity Test 27 6 5 Contact Erosion and Wipe 27 6 6 Insulation 28 6 7 Insulation Integrity Check 28 6...

Страница 6: ...reaker Manual Operation Single Tier Breaker Shown 13 5 1 Flush Mounted Configuration 16 5 2 Behind the Door Configuration 17 5 3 Closeup of Type W VAC Breaker Vacuum Interrupters and Current Carrying...

Страница 7: ...W VAC BREAKERS ARE PROTECTIVE DEVICES AS SUCH THEY ARE MAXIMUM RATED DEVICES THEREFORE THEY SHOULD NOT UNDER ANY CIRCUMSTANCES BE APPLIED OUT SIDE THEIR NAMEPLATE RATINGS WARNING Table 1 1 Type W VAC...

Страница 8: ...he hf 3L h3Le he hf S hS L h W he Y h Y J h U he hf H h V he hf he N he hf 3 hf J he W he V4 L h U he hf N h V he3L hf H h S hf J he W he Y L h U hf N h V he hf H h hf L h X he X hf J h N1 heV H h N...

Страница 9: ...V M 5 7 V H e hf 3L e N V h Xg X h X X h V h V e N1 hS N1 h L Lh7H h X f31 X T5 Xe Xe J5 Xe X h he X e e e e fS5 V Y V eV g U hf e f g f V f V hJ 1 h N1 h H f Y V h7 h J h h 3L f hf h Lhe S J h3 V h 7...

Страница 10: ...not work on a breaker with the secondary test cou pler engaged Failure to disconnect the test coupler could result in an electrical shock leading to death per sonal injury or property damage Do not wo...

Страница 11: ...for any signs of damage or rough handing Open the con tainer carefully to avoid any damage to the contents When opening the container be careful that any loose items or hardware are not discarded with...

Страница 12: ...cks should be made to make sure that the breaker is free from shipping dam age and is in satisfactory operating condition The breaker is shipped with its contacts open and clos ing springs discharged...

Страница 13: ...97 Figure 3 2 Type W VAC breaker element faceplate 1 2 3 8 7 4 5 6 Front Panel Manual Charge Socket Open Closed Indicator Spring Charged Discharged Indicator Operation Counter Rating Nameplate Manual...

Страница 14: ...1 2 3 4 5 L H Closing Spring Anti pump Relay Auxiliary Switch Motor Cutoff Switch Closing Cam Spring Release Close Coil Assembly Shunt Trip Assembly Position Switch Charging Motor Charging Pawl Ratch...

Страница 15: ...4 Rear external view of W VAC breaker element 1 Secondary Disconnect Lifter Yoke Opening Support Insulator Primary Disconnect Vacuum Interrupter Contact Loading Spring Wipe Spring Operating Rod Drive...

Страница 16: ...view W VAC breaker with carriage assembly for single tier switchgear Side View Rear View Mechanism Enclosure Support Insulator Primary Disconnect Levering in Screw Carriage Carriage Wheel Shoot Bolt...

Страница 17: ...VAC breaker with cradle assembly for double tier switchgear Front View Rear View Mechanism Enclosure Support Insulator Primary Disconnect Levering in Screw Cradle Cradle Wheel Shutter Operator Leveri...

Страница 18: ...TACT EROSION AND WIPE Manually charge the closing springs and close the breaker Check contact erosion and wipe as described in Section 6 5 4 6 PRIMARY CIRCUIT RESISTANCE Check the primary circuit resi...

Страница 19: ...Type W VAC breaker manual operation single tier breaker shown a Inserting the maintenance tool into the manual charging socket b Lifting shoot lever permits insertion of levering crank c Manually clos...

Страница 20: ...Anti Close Interlock This interlock prevents releasing the closing springs electrically or manually if the breaker is already closed d Anti Latch Interlock This interlock prevents the breaker from bei...

Страница 21: ...sembly version lift the shoot bolt lever and pull the breaker out The breaker will close and trip as it comes out from the Test position 2 For the double tier configuration cradle assembly version ret...

Страница 22: ...is racked into the fully connected position Possibility 3 The basic breaker element combined with a cradle assembly is used for double tier switchgear This combination is only for use in a behind the...

Страница 23: ...is located on the moving stem of the interrupter Figures 6 2 and 6 3 In order to determine if the contacts have eroded to the extent that the interrupter must be replaced close the breaker and observ...

Страница 24: ...ed to the support molding resulting in the support molding being enclosed on all four vertical sides Figure 5 4 5 2 STORED ENERGY MECHANISM KEEP HANDS AND FINGERS AWAY FROM THE BREAKER S INTERNAL PART...

Страница 25: ...gh the main link to close the breaker In Figure 5 5c the linkage is shown with the breaker in the closed position before the closing springs have been recharged Interference of the trip D shaft with t...

Страница 26: ...T XV X W T h V XV T R Ug N L N R XV U N1g W 3L X V S X Y V I 3 eW R h eV4 UeW g W XfV 7H 0R T T KS5 g 0R R40Y e 6T e W eI Y O g W Yh 0Y 7H hfV L g 3L f Kh V X S 3 O e eV X f he Y e V40Y h3Le S e f e h...

Страница 27: ...e V h g f e e V e e g hf f e e e e f W hf e f Y e e f J5 W2 Y h Xe f fW2 e U heV Me V e hf f g f W g W hO U he f Y f 0Y V g T e f f e eV U O K W V g 0R4 e f Y J5 Y X X V X e f f g J LV f X S Xh e e T...

Страница 28: ...nted male plugs To disengage the sec ondary plugs from the TEST position simply push the carriage to the rear 5 3 3 UNDERVOLTAGE TRIP DEVICE The undervoltage trip device for W VAC breakers is an elect...

Страница 29: ...d by the breaker operating shaft prevents the levering crank from being inserted with the breaker in the Closed position 5 4 3 ANTI CLOSE INTERLOCK This interlock prevents releasing the closing spring...

Страница 30: ...6Xg gW 6K f e W 1 6K f gW2 6Kg g O2 6X W2 6Kg f W2 X W26Kg Lg O2 6X gO2 6X N N X W 6K H 3 X J L W2 5 W2 6X 7 W2 W26X 3 K e f O 5 X f f W H 6X eJ eW 5 6X e Lf O f f O2 1 7 6Xf fW 1 7 6XfJ 1f W2 1 W2 6X...

Страница 31: ...he g V he 3T5 f Y eS 0 Me Hhe X 3T Xh N H g W 7UfV U O he h V e W V X g g U V U he U N R g 3L g N1 S he h X e V h N1 g U he g S g g S1 he Y e W g he h 7H g f 3Lhe g f h 3L hf eV he h 3L X V hf 3T X he...

Страница 32: ...7H 7 L heS5 75 7H V f 3 h X he f N1 e R4 g S S g He hV g O he X f gV g 7H e 5 X e S S g g L e V X U he fO2 f X V h 3L 3Lg he Ke X f e e7He U g W e f h U he S f h f e V Xe 7H 7 heW e 31 1 Le N1 heN1 31...

Страница 33: ...free cloth Primary Disconnects No burning or damage Visual Check Replace if burned damaged or eroded 3 Control Closing and Tripping Device Smooth and correct Test closing and tripping Replace any defe...

Страница 34: ...uld have sufficient volt ampere capacity It is recommended that the equipment be capable of delivering 25 milliamperes for one minute Although an ac high potential test is recommended a dc test may be...

Страница 35: ...55812CA or commercial equivalent Secondary control wiring requires inspection for tightness of all connections and damage to insulation 6 7 INSULATION INTEGRITY CHECK Primary Circuit The integrity of...

Страница 36: ...c These bearings are packed at the factory with a top grade slow oxidizing grease which normally should be effective for many years They should not be disturbed unless there is definite evidence of sl...

Страница 37: ...ood grease solvent Don not use carbon tetracholride They should then be washed in light machine oil until the cleaner is removed After the oil has been drawn off the bearings should be packed with Cut...

Страница 38: ...itch off Secondary Disconnects Motor Cut off Switch Poor or burned contacts Lever not operational Terminals and connectors Poor or burned contacts Motor Brushes worn or commutator segment open Mechani...

Страница 39: ...ch or trip bar not reset Auxiliary Switch b contact open or burned Motor Cut off Contacts open or burned Trip Coil Assembly Clapper fails to reset Pole Shaft Not open fully Trip Latch Reset Spring Dam...

Страница 40: ...en Terminals and Connections Poor or burned or open Trip Mechanism Trip Clapper Jammed Trip Bar Trip Latch Jammed Trip Sound Trip Mechanism Pole Shaft Jammed Operating Rod Assembly Broken or pins out...

Страница 41: ...and con tinuity requirements Each customer should develop his own stock level based on operating experience Refer to Table 7 1 for guidance 7 2 ORDERING INSTRUCTIONS a Always specify the breaker rati...

Страница 42: ...W M I MI Y hg Y X hf h 31 hf g V hf 3 6T KO2 W26Xhe S 40R4 U 0R X h 6T T W Yf B 9e h X S U 7U T K C MB hf V4 0R R N U H f g U S 6T T2 h J R MI R R he Y V Yh g h hf h hf h hf h hf h hf h h h e f h M h...

Страница 43: ...125 VAC Cap trip 3759A76G02 1 220 250 VDC 220 250 VAC Cap trip 3759A76G03 1 15 UV Trip Coils 48 VDC 8067A19G01 1 110 125 VDC 8067A19G02 1 220 250 VDC 8067A19G03 1 16 Motor Cut Off Switch 5677B02G01 1...

Страница 44: ...ard 691C662G01 1 UV 691C666G01 1 21 Trip Latch Hatchet 699B040G01 1 22 Cluster Assembly 630A 699B104G01 1 800 1250A 508B022G01 1 1600 2000A 5677B328G01 1 23 Shock Absorber 5677B26H01 1 W f hf e h 6K W...

Страница 45: ...I B 3A74499B Page 39 Effective 11 97...

Страница 46: ...I B 3A74499B Page 40 Effective 11 97...

Страница 47: ...I B 3A74499B Page 41 Effective 11 97...

Страница 48: ...e contract between the purchaser and Cutler Hammer NO WARRANTIES EXPRESSED OR IMPLIED INCLUDING WARRANTIES OF FITNESS FOR A PAR TICULAR PURPOSE OR MERCHANTABILITY OR WARRANTIES ARISING FROM COURSE OF...

Отзывы: